W6D910-GA01-01 ebm-papst 400VAC 910mm AC Axial Panel Fan

$980.00

ebm-papst W6D910-GA01-01 (W6D910GA0101) 400VAC 910mm 3-phase HyBlade axial panel fan, 885/685RPM, 19190CFM, 2480/1570W, with square full nozzle, M6D138-NA & IP54.

SKU: W6D910-GA01-01 Category: Brand:

Description

ebm-papst W6D910-GA01-01 (also known as W6D910GA0101) is a heavy-duty 3-phase AC axial panel fan from the S series featuring a 910 mm (35.83 in) 5-blade sickle-shaped HyBlade impeller integrated into a galvanized and black plastic-coated (RAL 9005) square full nozzle with a guard grille. Powered by an external-rotor M6D138-NA motor (size 138), this dual-speed (Delta/Star) unit operates on 400 VAC at 50 Hz, delivering up to 19,190 CFM (32,605 m³/h) free-air airflow in Delta connection (885 RPM nominal at 2,480 W / 5.4 A) or 15,860 CFM (26,945 m³/h) in Star connection (685 RPM nominal at 1,570 W / 2.9 A) against up to 150 Pa (0.60 in H₂O) nominal static pressure.

Engineered for harsh industrial environments, it incorporates hybrid aluminum-insert PP-sprayed composite blades, maintenance-free ball bearings, IP54 and H2 moisture protection, rotor/stator condensation drainage holes, and a PP terminal box with lead-out auto-reset thermal overload protection (TOP).

Key Features

  • Dual-Speed Delta/Star 3-Phase Operation: Configurable 400 VAC 50 Hz windings provide 885 RPM (2,480 W) in Delta or 685 RPM (1,570 W) in Star connection.
  • High-Volume HyBlade Aerodynamics: Five 0°-pitch sickle-shaped hybrid composite blades deliver up to 19,190 CFM (32,605 m³/h) free-air flow and 157 Pa ErP pressure.
  • Square Full Nozzle & Guard Architecture: Galvanized sheet steel full nozzle and steel guard grille coated in black plastic (RAL 9005) include FlowGrid mounting holes.
  • IP54 & H2 Wet-Environment Durability: Cast-aluminum rotor, Class F insulation, and dual-side condensation drainage holes withstand direct water exposure from -40 °C to +50 °C.
  • Integrated Thermal Overload Protection: Equipped with an auto-reset thermal switch (TOP) wired to the PP plastic terminal box for reliable continuous S1 duty.
  • ErP Ecodesign Directive Compliant: Achieves 37% overall static efficiency (ηes) and Efficiency Grade N 40.9 per EU Regulation 327/2011 without requiring a VSD.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) W6D910-GA01-01
Alternate Part Number W6D910GA0101
OEM Item Number 10563-5-9980
Integrated Motor Model M6D138-NA (Motor Size 138)
Product Series HyBlade S Series (Sickle-Shaped Blades with Square Full Nozzle)
Product Category AC Axial Fans
Fan / Component Type AC Axial Panel Fan with Square Full Nozzle & Guard Grille
Motor Design / Technology 3-Phase AC External Rotor Induction Motor (6-Pole, Dual-Speed Δ/Y)
Phase & Supply Type 3~ (3-Phase AC, Delta Δ / Star Y Configurable)
Rated Voltage 400 VAC
Frequency 50 Hz
Speed (Max. Load – Delta Δ) 885 RPM (at 150 Pa / 0.60 in H₂O)
Speed (Max. Load – Star Y) 685 RPM (at 90 Pa / 0.36 in H₂O nominal; 87 Pa curve point 8)
Free-Air Speed (RPM – Delta Δ) 925 RPM (at 0 Pa, Curve Point 1)
Free-Air Speed (RPM – Star Y) 785 RPM (at 0 Pa, Curve Point 5)
ErP Optimum Speed (RPM) 900 RPM (at 157 Pa / 0.631 in H₂O)
Intermediate Curve Speeds (Delta Δ) 910 RPM (at 50 Pa, Pt 2); 900 RPM (at 100 Pa, Pt 3)
Intermediate Curve Speeds (Star Y) 745 RPM (at 32 Pa, Pt 6); 715 RPM (at 61 Pa, Pt 7)
Power Rating (Max. Load – Delta Δ) 2,480 W (2.48 kW)
Power Rating (Max. Load – Star Y) 1,570 W (1.57 kW)
Free-Air Power Input (Delta Δ) 1,848 W (at 0 Pa, Curve Point 1)
Free-Air Power Input (Star Y) 1,290 W (at 0 Pa, Curve Point 5)
ErP Optimum Efficiency Power 2,460 W (2.46 kW)
Intermediate Curve Power Input (Delta Δ) 2,084 W (at 50 Pa, Pt 2); 2,298 W (at 100 Pa, Pt 3)
Intermediate Curve Power Input (Star Y) 1,412 W (at 32 Pa, Pt 6); 1,491 W (at 61 Pa, Pt 7)
Rated Current (Max. Load – Delta Δ) 5.4 A (Nominal Data) / 5.15 A (Measured Curve Point 4)
Rated Current (Max. Load – Star Y) 2.9 A (Nominal Data & Measured Curve Point 8)
Free-Air Current Draw (Delta Δ) 4.31 A (at 0 Pa, Curve Point 1)
Free-Air Current Draw (Star Y) 2.44 A (at 0 Pa, Curve Point 5)
Intermediate Curve Current Draw (Delta Δ) 4.59 A (at 50 Pa, Pt 2); 4.86 A (at 100 Pa, Pt 3)
Intermediate Curve Current Draw (Star Y) 2.67 A (at 32 Pa, Pt 6); 2.82 A (at 61 Pa, Pt 7)
Inrush / Starting Current (Delta Δ) 18.6 A
Inrush / Starting Current (Star Y) 6.2 A
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air – Delta Δ) 19,190 CFM (32,605 m³/h) at 0 Pa (Curve Point 1)
Airflow (Max. Free Air – Star Y) 15,860 CFM (26,945 m³/h) at 0 Pa (Curve Point 5)
Operating Duty Point Airflow (Delta Δ) 17,230 CFM (29,275 m³/h) at 0.20 in H₂O (50 Pa, Pt 2); 15,020 CFM (25,515 m³/h) at 0.40 in H₂O (100 Pa, Pt 3); 12,235 CFM (20,790 m³/h) at 0.60 in H₂O (150 Pa, Pt 4 Max. Load)
Operating Duty Point Airflow (Star Y) 13,800 CFM (23,445 m³/h) at 0.13 in H₂O (32 Pa, Pt 6); 11,725 CFM (19,925 m³/h) at 0.24 in H₂O (61 Pa, Pt 7); 9,305 CFM (15,805 m³/h) at 0.35 in H₂O (87 Pa, Pt 8 Max. Load)
ErP Optimum Efficiency Duty Point 13,034 CFM (22,145 m³/h) at 0.631 in H₂O (157 Pa)
Max. Static Pressure (Delta Δ) 0.60 in H₂O (150 Pa) Nominal Max. Back Pressure / 0.631 in H₂O (157 Pa) ErP Optimum
Max. Static Pressure (Star Y) 0.36 in H₂O (90 Pa) Nominal Max. Back Pressure / 0.35 in H₂O (87 Pa) Curve Point 8
Sound Pressure Level (Delta Δ Intake) 70 dB(A) at Free Air (Pt 1) & Max. Load (Pt 4); 69 dB(A) at 50 Pa (Pt 2); 68 dB(A) at 100 Pa (Pt 3) (at 1 m)
Sound Pressure Level (Star Y Intake) 65 dB(A) at Free Air (Pt 5); 63 dB(A) at 32 Pa (Pt 6) & Max. Load (Pt 8); 61 dB(A) at 61 Pa (Pt 7) (at 1 m)
Sound Power Level (Delta Δ Intake / Outlet) Pt 1 (0 Pa): 78 / 78 dB(A); Pt 2 (50 Pa): 76 / 77 dB(A); Pt 3 (100 Pa): 76 / 76 dB(A); Pt 4 (150 Pa): 77 / 77 dB(A)
Sound Power Level (Star Y Intake / Outlet) Pt 5 (0 Pa): 73 / 73 dB(A); Pt 6 (32 Pa): 70 / 70 dB(A); Pt 7 (61 Pa): 69 / 69 dB(A); Pt 8 (87 Pa): 71 / 70 dB(A)
ErP Efficiency & Grade (EU 327/2011) Overall Static Efficiency ηes = 37.0% (Req. 2015: 36.1%); Efficiency Grade N = 40.9 (Req. 40); Measurement Category A; Efficiency Category Static; Specific Ratio = 1.00; VSD = No (Air Duct Ref: LU-183158)
Air Density Reference (ISO 5801 Cat. A) 1.15 kg/m³ ± 2%
Airflow Direction V (Intake Over Stator / Struts, Exhaust Over Rotor)
Ingress Protection (IP) IP54
Moisture / Environmental Class H2 (Wet – Direct Exposure to Water)
Operating Temperature -40 °C to +50 °C (-40 °F to +122 °F) (Continuous operation down to -25 °C; occasional start-up permitted between -40 °C and -25 °C)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) Auto-Reset Thermal Switch, Lead Out, with Basic Insulation
Electrical Protection Class Class I (With Protective Earth Connected)
Touch Current (IEC 60990) <= 3.5 mA (Measuring Circuit Fig. 4, TN System)
Insulation Class Class F
Termination Type Terminal Box (PP Plastic, Tightening Torque 1.5 ± 0.2 Nm)
Cable Exit Orientation Axial
Conduit / Cable Gland Ports Cable Diameter Min. 7 mm (0.28 in) to Max. 14 mm (0.55 in), Gland Tightening Torque 2.0 ± 0.3 Nm
Wiring Pinout / Connection L1 = U1 (Black), L2 = V1 (Blue), L3 = W1 (Brown), W2 (Yellow), U2 (Green), V2 (White), TOP Thermal Switch (2x Gray), PE Protective Earth (Green/Yellow)
Impeller Size Ø 910 mm (35.83 in)
Weight 52.4 kg (115.52 lbs)
Blade Count & Geometry 5 Sickle-Shaped HyBlade Blades (S Series), 0° Blade Pitch
Bearing Type Ball Bearing
Terminal Box Material PP Plastic
Housing / Scroll / Frame Material Sheet Steel, Galvanized and Coated with Black Plastic (RAL 9005)
Impeller / Blade Material Sheet Aluminum Insert, Sprayed with PP Plastic (HyBlade Hybrid Composite)
Guard Grille Material Steel, Coated with Black Plastic (RAL 9005)
Rotor Surface Cast in Aluminum
Direction of Rotation Clockwise, Viewed Toward Rotor
Installation Position Any
Condensation Drainage Holes On Rotor and Stator Sides
Compatible Accessories (Optional) FlowGrid Air Inlet Grill (Part No. 91000-2-2957, Attachment Holes Provided)
Standards & Compliance EN 60034-1 (2010), CE, UKCA, VDE, EAC, EU 327/2011 (prEN 17166), ISO 5801 Cat. A, ISO 13347

Applications

The ebm-papst W6D910-GA01-01 AC axial panel fan is engineered for high-volume heat rejection in commercial and industrial air-cooled condensers, chillers, dry coolers, and large HVAC heat exchangers. Its corrosion-resistant square full nozzle, IP54/H2 wet-environment rating, and dual-speed Delta/Star flexibility make it ideal for outdoor refrigeration condensing units, industrial process cooling towers, and heavy-duty ventilation plenums operating in demanding climates. Built-in attachment points for an optional FlowGrid inlet grille further support low-noise OEM installations and direct MRO replacements in noise-sensitive rooftop or perimeter machinery.