S4D350-AN22-77 ebm-papst 400/480VAC 350mm AC Axial Fan

$823.00

ebm-papst S4D350-AN22-77 (S4D350AN2277) 400/480VAC 350mm 3-phase axial fan, 930/990RPM, 1475/1585CFM, 95/135W, with guard grille, M4D074-DF motor & IP44.

SKU: S4D350-AN22-77 Category: Brand:

Description

ebm-papst S4D350-AN22-77 (also known as S4D350AN2277, OEM Item No. 13422-5-9980) is an industrial three-phase S-series AC axial fan with a 350 mm (13.78 in) 5-blade sickle-shaped impeller and an integrated guard grille for short nozzle installation, powered by the M4D074-DF external rotor motor. Operating in star (Y) connection across 400 VAC (50/60 Hz) and 480 VAC (60 Hz) supplies, it delivers up to 1,475 CFM (2,505 m³/h) at 50 Hz free air and 1,585 CFM (2,695 m³/h) at 480 VAC 60 Hz free air, with nominal max-load ratings of 930 RPM / 95 W (400 VAC 50 Hz), 830 RPM / 100 W (400 VAC 60 Hz), and 990 RPM / 135 W (480 VAC 60 Hz).

Engineered for demanding thermal environments down to -40 °C (-40 °F), the unit features press-fitted sheet steel blades sprayed with polypropylene (PP) plastic, a black plastic-coated phosphated steel guard grille, ball bearings with low-temperature lubricant, IP44 ingress protection, F2-2 moisture protection, and an internal thermal overload protector (TOP) with a separately included terminal box.

Key Features

  • Multi-Voltage 3-Phase Star Operation: Supports 400 VAC (50/60 Hz) and 480 VAC (60 Hz) three-phase star (Y) power supplies.
  • High-Volume Sickle-Blade Aerodynamics: 5 sickle-shaped blades deliver 1,475 CFM (50 Hz) and 1,585 CFM (480 VAC 60 Hz) free-air flow.
  • Hybrid PP-Coated Steel Impeller: Press-fitted sheet steel blades sprayed with polypropylene plastic paired with a black-coated phosphated steel guard grille.
  • Extreme Low-Temperature Bearing System: Ball bearings with specialized low-temperature lubricant support operation from -40 °C up to +80 °C.
  • IP44 & F2-2 Environmental Rating: Combines IP44 protection, F2-2 environmental rating, Class F insulation, and rotor-side condensation drainage holes.
  • Thermal Overload & Terminal Kit: Integrated thermal overload protector (TOP) wired via PFA AWG 20 leads with a separate terminal box.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) S4D350-AN22-77
Alternate Part Number S4D350AN2277
OEM Item Number 13422-5-9980 (Change 89188)
Integrated Motor Model M4D074-DF
Product Series S Series (Sickle-Shaped Blades with Guard Grille for Short Nozzle)
Product Category AC Axial Fans
Fan / Component Type AC Axial Fan with Guard Grille
Motor Design / Technology 3-Phase AC External Rotor Induction Motor (4-Pole)
Phase & Supply Type 3~ (Three-Phase AC), Star (Y) Connection
Rated Voltage 400 VAC (50/60 Hz) / 480 VAC (60 Hz)
Frequency 50 / 60 Hz
Speed (Max. Load) 930 RPM (400 VAC, 50 Hz) / 830 RPM (400 VAC, 60 Hz) / 990 RPM (480 VAC, 60 Hz)
Free-Air Speed (RPM) 1080 RPM (400 VAC, 50 Hz) / 985 RPM (400 VAC, 60 Hz) / 1160 RPM (480 VAC, 60 Hz)
Power Rating (Max. Load) 95 W (400 VAC, 50 Hz) / 100 W (400 VAC, 60 Hz) / 135 W (480 VAC, 60 Hz)
Free-Air Power Input 80 W (400 VAC, 50 Hz) / 94 W (400 VAC, 60 Hz) / 119 W (480 VAC, 60 Hz)
Rated Current (Max. Load) 0.16 A (400 VAC, 50 Hz) / 0.17 A (400 VAC, 60 Hz) / 0.18 A (480 VAC, 60 Hz)
Free-Air Current Draw 0.13 A (400 VAC, 50 Hz) / 0.16 A (400 VAC, 60 Hz) / 0.16 A (480 VAC, 60 Hz)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 1475 CFM / 2505 m³/h (400 VAC, 50 Hz) / 1350 CFM / 2295 m³/h (400 VAC, 60 Hz) / 1585 CFM / 2695 m³/h (480 VAC, 60 Hz)
Operating Duty Point Airflow (400 VAC, 50 Hz) Pt 2: 1260 CFM (2135 m³/h) at 0.06 in H₂O (15 Pa), 1025 RPM, 85 W, 0.14 A; Pt 3: 1040 CFM (1770 m³/h) at 0.12 in H₂O (30 Pa), 980 RPM, 89 W, 0.15 A; Pt 4 (Max. Load): 810 CFM (1380 m³/h) at 0.16 in H₂O (40 Pa), 930 RPM, 95 W, 0.16 A
Operating Duty Point Airflow (480 VAC, 60 Hz) Pt 2: 1375 CFM (2335 m³/h) at 0.06 in H₂O (14 Pa), 1100 RPM, 124 W, 0.17 A; Pt 3: 1170 CFM (1985 m³/h) at 0.11 in H₂O (28 Pa), 1045 RPM, 128 W, 0.17 A; Pt 4 (Max. Load): 880 CFM (1500 m³/h) at 0.17 in H₂O (42 Pa), 990 RPM, 135 W, 0.18 A
Operating Duty Point Airflow (400 VAC, 60 Hz) Pt 6: 1150 CFM (1955 m³/h) at 0.04 in H₂O (10 Pa), 925 RPM, 96 W, 0.16 A; Pt 7: 985 CFM (1675 m³/h) at 0.08 in H₂O (20 Pa), 880 RPM, 98 W, 0.16 A; Pt 8 (Max. Load): 740 CFM (1255 m³/h) at 0.12 in H₂O (30 Pa), 830 RPM, 100 W, 0.17 A
Max. Static Pressure 0.16 in H₂O / 40 Pa (400 VAC, 50 Hz) / 0.12 in H₂O / 30 Pa (400 VAC, 60 Hz) / 0.17 in H₂O / 42 Pa (480 VAC, 60 Hz)
Aerodynamic Measurement Setup ISO 5801 Installation Category A (50 Hz: LU-140571-1; 60 Hz: LU-140577-1 & LU-140575-1)
Airflow Direction “V” (Intake over Guard Grille / Struts, Exhaust over Rotor)
Ingress Protection (IP) IP44 (Installation- and Position-Dependent per EN 60034-5)
Moisture / Environmental Class F2-2
Operating Temperature (400 VAC, 50 Hz) -40 °C to +80 °C (-40 °F to +176 °F)
Operating Temperature (400 VAC, 60 Hz) -40 °C to +65 °C (-40 °F to +149 °F)
Operating Temperature (480 VAC, 60 Hz) -40 °C to +55 °C (-40 °F to +131 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) with Basic Insulation (To Be Connected in Customer Circuit)
Electrical Protection Class Class I (With Customer Connection of Protective Earth)
Touch Current (IEC 60990) < 0.75 mA (Measuring Circuit Fig. 4, TN System)
Insulation Class Class “F”
Termination Type Lead Wires with 6x Crimped Splices (Terminal Box Included Separately)
Cable Exit Orientation Variable Cable Exit
Lead Wire Gauge & Spec PFA Cable, AWG 20 (PE Green/Yellow AWG 18)
Wiring Pinout / Connection Star (Y) Connection: L1 (U1) = Black, L2 (V1) = Blue, L3 (W1) = Brown, PE = Green/Yellow, TOP = 2x Gray (Reversing Two Phases Changes Rotation Direction)
Impeller Size Ø 350 mm (13.78 in)
Weight 4.7 kg (10.36 lbs)
Blade Count & Geometry 5 Sickle-Shaped Blades (S Series)
Bearing Type Ball Bearing with Low-Temperature Lubricant
Impeller / Blade Material Press-Fitted Sheet Steel Blank, Sprayed with Polypropylene (PP) Plastic
Guard Grille Material Steel, Phosphated and Coated with Black Plastic
Rotor Surface Painted Black
Direction of Rotation Counterclockwise, Viewed Toward Rotor
Installation Position Shaft Horizontal or Rotor on Bottom (Rotor on Top on Request)
Condensation Drainage Holes On Rotor Side
Standards & Compliance CE, EN 60335-1, UL 1004-1, CSA C22.2 No. 100

Applications

ebm-papst S4D350-AN22-77 is engineered for commercial refrigeration condensers, walk-in blast freezers, cold-storage unit coolers, and industrial heat exchangers requiring reliable airflow in sub-zero or high-heat environments. Its integrated guard grille and sickle-blade geometry make it directly suited for short-nozzle mounting in outdoor air-cooled chillers, rooftop HVAC condensers, and dry coolers. Industrial OEMs and MRO technicians also deploy this three-phase axial fan in process cooling towers, environmental test chambers, and heavy machinery ventilation plenums.