Description
ebm-papst W2E200-HK38-C01 (also known as W2E200HK38C01) is an S-series AC axial compact fan featuring a 200 mm (7.87 in) 7-blade sickled sheet-steel impeller, a die-cast aluminum wall ring, and an integrated M2E068-BF external-rotor capacitor motor. Operating on single-phase 230 VAC (50/60 Hz), it delivers nominal free-air speeds of 2550 RPM (50 Hz) / 2800 RPM (60 Hz) at 64 W / 80 W (0.29 A / 0.35 A), generating up to 517.95 CFM (880 m³/h) at 50 Hz and 588.58 CFM (1000 m³/h) at 60 Hz with maximum back pressure ratings of 80 Pa (0.321 in H₂O) and 95 Pa (0.382 in H₂O).
Engineered for continuous S1 industrial operation from -40 °C to +60 °C / +65 °C, the unit incorporates ball bearings, internally wired thermal overload protection (TOP), IP44 and Class I protection, and variable-exit terminal strip wiring with an integrated 1.5 µF / 450 VDB run capacitor.
Key Features
- Dual-Frequency Aerodynamic Output: Delivers 517.95 CFM (880 m³/h) at 50 Hz and 588.58 CFM (1000 m³/h) at 60 Hz free air.
- Integrated Terminal Strip & Capacitor: Pre-fitted with an integrated 1.5 µF (450 VDB) P0 capacitor wired directly via internal terminal strips.
- Heavy-Duty Metal Construction: Combines a die-cast aluminum wall ring with a 7-blade black-coated sheet steel sickled impeller.
- Thermal & Ingress Protection: Equipped with an internally wired thermal overload protector (TOP), Class B insulation, and IP44 environmental sealing.
- Ball Bearing S1 Reliability: Precision ball-bearing M2E068-BF motor supports continuous S1 duty in any mounting orientation up to +65 °C.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | W2E200-HK38-C01 |
| Alternate Part Number | W2E200HK38C01 |
| Integrated Motor Model | M2E068-BF |
| Product Series | S Series (W2E200 AC Axial Compact Series) |
| Product Category | AC Axial Fans |
| Fan / Component Type | AC Axial Compact Fan with Wall Ring |
| Motor Design / Technology | Single-Phase AC External-Rotor Capacitor Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Nominal Data Definition | rfa (Running at Free Air) |
| Speed (Nominal Free Air) | 2550 RPM (50 Hz) / 2800 RPM (60 Hz) |
| Free-Air Speed (Curve Point 1, 0 Pa) | 2630 RPM (50 Hz) / 3000 RPM (60 Hz) |
| Operating Speed (Curve Point 2, 30 Pa) | 2585 RPM (50 Hz) / 2935 RPM (60 Hz) |
| Operating Speed (Curve Point 3, 60 Pa) | 2530 RPM (50 Hz) / 2850 RPM (60 Hz) |
| Speed at Max. Back Pressure (Curve Point 4) | 2480 RPM at 80 Pa (50 Hz) / 2705 RPM at 95 Pa (60 Hz) |
| Power Rating (Nominal Free Air) | 64 W (50 Hz) / 80 W (60 Hz) |
| Free-Air Power Input (Curve Point 1, 0 Pa) | 60 W (50 Hz) / 70 W (60 Hz) |
| Operating Power Input (Curve Point 2, 30 Pa) | 64 W (50 Hz) / 73 W (60 Hz) |
| Operating Power Input (Curve Point 3, 60 Pa) | 66 W (50 Hz) / 77 W (60 Hz) |
| Power Input at Max. Back Pressure (Curve Point 4) | 69 W at 80 Pa (50 Hz) / 83 W at 95 Pa (60 Hz) |
| Rated Current (Nominal Free Air) | 0.29 A (50 Hz) / 0.35 A (60 Hz) |
| Free-Air Current Draw (Curve Point 1, 0 Pa) | 0.30 A (50 Hz) / 0.31 A (60 Hz) |
| Operating Current Draw (Curve Point 2, 30 Pa) | 0.31 A (50 Hz) / 0.32 A (60 Hz) |
| Operating Current Draw (Curve Point 3, 60 Pa) | 0.31 A (50 Hz) / 0.34 A (60 Hz) |
| Current Draw at Max. Back Pressure (Curve Point 4) | 0.32 A at 80 Pa (50 Hz) / 0.36 A at 95 Pa (60 Hz) |
| Run Capacitor | 1.5 µF, 450 VDB (Class P0 per CE) |
| Capacitor Wiring / Operation Mode | Integrated capacitor pre-connected via internal terminal strips |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air, 0 Pa) | 517.95 CFM / 880 m³/h (50 Hz) | 588.58 CFM / 1000 m³/h (60 Hz) |
| Operating Duty Point Airflow (Curve Point 2, 30 Pa / 0.121 in H₂O) | 467.92 CFM / 795 m³/h (50 Hz) | 544.44 CFM / 925 m³/h (60 Hz) |
| Operating Duty Point Airflow (Curve Point 3, 60 Pa / 0.241 in H₂O) | 400.24 CFM / 680 m³/h (50 Hz) | 482.64 CFM / 820 m³/h (60 Hz) |
| Operating Duty Point Airflow (Curve Point 4, Max. Back Pressure) | 317.83 CFM / 540 m³/h at 80 Pa / 0.321 in H₂O (50 Hz) | 335.49 CFM / 570 m³/h at 95 Pa / 0.382 in H₂O (60 Hz) |
| Max. Static Pressure (Rated Max. Back Pressure) | 0.321 in H₂O / 80 Pa (50 Hz) | 0.382 in H₂O / 95 Pa (60 Hz) |
| Aerodynamic Measurement Reference | Air density Rho = 1.2 kg/m³ (60 Hz Measurement ID: LU-62129) |
| Airflow Direction | “V” (Intake over struts / Exhaust over rotor) |
| Ingress Protection (IP) | IP44 (Depending on installation and position) |
| Moisture / Environmental Class | F0 |
| Operating Temperature | -40 °C to +60 °C (-40 °F to +140 °F) at 50 Hz / -40 °C to +65 °C (-40 °F to +149 °F) at 60 Hz |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) wired internally |
| Electrical Protection Class | Class I (with protective earth ground) |
| Touch / Leakage Current (IEC 60990) | < 0.75 mA |
| Insulation Class | Class “B” |
| Termination Type | Via terminal strips (with integrated capacitor connected via terminal strips) |
| Cable Exit Orientation | Variable |
| Wiring Pinout / Connection | U1 = Blue | Z = Brown | U2 = Black | PE = Green/Yellow |
| Impeller Size | Ø 200 mm (7.87 in) |
| Weight | 2.1 kg (4.63 lbs) |
| Blade Count & Geometry | 7 Sickled Blades (S Series) |
| Bearing Type | Ball Bearing |
| Housing / Wall Ring Material | Die-Cast Aluminum |
| Impeller / Blade Material | Sheet Steel, Coated in Black |
| Rotor Surface | Coated in Black |
| Direction of Rotation | Counter-Clockwise (CCW), seen on rotor |
| Installation Position | Any |
| Condensation Drainage Holes | None |
| Standards & Compliance | CE, EN 60335-1, UL, VDE, CCC |
Applications
The ebm-papst W2E200-HK38-C01 AC axial compact fan is engineered for high-reliability heat dissipation across industrial automation cabinets, variable frequency drives (VFDs), welding inverters, and UPS power conversion enclosures. Its die-cast aluminum wall ring, sickled steel blades, and integrated terminal-strip capacitor make it a direct drop-in OEM and MRO thermal solution for commercial refrigeration condensers, chiller heat exchangers, and HVAC ventilation plenums. Built to withstand harsh ambient conditions, it also supports continuous cooling in CNC machine tools, power distribution switchgear, and industrial baking or curing equipment.