R4E355-AL02-06 ebm-papst 230VAC 355mm AC Centrifugal Fan

$640.00

ebm-papst R4E355-AL02-06 (R4E355AL0206) 230VAC Ø355mm backward-curved centrifugal fan, 1420/1650RPM, 1865/2155CFM, 245/420W, with aluminum impeller & TOP.

SKU: R4E355-AL02-06 Category: Brand:

Description

ebm-papst R4E355-AL02-06 (also known as R4E355AL0206) is an unhoused single-intake, backward-curved AC centrifugal motorized impeller powered by an integrated M4E074-GA external rotor motor with a 355 mm (13.98 in) impeller diameter. Operating on single-phase 230 VAC (50/60 Hz) power, it delivers 1865 CFM (3165 m³/h) at 1420 RPM and 245 W at 50 Hz, scaling to 2155 CFM (3660 m³/h) at 1650 RPM and 420 W at 60 Hz in free-air operation. Under peak aerodynamic load on the performance curve, input reaches 298 W (1.32 A at 1390 RPM) at 50 Hz and 481 W (2.10 A at 1545 RPM) at 60 Hz.

Built for continuous S1 industrial duty, the assembly features a 6-blade sheet aluminum impeller, maintenance-free ball bearings, Class F insulation, H1+ environmental protection, an internal thermal overload protector (TOP) wired to two gray leads, and a 6-core 0.5 mm² PVC cable with spliced ends.

Key Features

  • Dual-Frequency Aerodynamic Output: Delivers 1865 CFM (3165 m³/h) at 50 Hz and 2155 CFM (3660 m³/h) at 60 Hz free air.
  • High-Static Backward-Curved Impeller: Six-blade sheet aluminum wheel generates up to 340 Pa (50 Hz) and 420 Pa (60 Hz) measured curve pressure.
  • Integrated M4E074-GA External Rotor Motor: Four-pole single-phase 230 VAC motor with ball bearings and black-painted rotor supports continuous S1 operation in any orientation.
  • Active Thermal Overload Protection: Built-in TOP thermal switch with dedicated dual gray leads safeguards windings up to +70 °C (50 Hz) ambient.
  • H1+ Environmental & Class F Insulation: Engineered with moisture protection class H1+, Class I grounding, and low touch current under 0.75 mA.
  • Industrial 6-Core PVC Harness: Pre-wired with a variable-exit 6 x 0.5 mm² PVC cable featuring 6x spliced leads for direct terminal integration.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) R4E355-AL02-06
Alternate Part Number R4E355AL0206
OEM Item Number 11300-5-9980
Integrated Motor Model M4E074-GA (Motor Size 74)
Product Series R4E355
Product Category AC Centrifugal Fans
Fan / Component Type Backward-Curved Single-Intake Motorized Impeller (Unhoused)
Motor Design / Technology 4-Pole Single-Phase External Rotor AC Induction Motor
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 / 60 Hz
Free-Air Speed (RPM) 1420 RPM (50 Hz) / 1650 RPM (60 Hz)
Speed (Max. Load) 1390 RPM (50 Hz at 260 Pa) / 1545 RPM (60 Hz at 300 Pa)
Free-Air Power Input 245 W (50 Hz) / 420 W (60 Hz)
Power Rating (Max. Load) 298 W (50 Hz at 260 Pa) / 481 W (60 Hz at 300 Pa)
Free-Air Current Draw 1.12 A (50 Hz) / 1.90 A (60 Hz)
Rated Current (Max. Load) 1.32 A (50 Hz at 260 Pa) / 2.10 A (60 Hz at 300 Pa)
Inrush / Starting Current 2.62 A (50 Hz)
Run Capacitor 8 µF / 400 VDB (50 Hz) | 10 µF / 450 VDB (60 Hz)
Capacitor Standard S0 (CE)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 1865 CFM (3165 m³/h) at 50 Hz / 2155 CFM (3660 m³/h) at 60 Hz (at 0 Pa)
Operating Duty Point 2 (Curve) 50 Hz: 1530 CFM (2600 m³/h) at 0.56 in H₂O (140 Pa), 1400 RPM, 288 W, 1.28 A | 60 Hz: 1780 CFM (3025 m³/h) at 0.64 in H₂O (160 Pa), 1595 RPM, 464 W, 2.04 A
Operating Duty Point 3 (Peak Load) 50 Hz: 1095 CFM (1865 m³/h) at 1.04 in H₂O (260 Pa), 1390 RPM, 298 W, 1.32 A | 60 Hz: 1295 CFM (2205 m³/h) at 1.20 in H₂O (300 Pa), 1545 RPM, 481 W, 2.10 A
Operating Duty Point 4 (High Pressure) 50 Hz: 650 CFM (1100 m³/h) at 1.36 in H₂O (340 Pa), 1410 RPM, 271 W, 1.22 A | 60 Hz: 790 CFM (1345 m³/h) at 1.69 in H₂O (420 Pa), 1605 RPM, 458 W, 2.01 A
Max. Static Pressure (Measured Table) 1.36 in H₂O (340 Pa) at 50 Hz / 1.69 in H₂O (420 Pa) at 60 Hz
Max. Static Pressure (Chart Curve) 1.73 in H₂O (430 Pa) at 50 Hz / 2.25 in H₂O (560 Pa) at 60 Hz
Min. Back Pressure 0 in H₂O (0 Pa)
Aerodynamic Measurement Standard ISO 5801 Installation Category A (LU-106561-1 for 50 Hz / LU-54519-1 for 60 Hz)
Ingress Protection (IP) IP00
Moisture / Environmental Class H1+
Operating Temperature (50 Hz) -25 °C to +70 °C (-13 °F to +158 °F)
Operating Temperature (60 Hz) -25 °C to +40 °C (-13 °F to +104 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) with basic insulation (externally wired via 2x gray leads)
Electrical Protection Class Class I (with customer connection of protective earth)
Touch Current (IEC 60990) < 0.75 mA (Measuring circuit Fig. 4, TN system)
Insulation Class Class F
Termination Type PVC Multi-Core Cable with 6x Spliced Wire Ends
Cable Exit Orientation Variable
Lead Wire Gauge & Spec PVC 6 x 0.5 mm² (with 6x splice)
Wiring Pinout / Connection U1 = Blue | Z = Brown | U2 = Black | PE = Green/Yellow | TOP (Thermal Protector) = 2x Gray
Impeller Size Ø 355 mm (13.98 in)
Max. Screw Clearance (Rotor Side) 10 mm (0.39 in)
Max. Screw Clearance (Stator Side) 5 mm (0.20 in)
Weight 5.5 kg (12.13 lbs)
Blade Count & Geometry 6 Backward-Curved Blades (Single-Intake)
Bearing Type Ball Bearing
Impeller / Blade Material Sheet Aluminum
Rotor Surface Painted Black
Direction of Rotation Clockwise, viewed toward rotor
Installation Position Any
Compatible Inlet Ring (Optional) 35560-2-4013 (not included in scope of delivery)
Standards & Compliance CE, CCC, EN 60034-1, EN 60204-1, EN 60335-1, ISO 5801, ISO 13347

Applications

ebm-papst R4E355-AL02-06 backward-curved centrifugal motorized impellers are engineered for pressurized plenum and ductless air-handling systems where static resistance requires radial airflow without a bulky scroll housing. Typical OEM and MRO installations include data center CRAC and CRAH precision air conditioning units, commercial rooftop HVAC air handling units (AHUs), heat recovery ventilation (HRV) systems, and cleanroom fan filter units (FFUs). Its sheet aluminum impeller and high-temperature thermal endurance also make it ideal for industrial drying ovens, chiller condenser modules, and large power electronics or transformer cooling cabinets.