Description
ebm-papst G1G170-AB31-08 (also known as G1G170AB3108) is a high-pressure single-inlet backward-curved EC centrifugal blower fan with a flanged scroll housing and an integrated M1G074-CF electronically commutated motor around a 170 mm (6.69 in) impeller. Operating across a 230 VAC (197 to 253 VAC) single-phase 50/60 Hz supply, it delivers a free-air flow of 380 CFM (645 m³/h) at 5600 RPM (330 W, 2.30 A) and reaches high static pressures up to 8.83 in H₂O (2200 Pa) at 6215 RPM.
Engineered for demanding gas-tight and high-resistance industrial environments, the unit features a die-cast aluminum housing sealed with a pentane-resistant NBR round cord, an aluminum sheet impeller, anti-vibration motor mounting, and ball bearings rated for continuous S1 operation from -25 °C to +60 °C (-13 °F to +140 °F). It incorporates a SELV-isolated control interface with PWM speed control and a 3-pulse/revolution tachometer output via dedicated plug strips, alongside internal thermal overload protection (TOP) and UL 507, CSA, VDE, and CE compliance.
Key Features
- High-Pressure EC Aerodynamics: Delivers 380 CFM (645 m³/h) at free air and sustains 155 CFM (260 m³/h) at 8.83 in H₂O (2200 Pa).
- Sealed Die-Cast Aluminum Housing: Constructed with a die-cast aluminum scroll, pentane-resistant NBR round cord seal, and sheet aluminum backward-curved impeller.
- SELV PWM & Tachometer Control: Features a safely isolated control interface with frequency-coded PWM input and 3-pulse/revolution speed monitoring output.
- Anti-Vibration & Thermal Protection: Integrates one-sided anti-vibration motor mounting, motor current limiting, and an internally wired thermal overload protector (TOP).
- Dual Plug-Strip Termination: Equipped with a 3-pole power plug (mating Tyco 350 766-1) and 5-pole control header (mating Molex 39-01-4050).
- Global Safety & ErP Compliance: Exceeds ErP Directive requirements with 61.3% static efficiency (Grade N 77.4) and holds UL 507, CSA, VDE, and CE approvals.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | G1G170-AB31-08 |
| Alternate Part Number | G1G170AB3108 |
| OEM Item Number | 51257-5-9980 |
| Integrated Motor Model | M1G074-CF |
| Product Series | G1G170 |
| Product Category | EC Blower Fans |
| Fan / Component Type | Single-Inlet Backward-Curved EC Centrifugal Blower Fan with Flanged Housing |
| Motor Design / Technology | Electronically Commutated (EC) Brushless External Rotor Motor with Integrated Drive |
| Phase & Supply Type | 1~ (Single-Phase AC Input) |
| Rated Voltage | 230 VAC |
| Operating Voltage Range | 197 to 253 VAC |
| Frequency | 50 / 60 Hz |
| Nominal Data Definition | fa (Running at Free Air) |
| Free-Air Speed (RPM) | 5600 RPM (Nominal at 0 Pa, Point 1) |
| Operating Curve Speed (Point 2) | 5685 RPM (at 800 Pa / 3.21 in H₂O) |
| Operating Curve Speed (Point 3) | 5920 RPM (at 1600 Pa / 6.42 in H₂O) |
| Max. Static Pressure Speed (Point 4) | 6215 RPM (at 2200 Pa / 8.83 in H₂O) |
| ErP Optimum Speed (RPM) | 5960 RPM (at Optimum Static Efficiency) |
| Free-Air Power Input | 330 W (Nominal at 0 Pa, Point 1) |
| Operating Curve Power Input (Point 2) | 329 W (at 800 Pa / 3.21 in H₂O) |
| Operating Curve Power Input (Point 3) | 318 W (at 1600 Pa / 6.42 in H₂O) |
| Max. Static Pressure Power Input (Point 4) | 292 W (at 2200 Pa / 8.83 in H₂O) |
| ErP Optimum Efficiency Power | 290 W (0.29 kW) |
| Free-Air Current Draw | 2.30 A (Nominal at 0 Pa, Point 1) |
| Operating Curve Current Draw (Point 2) | 2.28 A (at 800 Pa / 3.21 in H₂O) |
| Operating Curve Current Draw (Point 3) | 2.22 A (at 1600 Pa / 6.42 in H₂O) |
| Max. Static Pressure Current Draw (Point 4) | 2.01 A (at 2200 Pa / 8.83 in H₂O) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 380 CFM (645 m³/h) at 0 in H₂O (0 Pa) (Point 1) |
| Operating Duty Point Airflow (Point 2) | 315 CFM (530 m³/h) at 3.21 in H₂O (800 Pa) |
| Operating Duty Point Airflow (Point 3) | 225 CFM (385 m³/h) at 6.42 in H₂O (1600 Pa) |
| Operating Duty Point Airflow (Point 4) | 155 CFM (260 m³/h) at 8.83 in H₂O (2200 Pa) |
| ErP Optimum Efficiency Duty Point | 217.77 CFM (370 m³/h) at 6.43 in H₂O (1601 Pa) (Test Setup LU-48240) |
| Max. Measured Static Pressure (Curve Point 4) | 8.83 in H₂O (2200 Pa) |
| Aerodynamic & Acoustic Measurement Standard | ISO 5801 Installation Category A (Test Setup LU-110151-1); LwA per ISO 13347 / LpA at 1 m to fan axis |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes = 61.3% (2015 Target: 44.9%); Efficiency Grade N = 77.4 (Target: 61); Category A, Static; VSD Integrated; Specific Ratio = 1.02 |
| Ingress Protection (IP) | IP20 (Depending on installation and position) |
| Operating Temperature | -25 °C to +60 °C (-13 °F to +140 °F) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) Wired Internally, Over-Temperature Protected Motor, Motor Current Limit |
| Electrical Protection Class | Class I (If protective earth is connected by customer) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring network Fig. 4, TN system) |
| Insulation Class | Class B |
| Control / Signal Features | SELV Control Interface, PWM Control Input, Tachometer (Speed Monitoring) Output (3 pulses/rev, Isink 10 mA) |
| Speed Monitoring Supply Voltage (Pin DU) | 20 to 29 VDC |
| PWM Control Signal Specification | Spec. DMT / Min. PWM Operation: f = 1 ± 0.2 kHz -> 10% PWM; f = 4 ± 0.2 kHz -> 18% PWM; f = 6 ± 0.2 kHz -> 25% PWM (PWM Low = Fan Off, PWM High = Fan On) |
| Termination Type | Electrical Leads with 3-Pole Power Plug (ST1) and 5-Pole Control Plug (ST2) |
| Power Mating Connector (ST1) | 3-Pole Strip — Mating Connector: Tyco No. 350 766-1; Female Terminal: Tyco No. 926 884-1 (Not included in standard delivery) |
| Control Mating Connector (ST2) | 5-Pole Strip — Mating Connector: Molex No. 39-01-4050; Female Terminal: Molex No. 39-00-0059 (Not included in standard delivery) |
| Power Wiring Pinout (ST1) | Pin 2.1 (L) = Line (230 VAC, 50-60 Hz); Pin 2.2 (N) = Neutral; Pin 2.3 (PE) = Protective Earth |
| Control & Signal Pinout (ST2) | Pin 1 (3.1, NB) = Not Assigned; Pin 2 (3.2, DU) = Speed Monitoring Input Voltage (20-29 VDC); Pin 3 (3.3, DZU) = Speed Monitoring Output (3 pulses/rev); Pin 4 (3.4, PWM) = PWM Input; Pin 5 (3.5, GND) = Control Interface Ground (-) |
| Impeller Size | Ø 170 mm (6.69 in) |
| Weight | 4.5 kg (9.92 lbs) |
| Bearing Type | Ball Bearing |
| Motor Suspension | Motor Anti-Vibration Mounted on One Side via Mounting Plate |
| Housing / Scroll / Frame Material | Die-Cast Aluminum |
| Housing Sealing & Pressure Relief | Housing Side Parts Sealed with Pentane-Resistant NBR Round Cord; Bleeder Connection for Pressure Relief Possible |
| Impeller / Blade Material | Sheet Aluminum (Backward-Curved) |
| Direction of Rotation | Clockwise, Viewed Toward Rotor |
| Installation Position | Shaft Horizontal or Rotor on Bottom (Rotor on Top Available on Request) |
| Condensation Drainage Holes | Rotor-Side Condensate Discharge Holes and Rotor-Side Cooling Bore / Aperture |
| Standards & Compliance | EN 60335-1, CE, UL 507, CSA C22.2 No. 113, VDE, ErP Directive Compliant |
Applications
ebm-papst G1G170-AB31-08 is engineered for high-back-pressure industrial air movement, gas-tight process extraction, and precision thermal management where sealed scroll housings and variable speed control are critical. Its pentane-resistant NBR-sealed die-cast aluminum housing makes it particularly well-suited for commercial refrigeration systems using hydrocarbon refrigerants, industrial condensing units, gas-fired premix heating boilers, and laboratory fume extraction hoods. OEM equipment builders and MRO technicians also deploy this flanged EC centrifugal blower in laser cutting exhaust systems, environmental test chambers, fuel cell ventilation modules, and pressurized power electronics cabinets.