W2D300-CP02-16 ebm-papst 230/400VAC 300mm AC Axial Fan

$999.00

ebm-papst W2D300-CP02-16 (W2D300CP0216) 230/400VAC 300mm 3-phase axial fan, 2580RPM, 1845CFM (3135m³/h), 210W, with wall ring housing, guard grille & IP44.

SKU: W2D300-CP02-16 Category: Brand:

Description

ebm-papst W2D300-CP02-16 (also known as W2D300CP0216, OEM Item No. 12898-5-9980) is an industrial three-phase S-series AC axial fan unit featuring a 300 mm (11.81 in) 5-blade sickle-shaped impeller, a pre-galvanized sheet steel wall ring housing, and an integrated steel guard grille powered by the M2D074-DF external rotor motor. Operating on 50 Hz three-phase supplies wired in either Delta (220–230 VAC) or Star (380–400 VAC), it delivers a free-air flow of 1845 CFM (3135 m³/h) at 2580 RPM with a nominal free-air power input of 210 W (0.62 A at 230 VAC Δ / 0.36 A at 400 VAC Y) and reaches up to 281 W (0.44 A at 400 VAC Y) at its 160 Pa (0.64 in H₂O) high-load curve duty point.

Engineered for continuous S1 operation across ambient temperatures from -25 °C to +75 °C (-13 °F to +167 °F), the assembly incorporates ball bearings, RAL 9005 black plastic-coated steel components, an ABS terminal box for variable cable entry, and IP44 ingress protection.

Key Features

  • Dual-Voltage Three-Phase Motor: Configurable M2D074-DF motor supports 220/230 VAC Delta and 380/400 VAC Star 50 Hz connections with reversible phase rotation.
  • High-Airflow Sickle Impeller: Aerodynamic 300 mm 5-blade painted sheet steel impeller delivers up to 1845 CFM (3135 m³/h) free-air output.
  • Full Nozzle Housing & Guard: Pre-galvanized sheet steel wall ring and steel guard grille finished in durable RAL 9005 black plastic coating.
  • Wide Thermal & IP44 Rating: Ball bearing system and Class F insulation support S1 continuous duty from -25 °C to +75 °C under IP44 protection.
  • Integrated ABS Terminal Box: Features variable cable exit orientation accepting up to 10 mm cord diameter with rotor-side condensation drainage holes.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) W2D300-CP02-16
Alternate Part Number W2D300CP0216
OEM Item Number 12898-5-9980
Integrated Motor Model M2D074-DF
Product Series S Series (W2D300)
Product Category AC Axial Fans
Fan / Component Type AC Axial Fan with Wall Ring Housing and Guard Grille
Motor Design / Technology Three-Phase AC External Rotor Induction Motor
Phase & Supply Type 3~ (Three-Phase AC, Delta Δ / Star Y Configurable)
Rated Voltage 220 / 230 VAC (Delta Δ) | 380 / 400 VAC (Star Y)
Frequency 50 Hz
Free-Air Speed (RPM) 2560 RPM (at 220 VAC Δ / 380 VAC Y) | 2580 RPM (at 230 VAC Δ / 400 VAC Y)
Speed (Max. Curve Load) 2385 RPM (at 400 VAC Y, 160 Pa / 0.64 in H₂O)
ErP Optimum Speed (RPM) 2455 RPM (at 125 Pa / 0.502 in H₂O)
Free-Air Power Input 195 W (at 220 VAC Δ / 380 VAC Y) | 210 W (at 230 VAC Δ / 400 VAC Y)
Power Rating (Max. Curve Load) 281 W (at 400 VAC Y, 160 Pa / 0.64 in H₂O)
ErP Optimum Efficiency Power 250 W (0.25 kW at 125 Pa / 0.502 in H₂O)
Free-Air Current Draw 0.59 A (220 VAC Δ) / 0.62 A (230 VAC Δ) | 0.34 A (380 VAC Y) / 0.36 A (400 VAC Y)
Rated Current (Max. Curve Load) 0.44 A (at 400 VAC Y, 160 Pa / 0.64 in H₂O)
Inrush / Starting Current 2.0 A (at 230 VAC Δ) | 1.16 A (at 400 VAC Y)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 1845 CFM (3135 m³/h at 0 Pa, 400 VAC Y, 50 Hz)
Operating Duty Point Airflow (Point 2) 1650 CFM (2805 m³/h) at 0.20 in H₂O (50 Pa) — 2540 RPM, 228 W, 0.36 A
Operating Duty Point Airflow (Point 3) 1440 CFM (2445 m³/h) at 0.40 in H₂O (100 Pa) — 2490 RPM, 244 W, 0.39 A
Operating Duty Point Airflow (Point 4 Max. Curve) 995 CFM (1690 m³/h) at 0.64 in H₂O (160 Pa) — 2385 RPM, 281 W, 0.44 A
ErP Optimum Efficiency Duty Point 1300.76 CFM (2210 m³/h) at 0.502 in H₂O (125 Pa) — 2455 RPM, 250 W
Max. Static Pressure 0.76 in H₂O (190 Pa at 220/380 VAC) | 0.80 in H₂O (200 Pa at 230/400 VAC)
ErP Efficiency & Grade (EU 327/2011) Overall Static Efficiency ηes: 29.9% (Req. 2015: 29.9%), Efficiency Grade N: 40 (Req. 2015: 40), Measurement Category: A, Efficiency Category: Static, VSD: No, Specific Ratio: 1.00 (Test Setup LU-62732)
Airflow Direction Direction “A” (Intake over Guard Grille, Exhaust over Rotor / Struts)
Ingress Protection (IP) IP44 (Installation- and Position-Dependent per EN 60034-5)
Moisture / Environmental Class H0+
Operating Temperature -25 °C to +75 °C (-13 °F to +167 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Electrical Protection Class Class I (With Customer Connection of Protective Earth)
Touch Current (IEC 60990) < 0.75 mA (Measuring Circuit Fig. 4, TN System)
Insulation Class Class “F”
Termination Type Via Integrated Terminal Box (Cover Tightening Torque: 0.5 ± 0.1 Nm)
Cable Exit Orientation Variable
Conduit / Cable Gland Ports Accepts Cable Diameter up to Max. 10 mm (0.39 in), Gland Tightening Torque: 1.3 ± 0.2 Nm
Wiring Pinout / Connection 3-Phase Delta (Δ) / Star (Y) — L1 (U1): Black, L2 (V1): Blue, L3 (W1): Brown, U2: Green, V2: White, W2: Yellow, PE: Green/Yellow (Reversible Rotation by Swapping Two Phases)
Impeller Size Ø 300 mm (11.81 in)
Weight 5.33 kg (11.75 lbs)
Blade Count & Geometry 5 Sickle-Shaped Blades (S Series)
Bearing Type Ball Bearing
Electronics Housing Material ABS Plastic (Terminal Box)
Housing / Scroll / Frame Material Pre-Galvanized Sheet Steel, Coated with Black Plastic (RAL 9005)
Impeller / Blade Material Sheet Steel, Painted Black
Guard Grille Material Steel, Coated with Black Plastic (RAL 9005)
Rotor Surface Painted Black
Direction of Rotation Clockwise, Viewed Toward Rotor
Installation Position Shaft Horizontal or Rotor on Bottom (Rotor on Top Available on Request)
Condensation Drainage Holes On Rotor Side
Standards & Compliance EN 60335-1, ISO 5801 (Category A), ISO 13347, CE

Applications

ebm-papst W2D300-CP02-16 three-phase wall-ring axial fan is engineered for high-throughput thermal management across commercial refrigeration condensers, walk-in cold storage evaporators, and industrial heat exchangers. Its full-nozzle steel housing and integrated guard grille allow direct panel or bulkhead mounting in air-cooled liquid chillers, dry coolers, and large HVAC air handling units. In factory automation and power conversion environments, it provides reliable forced-air ventilation for high-power variable frequency drive (VFD) cabinets, transformer enclosures, and industrial drying or curing machinery.