D2E146-AP47-F8 ebm-papst 230VAC 146mm AC Centrifugal Blower

$617.00

ebm-papst D2E146-AP47-F8 (D2E146AP47F8) 230VAC Ø146mm dual-inlet blower, 2050/2550RPM, 570/410CFM, 300/330W, with galvanized steel scroll, M2E068-EC motor & IP44.

SKU: D2E146-AP47-F8 Category: Brand:

Description

ebm-papst D2E146-AP47-F8 (also known as D2E146AP47F8) is an industrial dual-intake, forward-curved AC centrifugal scroll blower with a discharge flange, driven by an integrated M2E068-EC external-rotor motor and a 146 mm (5.75 in) galvanized sheet steel impeller. Operating on single-phase 230 VAC (50/60 Hz) power with an 8 µF / 400 VDB run capacitor, this blower delivers 2050 RPM, 300 W (1.31 A), and 570 CFM (970 m³/h) at 200 Pa (0.80 in H₂O) minimum back pressure at 50 Hz, or 2550 RPM, 330 W (1.45 A), and 410 CFM (700 m³/h) at 400 Pa (1.61 in H₂O) at 60 Hz.

Built with a galvanized sheet steel scroll housing, precision ball bearings, and one-sided bracket motor suspension, it provides continuous S1 duty operation across ambient temperatures from -25 °C to +50 °C (50 Hz) or +45 °C (60 Hz). The unit features IP44 ingress protection, Class F insulation, an externally wired thermal overload protector (TOP), and an axial 6G 0.5 mm² halogen- and silicone-free connection cable with 6x crimped splices.

Key Features

  • Dual-Inlet Scroll Aerodynamics: Delivers 570 CFM (970 m³/h) at 200 Pa (50 Hz) and up to 625 Pa (2.51 in H₂O) at 60 Hz.
  • Integrated M2E068-EC AC Drive: Single-phase 230 VAC external-rotor motor rated at 300 W / 1.31 A (50 Hz) and 330 W / 1.45 A (60 Hz).
  • Galvanized Sheet Steel Construction: Corrosion-resistant galvanized steel scroll housing with integrated mounting flange and dual-intake forward-curved drum impeller.
  • External TOP Thermal Protection: Equipped with a basic-insulation thermal overload protector (2x gray leads) and Class F motor insulation for fail-safe operation.
  • Halogen- & Silicone-Free Harness: Pre-wired axial 6G 0.5 mm² multi-conductor cable terminated with 6x crimped splices for clean industrial panel integration.
  • Precision Ball Bearing System: Supports continuous S1 duty in any installation position with IP44 environmental protection and low touch current (< 0.75 mA).

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) D2E146-AP47-F8
Alternate Part Number D2E146AP47F8
OEM Item Number 15888-5-9980 (Change 89332)
Integrated Motor Model M2E068-EC
Product Series D2E146 Series
Product Category AC Blower Fans
Fan / Component Type Dual-Intake Forward-Curved Centrifugal Scroll Blower with Flange Housing
Motor Design / Technology AC External-Rotor Capacitor-Run Induction Motor
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 / 60 Hz
Speed (Max. Load / Point 1) 2050 RPM (50 Hz) / 2550 RPM (60 Hz)
Speed (Curve Point 2) 2265 RPM (50 Hz) / 2770 RPM (60 Hz)
Speed (Curve Point 3) 2490 RPM (50 Hz) / 2975 RPM (60 Hz)
Speed (High Static Pressure / Point 4) 2675 RPM (50 Hz) / 3095 RPM (60 Hz)
Power Rating (Max. Load / Point 1) 300 W (50 Hz) / 330 W (60 Hz)
Power Input (Curve Point 2) 267 W (50 Hz) / 300 W (60 Hz)
Power Input (Curve Point 3) 232 W (50 Hz) / 277 W (60 Hz)
Power Input (High Static Pressure / Point 4) 191 W (50 Hz) / 260 W (60 Hz)
Rated Current (Max. Load / Point 1) 1.31 A (50 Hz) / 1.45 A (60 Hz)
Current Draw (Curve Point 2) 1.18 A (50 Hz) / 1.36 A (60 Hz)
Current Draw (Curve Point 3) 1.02 A (50 Hz) / 1.28 A (60 Hz)
Current Draw (High Static Pressure / Point 4) 0.84 A (50 Hz) / 1.22 A (60 Hz)
Run Capacitor 8 µF, 400 VDB (Standard S0 per CE)
Capacitor Wiring / Operation Mode Y (Single-Phase Capacitor-Run Connection)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow at Min. Back Pressure (Point 1 / Max. Load) 570 CFM / 970 m³/h at 0.80 in H₂O / 200 Pa (50 Hz); 410 CFM / 700 m³/h at 1.61 in H₂O / 400 Pa (60 Hz)
Operating Duty Point Airflow (Curve Point 2) 490 CFM / 830 m³/h at 1.20 in H₂O / 300 Pa (50 Hz); 325 CFM / 550 m³/h at 1.91 in H₂O / 475 Pa (60 Hz)
Operating Duty Point Airflow (Curve Point 3) 375 CFM / 635 m³/h at 1.53 in H₂O / 380 Pa (50 Hz); 230 CFM / 390 m³/h at 2.21 in H₂O / 550 Pa (60 Hz)
Operating Duty Point Airflow (Curve Point 4) 215 CFM / 365 m³/h at 1.77 in H₂O / 440 Pa (50 Hz); 125 CFM / 210 m³/h at 2.51 in H₂O / 625 Pa (60 Hz)
Max. Measured Static Pressure (Point 4) 1.77 in H₂O / 440 Pa (50 Hz) / 2.51 in H₂O / 625 Pa (60 Hz)
Min. Required Back Pressure 0.80 in H₂O / 200 Pa (50 Hz) / 1.61 in H₂O / 400 Pa (60 Hz)
Aerodynamic Test Standard ISO 5801 Installation Category A (50 Hz Test: LU-32744-1; 60 Hz Test: LU-32745-1)
Acoustic Measurement Standard ISO 13347 (Sound Power) / 1 m Distance from Fan Axis (Sound Pressure)
Airflow Direction Dual-Axial Intake, Tangential Scroll Discharge
Ingress Protection (IP) IP44 (Installation- and Position-Dependent)
Moisture / Environmental Class H0 – Dry Environment
Operating Temperature (50 Hz) -25 °C to +50 °C (-13 °F to +122 °F)
Operating Temperature (60 Hz) -25 °C to +45 °C (-13 °F to +113 °F)
Storage / Transport Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) with Basic Insulation (External Circuit Connection)
Electrical Protection Class Class I (With Customer Connection of Protective Earth)
Touch Current (IEC 60990) < 0.75 mA (Measuring Circuit Fig. 4, TN System)
Insulation Class Class F
Termination Type Multi-Conductor Cable with 6x Crimped Splices
Cable Exit Orientation Axial Cable Exit
Lead Wire Gauge & Spec 6G 0.5 mm² (Halogen- and Silicone-Free)
Wiring Pinout / Connection U1 = Blue, Z = Brown, U2 = Black, PE = Green/Yellow, TOP (Thermal Overload Protector) = 2x Gray
Impeller Size Ø146 mm (5.75 in)
Scroll Housing Width (Overall Flange Width) 270 mm (10.63 in)
Scroll Housing Depth / Height Callouts 254 mm (10.00 in) × 232.5 mm (9.15 in) × 232 mm (9.13 in) × 205 mm (8.07 in)
Discharge Flange Offset / Section Callout 96 mm (3.78 in)
Flange / Sheet Metal Thickness 1.25 mm (0.049 in)
Mounting Hole Diameter Ø5.5 mm / 0.217 in (4x Flange Mounting Holes)
Weight 4.4 kg (9.70 lbs)
Blade Geometry Forward-Curved Dual-Intake Centrifugal Drum Impeller
Bearing Type Ball Bearing
Motor Suspension Motor Mounted with Brackets on One Side
Housing / Scroll Material Galvanized Sheet Steel
Impeller / Blade Material Galvanized Sheet Steel
Rotor Surface Unpainted
Direction of Rotation Counterclockwise (Viewed Toward Rotor)
Installation Position Any
Condensation Drainage Holes None
Standards & Compliance EN 60335-1, CCC, EAC, CE

Applications

ebm-papst D2E146-AP47-F8 dual-intake forward-curved centrifugal scroll blowers are engineered for medium-to-high static pressure ducted ventilation and industrial process air movement where defined system back pressure is present. Typical OEM and MRO installations include commercial HVAC air handling units (AHUs), variable air volume (VAV) terminal boxes, industrial drying and curing ovens, reflow soldering tunnels, packaging and printing machinery, and doorway air curtains. Its flanged galvanized steel scroll housing and external thermal overload leads make it directly suited for closed-loop ducted plenums, heat recovery systems, and pressurized machinery enclosures.