Description
The ebm-papst S4D350-AP08-30/A06 (also known as S4D350AP0830A06) is a 3-phase S-series AC axial fan with a 350 mm (13.78 in) impeller and an integrated guard grille for short nozzles, driven by an external-rotor M4D074-DF motor. Configurable for 230 VAC Delta (Δ) or 400 VAC Star (Y) 50/60 Hz supply, it delivers up to 1930.55 CFM (3280 m³/h) at 1410 RPM (130 W) on 50 Hz and 2195.41 CFM (3730 m³/h) at 1600 RPM (180 W) on 60 Hz, with a maximum back pressure of 0.361 in H₂O (90 Pa).
Built with 5 black-coated sheet steel sickled blades, a RAL 9005 plastic-coated steel guard grille, maintenance-free ball bearings, and a 7-conductor PVC lead harness, it meets IP44 and EN 60335-1 standards for continuous S1 industrial duty.
Key Features
- Dual-Voltage 3-Phase Operation: Supports 230 VAC Delta (Δ) and 400 VAC Star (Y) wiring across 50/60 Hz power grids.
- High-Efficiency Sickled Impeller: Five black-coated sheet steel sickled blades deliver up to 2195.41 CFM (3730 m³/h) with low acoustic turbulence.
- Integrated Short-Nozzle Guard Grille: Heavy-duty steel grille coated in RAL 9005 black plastic enables direct mounting into short nozzle apertures.
- External-Rotor M4D074-DF Motor: Compact ball-bearing induction drive rated for S1 continuous operation with Class B insulation and rotor-side condensate drains.
- ErP Compliant Aerodynamics: Achieves 30.7% overall static efficiency and efficiency grade N 42.2, exceeding EU ErP directive benchmarks.
- 7-Lead Harness & IP44 Protection: Equipped with a variable-exit 7G 0.5 mm² PVC cable with crimped brass ferrules and IP44 ingress sealing.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | S4D350-AP08-30/A06 |
| Alternate Part Number | S4D350AP0830A06 |
| Integrated Motor Model | M4D074-DF |
| Product Series | S Series (Sickled Blades) |
| Product Category | AC Axial Fans |
| Fan / Component Type | AC Axial Fan with Guard Grille for Short Nozzle |
| Motor Design / Technology | AC External-Rotor 3-Phase Induction Motor (4-Pole) |
| Phase & Supply Type | 3-Phase (3~) AC |
| Rated Voltage | 230 VAC (Delta Δ) / 400 VAC (Star Y) |
| Frequency | 50 / 60 Hz |
| Free-Air Speed (RPM) | 1410 RPM (50 Hz) / 1600 RPM (60 Hz) |
| Speed at Max. Load (400V Y) | 1355 RPM (50 Hz) / 1525 RPM (60 Hz) |
| ErP Optimum Speed (RPM) | 1385 RPM (50 Hz) |
| Free-Air Power Input | 130 W (50 Hz) / 180 W (60 Hz) |
| Power Input at Max. Load (400V Y) | 179 W (50 Hz) / 232 W (60 Hz) |
| ErP Optimum Efficiency Power | 150 W / 0.15 kW (50 Hz) |
| Free-Air Current Draw (230V Δ) | 0.61 A (50 Hz) / 0.59 A (60 Hz) |
| Free-Air Current Draw (400V Y) | 0.35 A (50 Hz) / 0.34 A (60 Hz) |
| Current Draw at Max. Load (400V Y) | 0.38 A (50 Hz) / 0.40 A (60 Hz) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 1930.55 CFM (3280 m³/h) at 50 Hz / 2195.41 CFM (3730 m³/h) at 60 Hz |
| Operating Duty Point Airflow (50 Hz, 400V Y) | 1745.14 CFM (2965 m³/h) at 0.121 in H₂O (30 Pa); 1509.71 CFM (2565 m³/h) at 0.241 in H₂O (60 Pa) |
| Max. Load Duty Point Airflow (50 Hz, 400V Y) | 1186.00 CFM (2015 m³/h) at 0.361 in H₂O (90 Pa) |
| Operating Duty Point Airflow (60 Hz, 400V Y) | 2015.89 CFM (3425 m³/h) at 0.121 in H₂O (30 Pa); 1801.06 CFM (3060 m³/h) at 0.241 in H₂O (60 Pa) |
| Max. Load Duty Point Airflow (60 Hz, 400V Y) | 1539.14 CFM (2615 m³/h) at 0.361 in H₂O (90 Pa) |
| ErP Optimum Efficiency Duty Point | 1241.91 CFM (2110 m³/h) at 0.321 in H₂O (80 Pa) |
| Max. Static Pressure | 0.361 in H₂O (90 Pa) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes: 30.7% (Grade N: 42.2, Installation Cat. A, Static, Specific Ratio 1.00) |
| Airflow Direction | “V” (Airflow over struts / motor toward impeller) |
| Ingress Protection (IP) | IP44 (depending on installation and position per EN 60034-5) |
| Operating Temperature | -40 °C to +50 °C (-40 °F to +122 °F) at 50 Hz / -40 °C to +40 °C (-40 °F to +104 °F) at 60 Hz |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Electrical Protection Class | Class I (when protective earth is connected by customer) |
| Touch Current (IEC 60990) | < 0.75 mA (measuring network Fig. 4, TN system) |
| Insulation Class | Class B |
| Termination Type | 7-Conductor Lead Wires with Crimped Brass Lead Tips |
| Cable Exit Orientation | Variable |
| Lead Wire Gauge & Spec | PVC 7G 0.5 mm² (7x crimped brass ferrules) |
| Wiring Pinout / Connection | Delta (Δ) / Star (Y): L1/U1 = Black, L2/V1 = Blue, L3/W1 = Brown, U2 = Green, V2 = White, W2 = Yellow, PE = Green/Yellow (reverse any two phases to reverse rotation) |
| Impeller Size | Ø 350 mm (13.78 in) |
| Weight | 4.6 kg (10.14 lbs) |
| Blade Count & Geometry | 5 Sickled Blades |
| Bearing Type | Ball Bearing |
| Impeller / Blade Material | Sheet Steel, Coated in Black |
| Guard Grille Material | Steel, Coated with Black Plastic (RAL 9005) |
| Rotor Surface | Coated in Black |
| Direction of Rotation | “V” (Counter-clockwise viewed toward rotor) |
| Installation Position | Shaft horizontal or rotor on bottom (rotor on top on request) |
| Condensation Drainage Holes | Rotor-side |
| Standards & Compliance | EN 60335-1, EN 60034-5, ISO 5801, ISO 13347, CCC |
Applications
The ebm-papst S4D350-AP08-30/A06 is engineered for medium-to-high airflow ventilation and heat rejection in commercial HVACR and industrial machinery. It is widely deployed in air-cooled refrigeration condensers, commercial heat pumps, cold-storage evaporators, and rooftop air handling units. Additionally, its integrated short-nozzle guard grille makes it ideal for industrial drying ovens, transformer enclosures, power generator cooling modules, and heavy-duty process equipment cabinets.