Description
ebm-papst K3G280-AU11-C3 (also known as K3G280AU11C3) is a 280 mm (11.02 in) RadiPac series single-intake backward-curved EC centrifugal fan module integrated with an M3G084-GF brushless motor and a 400 × 400 mm (15.75 × 15.75 in) galvanized steel support plate and black-painted steel mounting bracket. Operating across a 3-phase 380–480 VAC (400 VAC nominal, 50/60 Hz) supply, it delivers a free-air flow of 2,315 CFM (3,935 m³/h) at 645 W (1.04 A) and reaches its nominal maximum-load rating of 1,000 W and 1.60 A at 3,100 RPM (delivering 1,565 CFM / 2,660 m³/h at 3.11 in H₂O / 775 Pa static pressure, and up to 4.14 in H₂O / 1,030 Pa on the measured operating curve).
Engineered for demanding continuous-duty (S1) industrial ventilation from -25 °C to +60 °C (-13 °F to +140 °F), the assembly features a 7-blade sheet aluminum impeller, die-cast aluminum electronics enclosure, maintenance-free ball bearings, IP54 and F3-1 environmental protection, and an internal terminal box equipped with RS-485 MODBUS-RTU, 0–10 VDC / PWM / 4–20 mA control inputs, and a floating status alarm relay.
Key Features
- High-Static RadiPac Aerodynamics: 7-blade backward-curved 280 mm aluminum impeller delivers 2,315 CFM (3,935 m³/h) free air and 4.14 in H₂O (1,030 Pa) measured static pressure.
- Wide-Range 3-Phase EC Drive: Integrated M3G084-GF EC motor operates on 380–480 VAC (50/60 Hz), achieving 61.1% overall static efficiency (ErP Grade N 71.6).
- RS-485 MODBUS & Analog Control: SELV-isolated interface supports MODBUS-RTU networking, 0–10 VDC / PWM or 4–20 mA speed/sensor inputs, and 0–10 V slave modulation output.
- Integrated Auxiliary Power & Relay: Provides onboard +10 VDC (10 mA) and +20 VDC (50 mA) sensor supplies plus a Form-C changeover status relay (250 VAC, 2 A).
- Comprehensive Drive Protection: Built-in thermal overload protection (TOP), phase failure and line undervoltage detection, soft start, plus active power and current limitation.
- Rugged Plug-and-Play Module: Pre-assembled with galvanized steel inlet nozzle plate, black steel support bracket, IP54/F3-1 protection, and three M16 × 1.5 cable glands.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | K3G280-AU11-C3 |
| Alternate Part Number | K3G280AU11C3 |
| OEM Item Number | 52346-5-9980 |
| Integrated Motor Model | M3G084-GF |
| Product Series | RadiPac (K3G Series) |
| Product Category | EC Centrifugal Fans |
| Fan / Component Type | Single-Intake Backward-Curved EC Centrifugal Module with Support Bracket |
| Motor Design / Technology | Electronically Commutated (EC) External Rotor Motor with Integrated Drive Electronics |
| Phase & Supply Type | 3~ (3-Phase AC Input to Integrated EC Drive) |
| Rated Voltage | 400 VAC |
| Operating Voltage Range | 380 to 480 VAC |
| Frequency | 50 / 60 Hz |
| Speed (RPM) | 3100 RPM (Nominal Max. Load) |
| Free-Air Speed (RPM) | 3100 RPM (at 0 Pa Static Pressure) |
| ErP Optimum Speed (RPM) | 3120 RPM (at Optimum Efficiency Level) |
| Reduced Curve Speeds (RPM) | 2575 RPM (Curve II), 2045 RPM (Curve III) |
| Power Rating | 1000 W (Nominal Max. Load at 775 Pa) |
| Free-Air Power Input | 645 W (Curve Point 1 at 0 Pa) |
| ErP Optimum Efficiency Power | 1000 W (1.0 kW at 844 Pa) |
| Curve Operating Power Points | 852 W (Pt 2 at 390 Pa), 921 W (Pt 4 at 1030 Pa), 358 to 562 W (at 2575 RPM), 180 to 282 W (at 2045 RPM) |
| Rated Current | 1.60 A (Nominal Max. Load at 400 VAC) |
| Free-Air Current Draw | 1.04 A (Curve Point 1 at 0 Pa, 400 VAC) |
| Curve Operating Current Points | 1.35 A (Pt 2 at 390 Pa), 1.46 A (Pt 4 at 1030 Pa), 0.58 to 0.89 A (at 2575 RPM), 0.29 to 0.45 A (at 2045 RPM) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 2315 CFM (3935 m³/h) at 0 Pa (0.00 in H₂O), 3100 RPM |
| Nominal Max-Load Duty Point Airflow | 1565 CFM (2660 m³/h) at 3.11 in H₂O (775 Pa), 3100 RPM (Curve Point 3) |
| Operating Duty Point Airflow (3100 RPM) | 1985 CFM (3375 m³/h) at 1.57 in H₂O (390 Pa, Pt 2); 1005 CFM (1705 m³/h) at 4.14 in H₂O (1030 Pa, Pt 4) |
| Operating Duty Point Airflow (2575 RPM) | 1905 CFM (3235 m³/h) at 0 Pa (Pt 5); 1640 CFM (2790 m³/h) at 1.08 in H₂O (269 Pa, Pt 6); 1295 CFM (2195 m³/h) at 2.14 in H₂O (534 Pa, Pt 7); 825 CFM (1405 m³/h) at 2.81 in H₂O (700 Pa, Pt 8) |
| Operating Duty Point Airflow (2045 RPM) | 1515 CFM (2570 m³/h) at 0 Pa (Pt 9); 1305 CFM (2215 m³/h) at 0.68 in H₂O (170 Pa, Pt 10); 1025 CFM (1745 m³/h) at 1.35 in H₂O (337 Pa, Pt 11); 655 CFM (1115 m³/h) at 1.77 in H₂O (442 Pa, Pt 12) |
| ErP Optimum Efficiency Duty Point | 1415.5 CFM (2405 m³/h) at 3.39 in H₂O (844 Pa), 3120 RPM |
| Max. Static Pressure (Measured Table) | 4.14 in H₂O (1030 Pa) at 1005 CFM (1705 m³/h), Curve Point 4 |
| Max. Static Pressure (Chart Curve) | 4.62 in H₂O (1150 Pa) Shut-Off on 4.82 in H₂O (1200 Pa) Chart Axis (Measurement LU-130335-1) |
| Sound Pressure Level (Max. Load) | 72 dB(A) Intake at 1 m (Curve Point 3, 775 Pa) |
| Free-Air Sound Pressure Level | 78 dB(A) Intake at 1 m (Curve Point 1, 0 Pa) |
| Curve Sound Pressure Levels (Intake) | 75 dB(A) (Pt 2, 390 Pa), 76 dB(A) (Pt 4, 1030 Pa), 68 to 74 dB(A) (at 2575 RPM), 63 to 69 dB(A) (at 2045 RPM) |
| Sound Power Level (Max. Load) | 80 dB(A) Intake / 86 dB(A) Outlet (Curve Point 3, ISO 13347) |
| Free-Air Sound Power Level | 86 dB(A) Intake / 93 dB(A) Outlet (Curve Point 1, ISO 13347) |
| Curve Sound Power Levels (Intake / Outlet) | 83 / 90 dB(A) (Pt 2), 83 / 89 dB(A) (Pt 4), 76–82 / 82–88 dB(A) (at 2575 RPM), 71–77 / 77–83 dB(A) (at 2045 RPM) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes = 61.1% (2015 Target: 51.5%), Efficiency Grade N = 71.6 (2015 Target: 62), Measurement Category A, Specific Ratio 1.01, Integrated VSD (Setup LU-147097) |
| Airflow Direction | Axial Single-Intake via Inlet Nozzle, Radial Centrifugal Discharge |
| Ingress Protection (IP) | IP54 |
| Moisture / Environmental Class | F3-1 |
| Operating Temperature | -25 °C to +60 °C (-13 °F to +140 °F) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Internal Thermal Overload Protector (TOP) for Electronics/Motor, Line Undervoltage & Phase Failure Detection, Power Limiter, Motor Current Limitation, Soft Start |
| Electrical Protection Class | Class I (with customer protective earth connected to housing terminal) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring Circuit Fig. 4, TN System) |
| Insulation Class | Class B |
| Control / Signal Features | RS-485 MODBUS-RTU, 0–10 VDC / PWM Control Input, 4–20 mA Sensor/Control Input, 0–10 VDC Slave Modulation Output, +10 VDC & +20 VDC Auxiliary Supplies, External 24 V Parameterization Input, Floating Status Alarm Relay, SELV Control Isolation |
| Termination Type | Internal Terminal Box (Terminal Blocks PE, KL1, KL2, KL3) |
| Conduit / Cable Gland Ports | 3 × M16 × 1.5 Cable Glands (Accommodates Cable Ø 4 to 10 mm / 0.16 to 0.39 in; Gland Tightening Torque 2.5 ±0.4 Nm; Terminal Cover Screw Torque 3.5 ±0.5 Nm) |
| Power Wiring Pinout (KL1 & PE) | PE: Protective Earth Terminal; KL1-1 (L1), KL1-2 (L2), KL1-3 (L3): 3-Phase Mains Supply (380–480 VAC, 50/60 Hz) |
| Alarm Relay Pinout (KL2) | KL2-1 (NC): Floating Status Contact (Break for Failure); KL2-2 (COM): Changeover Common (2 A, Max. 250 VAC, Min. 10 mA, AC1); KL2-3 (NO): Floating Status Contact (Make for Failure) |
| Control & MODBUS Pinout (KL3) | KL3-1 (OUT): 0–10 VDC Modulation Output (Max. 3 mA, 1 V = 10% to 10 V = 100%); KL3-2 & KL3-8 (GND): SELV Reference Ground; KL3-3 & KL3-7 (0–10 V): Control/Sensor Input (100 kΩ); KL3-4 (+10 V): 10 VDC ±3% Supply (Max. 10 mA); KL3-5 (+20 V): 20 VDC +25%/-10% Supply (Max. 50 mA); KL3-6 (4–20 mA): Current Loop Input (100 Ω); KL3-9 & KL3-11 (RSB): RS-485 MODBUS RSB; KL3-10 & KL3-12 (RSA): RS-485 MODBUS RSA |
| Impeller Size | Ø 280 mm (11.02 in) |
| Outer Dimensions (L × H × D) | 400 × 400 × 257.5 mm (15.75 × 15.75 × 10.14 in) |
| Support Plate Dimensions | 400 × 400 mm (15.75 × 15.75 in) Square Inlet Plate |
| Total Axial Depth | 257.5 ±3 mm (10.14 ±0.12 in) |
| Bracket / Impeller Section Depth | 201 ±1 mm (7.91 ±0.04 in) |
| Inlet Nozzle / Intake Ring Diameter | Ø 298 mm (11.73 in) Outer Nozzle Collar Diameter |
| Mounting Hole Pitch | 350 × 350 mm (13.78 × 13.78 in) Square Bolt Circle on Support Plate |
| Weight | 11.3 kg (24.91 lbs) |
| Blade Count & Geometry | 7 Backward-Curved Single-Intake Centrifugal Blades |
| Bearing Type | Ball Bearing |
| Electronics Housing Material | Die-Cast Aluminum |
| Housing / Scroll / Frame Material | Galvanized Sheet Steel Support Plate & Inlet Nozzle; Black-Painted Steel Support Bracket |
| Impeller / Blade Material | Sheet Aluminum |
| Rotor Surface | Painted Black |
| Direction of Rotation | Clockwise, Viewed Toward Rotor |
| Installation Position | Shaft Horizontal or Rotor on Bottom (Rotor on Top on Request) |
| Condensation Drainage Holes | On Rotor Side |
| Standards & Compliance | CE, EN 61800-5-1, UL 1004-7 + 60730, CSA C22.2 No. 77 + CAN/CSA-E60730-1, CCC, EAC, ISO 5801 Category A, ISO 13347, ErP Directive 2015 |
Applications
ebm-papst K3G280-AU11-C3 RadiPac EC centrifugal fan module is engineered for plug-and-play plenum installation in commercial air handling units (AHUs), data center CRAC and CRAH precision cooling systems, and modular FanGrid ventilation walls. Its integrated mounting plate, intake nozzle, and support bracket allow direct drop-in assembly inside cleanroom recirculation plenums, hospital hygiene ventilation cabinets, and building heat recovery ventilation (HRV) systems. Built-in RS-485 MODBUS-RTU networking and analog sensor loops make it equally suited for automated OEM climate control equipment and high-efficiency MRO retrofits.