4184NXH ebm-papst 24VDC 119x119x38mm DC Axial Cooling Fan

$67.45

ebm-papst 4184NXH 24VDC 119x119x38mm brushless axial fan, 4400RPM, 133.6CFM (227m³/h), 11W, featuring metal housing, ball bearings, plug connection & auto-restart.

SKU: 4184NXH Category: Brand:

Description

ebm-papst 4184NXH (OEM Product Data Sheet 9294310138 / spec code VUC0119YUJBS) is a heavy-duty 4100N series brushless DC tubeaxial cooling fan built with a rugged metal housing, plastic impeller, and precision ball bearing system in a standard 119.0 × 119.0 × 38.0 mm (4.69 × 4.69 × 1.50 in) square frame. Operating on a nominal 24 VDC supply across a broad 12 to 28 VDC voltage range, it delivers a nominal free-air speed of 4,400 RPM while drawing 11.0 W (460 mA) to generate 133.61 CFM (227.0 m³/h) of maximum free-air airflow and up to 0.723 in H₂O (180 Pa) of static pressure.

Engineered for continuous industrial thermal management between -30 °C and +70 °C (-22 °F to +158 °F), this fan features an integrated 2-terminal plug connection, rectifying diode reverse-polarity protection, and automatic locked-rotor restart with a rated L10 service life of 70,000 hours at 40 °C (117,500 hours per IPC 9591).

Key Features

  • High-Pressure Axial Airflow: Delivers 133.61 CFM (227.0 m³/h) free-air flow and 0.723 in H₂O (180 Pa) peak static pressure at 4,400 RPM.
  • Wide 12–28 VDC Operating Envelope: Scales dynamically from 2,500 RPM (2.5 W) at 12 VDC up to 4,750 RPM (15.3 W) at 28 VDC.
  • Rugged Metal Frame & Ball Bearings: Combines a rigid metal wall-ring housing with spring-compensated ball bearings for any-orientation shaft mounting.
  • Integrated Motor Protection Suite: Built-in rectifying diode prevents reverse-polarity damage while cyclic auto-restart limits locked-rotor current to 1,900 mA.
  • Extended Multi-Standard Reliability: Rated for 70,000 hours L10 life at 40 °C and certified to UL 507, CSA, VDE, CE, and EAC standards.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) 4184NXH
OEM Item Number 9294310138 (Spec Code: VUC0119YUJBS)
Product Series 4100N Series
Product Category DC Axial Fans
Fan / Component Type DC Tubeaxial Cooling Fan with Wall Ring
Motor Design / Technology Brushless DC External Rotor Motor
Phase & Supply Type DC Supply
Rated Voltage 24 VDC
Operating Voltage Range 12 to 28 VDC
Min. Starting Voltage 12 VDC
Max. Permissible Voltage 28 VDC
Free-Air Speed (RPM) 4,400 RPM ±7.5% (at 24 VDC Nominal)
Speed at Min. Voltage (12 VDC) 2,500 RPM ±12.5% (at Free Air)
Speed at Max. Voltage (28 VDC) 4,750 RPM ±10% (at Free Air)
Free-Air Power Input 11.0 W ±12.5% (at 24 VDC Nominal)
Power Input at Min. Voltage (12 VDC) 2.5 W ±17.5% (at Free Air)
Power Input at Max. Voltage (28 VDC) 15.3 W ±15% (at Free Air)
Free-Air Current Draw 460 mA ±12.5% (0.46 A at 24 VDC Nominal)
Current Draw at Min. Voltage (12 VDC) 210 mA ±17.5% (0.21 A at Free Air)
Current Draw at Max. Voltage (28 VDC) 545 mA ±15% (0.545 A at Free Air)
Inrush / Starting Current 1,900 mA (1.90 A)
Locked Rotor Current Approx. 1,900 mA (at 24 VDC Nominal)
Airflow (Max. Free Air) 133.61 CFM (227.0 m³/h / 3.78 m³/min at 0 Pa)
Optimal Operating Duty Point 76.52 CFM (130.0 m³/h) at 0.317 in H₂O (79 Pa)
Max. Static Pressure 0.723 in H₂O (180 Pa / 18.35 mmH₂O at 0 CFM)
Aerodynamic Test Standard DIN EN ISO 5801 (Double-Chamber Intake Rig at 1.2 kg/m³, 23 °C)
Free-Air Sound Pressure Level 56.0 dB(A) (Measured at 1 m Intake Distance in Rubber Bands)
Optimal Duty Point Sound Power Level 6.2 bel(A) / 62 dB(A) (at 130.0 m³/h @ 79 Pa per DIN 45635-38 / ISO 10302)
Airflow Direction Air Intake Over Struts
Ingress Protection (IP) IP20
Pollution Degree Pollution Degree 1 (per DIN EN 60664-1)
Operating Temperature -30 °C to +70 °C (-22 °F to +158 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Climatic Humidity Rating Constant Humid Heat per DIN EN 60068-2-78 (14 Days)
Service Life L10 (at 40 °C) 70,000 Hours
Service Life L10 (at Max. Temp) 35,000 Hours (at 70 °C)
Service Life L10IPC 117,500 Hours (at 40 °C per IPC 9591)
Motor & Drive Protection Rectifying Diode Reverse Polarity Protection (Max. Residual Current IF <= 10 mA), Electronic Locked-Rotor Auto-Restart
Locked-Rotor Clock Signal (t3 / t4) 0.6 s On / 10 s Off (Typical)
Electrical Protection Class Protection Class III
Insulation Resistance > 10 MΩ (at 500 VDC for 1 Min after 48h at 95% RH, 25 °C)
Dielectric Strength (Type Test) 500 VAC for 1 Minute (per DIN EN 60950 / VDE 0805 & DIN EN 60335 / VDE 0700)
Dielectric Strength (Routine Test) 850 VDC for 1 Second
Clearance / Creepage Distance 1.0 mm / 1.2 mm (0.039 in / 0.047 in)
Control / Signal Features None (2-Pin Uncontrolled Speed)
Termination Type Integrated 2-Terminal Plug / Pin Connector
Wiring Pinout / Connection 2-Pin Plug (Pin a: -GND)
Dimensions (L × H × D) 119.0 × 119.0 × 38.0 mm (4.69 × 4.69 × 1.50 in)
Housing Section Width 119.0 mm (4.69 in)
Total Axial Depth 38.0 mm (1.50 in)
Mounting Screw Specification ISO 4762 – M3 Degreased (Without Additional Brace or Washer)
Max. Mounting Flange Torque 170 Ncm (15.05 in-lbs at Wire Outlet Corner) / 300 Ncm (26.55 in-lbs at Remaining Corners)
Bearing Axial Clearance 0 mm (Spring-Compensated Ball Bearing)
Weight 0.380 kg (0.838 lbs / 380 g)
Bearing Type Ball Bearing (with Spring Compensation)
Housing / Scroll / Frame Material Metal
Impeller / Blade Material Plastic
Direction of Rotation Clockwise (Looking at Rotor)
Installation Position Any Shaft Orientation (Horizontal or Vertical)
Standards & Compliance UL 507 (File E38324), CSA C22.2 No. 113, VDE (EN 60950 / VDE 0805), CE, EAC
RoHS / Environmental Compliance RoHS3 Compliant

Applications

ebm-papst 4184NXH DC axial cooling fan is engineered for forced-air heat dissipation across high-density industrial automation, power electronics, and telecommunications enclosures. Typical installations include variable frequency drives (VFDs), servo amplifier racks, programmable logic controller (PLC) cabinets, uninterruptible power supply (UPS) rectifier modules, and CNC machine tool control consoles. Its rigid metal frame, spring-compensated ball bearing assembly, and integrated plug termination make it a dependable OEM design-in and direct MRO drop-in replacement for sheltered equipment operating under elevated thermal loads.