W4E560-GN03-01 ebm-papst 230VAC 560mm AC Axial Fan

$617.00

ebm-papst W4E560-GN03-01 (W4E560GN0301) 230VAC 560mm HyBlade AC axial fan, 1185/1330RPM, 6715CFM, 1010W, with square full nozzle, M4E110-GF motor & IP54.

SKU: W4E560-GN03-01 Category: Brand:

Description

ebm-papst W4E560-GN03-01 (also known as W4E560GN0301) is a heavy-duty S-series HyBlade AC axial fan with a square full nozzle and guard grille, powered by an integrated M4E110-GF external rotor motor across a 560 mm (22.05 in) impeller diameter. Operating on single-phase 230 VAC at 50 Hz, it delivers 6715 CFM (11410 m³/h) of free-air volume at 1330 RPM (876 W / 3.81 A) and sustains 4555 CFM (7740 m³/h) at its nominal maximum back pressure of 0.48 in H₂O (120 Pa) at 1185 RPM (1010 W / 4.38 A).

Engineered for demanding industrial climates from -40 °C to +50 °C (-40 °F to +122 °F), the assembly combines five hybrid aluminum-core/PP-sprayed sickle blades (-5° pitch) with a pre-galvanized RAL 9005 black plastic-coated steel nozzle housing and guard grille. Maintenance-free ball bearings, an IP54 and H2 environmental rating, internal Thermal Overload Protector (TOP) wiring, and a top-mounted PP plastic terminal box ensure dependable continuous S1 operation.

Key Features

  • HyBlade Aerodynamic Performance: Delivers 6715 CFM (11410 m³/h) free-air flow and 4555 CFM (7740 m³/h) at 120 Pa (0.48 in H₂O).
  • Hybrid Sickle Impeller Construction: Five sickle-shaped blades (-5° pitch) feature a sheet aluminum insert sprayed with PP plastic for reduced acoustic emissions.
  • Full Square Nozzle & Guard: Pre-galvanized sheet steel full nozzle and steel guard grille finished in black plastic coating (RAL 9005).
  • Integrated M4E110-GF AC Drive: Single-phase 230 VAC 50 Hz ball-bearing motor paired with an 18 µF / 400 VDB Class S0 run capacitor.
  • IP54 & H2 Environmental Resilience: Cast aluminum rotor, rotor-side condensation drainage holes, Class F insulation, and -40 °C to +50 °C operating range.
  • Protected Terminal Box Hookup: Axial cable entry (6–12 mm diameter) with dedicated gray leads for the internal Thermal Overload Protector (TOP).

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) W4E560-GN03-01
Alternate Part Number W4E560GN0301
OEM Item Number 13441-5-9980
Integrated Motor Model M4E110-GF (Motor Size 110)
Product Series S Series HyBlade (W4E)
Product Category AC Axial Fans
Fan / Component Type AC Axial Fan with Square Full Nozzle & Guard Grille
Motor Design / Technology AC External Rotor Induction Motor (Capacitor-Run)
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 Hz
Speed (Max. Load) 1185 RPM (at 120 Pa / 0.48 in H₂O)
Free-Air Speed (RPM) 1330 RPM (at 0 Pa / Point 1)
Intermediate Curve Speed (RPM) 1295 RPM (at 40 Pa / Point 2), 1265 RPM (at 80 Pa / Point 3)
Power Rating (Max. Load) 1010 W (at 120 Pa / 0.48 in H₂O)
Free-Air Power Input 876 W (at 0 Pa / Point 1)
Intermediate Curve Power Input 931 W (at 40 Pa / Point 2), 969 W (at 80 Pa / Point 3)
Rated Current (Max. Load) 4.38 A (at 120 Pa / 0.48 in H₂O)
Free-Air Current Draw 3.81 A (at 0 Pa / Point 1)
Intermediate Curve Current Draw 4.03 A (at 40 Pa / Point 2), 4.20 A (at 80 Pa / Point 3)
Inrush / Starting Current 6.5 A
Run Capacitor 18 µF, 400 VDB (Safety Protection Class S0 per EN 60252-1)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 6715 CFM (11410 m³/h) at 0 Pa (Point 1)
Operating Duty Point Airflow 6105 CFM (10370 m³/h) at 0.16 in H₂O (40 Pa, Point 2); 5395 CFM (9165 m³/h) at 0.32 in H₂O (80 Pa, Point 3); 4555 CFM (7740 m³/h) at 0.48 in H₂O (120 Pa, Point 4 Max. Load)
Max. Static Pressure 0.48 in H₂O (120 Pa)
Sound Pressure Level (Max. Load) 67 dB(A) (Intake side LpAin at 1 m, 120 Pa / Point 4)
Free-Air Sound Pressure Level 68 dB(A) (Intake side LpAin at 1 m, 0 Pa / Point 1)
Intermediate Sound Pressure Level 66 dB(A) (Intake side LpAin at 1 m, 40 Pa & 80 Pa / Points 2 & 3)
Sound Power Level (Max. Load) 74 dB(A) Intake (LwAin) / 73 dB(A) Outlet (LwAout) at 120 Pa (Point 4)
Free-Air Sound Power Level 75 dB(A) Intake (LwAin) / 76 dB(A) Outlet (LwAout) at 0 Pa (Point 1)
Intermediate Sound Power Level 73 dB(A) Intake (LwAin) / 73 dB(A) Outlet (LwAout) at 40 Pa & 80 Pa (Points 2 & 3)
Airflow Direction V (Intake over struts / blowing toward guard grille)
Ingress Protection (IP) IP54
Moisture / Environmental Class H2
Operating Temperature -40 °C to +50 °C (-40 °F to +122 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) with basic insulation (externally wired)
Electrical Protection Class Class I (with customer connection of protective earth)
Touch Current (IEC 60990) <= 3.5 mA (Measuring circuit Fig. 4, TN system)
Insulation Class Class F
Termination Type Terminal Box (Cover tightening torque: 1.5 ± 0.2 Nm)
Cable Exit Orientation Axial
Conduit / Cable Gland Ports Cable diameter min. 6 mm (0.24 in), max. 12 mm (0.47 in); tightening torque 2.0 ± 0.3 Nm
Wiring Pinout / Connection L = U1 = Blue; N = U2 = Black; Z = Brown (Start/Capacitor); PE = Green/Yellow; TOP = Gray (Thermal Overload Protector)
Impeller Size Ø 560 mm (22.05 in)
Weight 21.7 kg (47.84 lbs)
Blade Count & Geometry 5 Sickle-Shaped HyBlade Blades (-5° Blade Pitch)
Bearing Type Ball Bearing
Electronics Housing Material PP Plastic (Terminal Box)
Housing / Scroll / Frame Material Sheet Steel, Pre-Galvanized and Coated with Black Plastic (RAL 9005)
Impeller / Blade Material Sheet Aluminum Insert, Sprayed with PP Plastic (HyBlade)
Guard Grille Material Steel, Coated with Black Plastic (RAL 9005)
Rotor Surface Cast in Aluminum
Direction of Rotation Counterclockwise, Viewed Toward Rotor
Installation Position Shaft Horizontal or Rotor on Bottom (Rotor on Top on Request)
Condensation Drainage Holes On Rotor Side
Standards & Compliance EN 61800-5-1, EN 60252-1, IEC 60990, ISO 5801 (Category A, Measurement LU-129185-1), ISO 13347, VDE, EAC

Applications

The ebm-papst W4E560-GN03-01 square-plate HyBlade axial fan is engineered for high-volume heat rejection across commercial and industrial HVACR and process cooling infrastructure. Typical OEM installations and MRO replacement scenarios include air-cooled refrigeration condensers, chiller condenser banks, dry coolers, heat pump outdoor units, and large industrial heat exchangers. Its rigid pre-galvanized full nozzle plate and weather-resistant construction also suit factory wall ventilation, agricultural climate control plenums, and transformer radiator cooling modules operating in harsh outdoor or washdown environments.