Description
ebm-papst R4E310-AP11-01 (also known as R4E310AP1101) is an unhoused, single-intake backward-curved AC centrifugal motorized impeller powered by an integrated M4E074-DF external rotor motor with a 310 mm (12.20 in) impeller diameter. Operating on single-phase 230 VAC (50/60 Hz) power, it delivers a free-air flow of 1,230 CFM (2,085 m³/h) at 1,390 RPM (115 W, 0.52 A) on 50 Hz and 1,395 CFM (2,370 m³/h) at 1,580 RPM (160 W, 0.70 A) on 60 Hz, reaching peak curve power of 145 W (50 Hz) and 201 W (60 Hz) under back-pressure load.
Engineered for continuous S1 industrial duty, this 6-blade sheet aluminum impeller assembly features precision ball bearings, a black-painted rotor with condensation drainage holes, internally connected thermal overload protection (TOP), IP44 environmental ingress rating, and a 4G 0.5 mm² silicone lead cable.
Key Features
- Dual-Frequency Aerodynamic Output: Delivers 1,230 CFM (2,085 m³/h) at 50 Hz and 1,395 CFM (2,370 m³/h) at 60 Hz free air.
- Backward-Curved Aluminum Impeller: Unhoused 310 mm 6-blade sheet aluminum impeller provides high static efficiency without requiring a scroll housing.
- Integrated External Rotor Motor: Driven by an M4E074-DF single-phase AC motor paired with a 4 µF / 400 VDB run capacitor.
- Internal Thermal Overload Protection: Built-in thermal overload protector (TOP) and Class F insulation prevent motor overheating under high back pressure.
- Industrial IP44 & H1 Durability: Ball bearing construction with rotor-side condensation drainage holes supports operation up to +65 °C at 50 Hz.
- High-Temp Silicone Harness: Terminated with a variable-exit 4G 0.5 mm² silicone cable featuring 4x spliced leads for reliable cabinet wiring.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R4E310-AP11-01 |
| Alternate Part Number | R4E310AP1101 |
| OEM Item Number | 15245-5-9980 |
| Integrated Motor Model | M4E074-DF (Motor Size 74) |
| Product Series | R4E310 |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | Backward-Curved Motorized Impeller (Single-Intake, Unhoused) |
| Motor Design / Technology | 4-Pole AC External Rotor Capacitor-Run Induction Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Free-Air Speed (RPM) | 1,390 RPM (50 Hz) / 1,580 RPM (60 Hz) (Nominal Data at 0 Pa) |
| Speed (Curve Point 2) | 1,350 RPM at 90 Pa (50 Hz) / 1,480 RPM at 100 Pa (60 Hz) |
| Speed (Peak Power Load – Point 3) | 1,325 RPM at 160 Pa (50 Hz) / 1,395 RPM at 180 Pa (60 Hz) |
| Speed (High-Pressure Load – Point 4) | 1,350 RPM at 220 Pa (50 Hz) / 1,495 RPM at 280 Pa (60 Hz) |
| Free-Air Power Input | 115 W (50 Hz) / 160 W (60 Hz) (Nominal Data at 0 Pa) |
| Power Input (Curve Point 2) | 135 W at 90 Pa (50 Hz) / 186 W at 100 Pa (60 Hz) |
| Max. Curve Power Input (Point 3) | 145 W at 160 Pa (50 Hz) / 201 W at 180 Pa (60 Hz) |
| Power Input (High-Pressure Load – Point 4) | 135 W at 220 Pa (50 Hz) / 183 W at 280 Pa (60 Hz) |
| Free-Air Current Draw | 0.52 A (50 Hz) / 0.70 A (60 Hz) (Nominal Data at 0 Pa) |
| Current Draw (Curve Point 2) | 0.60 A at 90 Pa (50 Hz) / 0.81 A at 100 Pa (60 Hz) |
| Max. Curve Current Draw (Point 3) | 0.64 A at 160 Pa (50 Hz) / 0.87 A at 180 Pa (60 Hz) |
| Current Draw (High-Pressure Load – Point 4) | 0.60 A at 220 Pa (50 Hz) / 0.79 A at 280 Pa (60 Hz) |
| Inrush / Starting Current | 1.20 A (50 Hz) / 1.15 A (60 Hz) |
| Run Capacitor | 4 µF, 400 VDB (Standard S0 per CE) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 1,230 CFM (2,085 m³/h) at 50 Hz / 1,395 CFM (2,370 m³/h) at 60 Hz (at 0 Pa) |
| Operating Duty Point Airflow (Point 2) | 980 CFM (1,660 m³/h) at 0.36 in H₂O (90 Pa) (50 Hz) / 1,090 CFM (1,855 m³/h) at 0.40 in H₂O (100 Pa) (60 Hz) |
| Operating Duty Point Airflow (Peak Load – Point 3) | 740 CFM (1,260 m³/h) at 0.64 in H₂O (160 Pa) (50 Hz) / 790 CFM (1,340 m³/h) at 0.72 in H₂O (180 Pa) (60 Hz) |
| Operating Duty Point Airflow (High Pressure – Point 4) | 450 CFM (770 m³/h) at 0.88 in H₂O (220 Pa) (50 Hz) / 455 CFM (770 m³/h) at 1.12 in H₂O (280 Pa) (60 Hz) |
| Max. Tested Curve Static Pressure (Point 4) | 0.88 in H₂O (220 Pa) at 50 Hz / 1.12 in H₂O (280 Pa) at 60 Hz |
| Min. Back Pressure | 0 Pa (0 in H₂O) |
| Air Performance Test Standard | ISO 5801 Installation Category A (Measurements LU-53848-1 & LU-53849-1 at ρ = 1.2 kg/m³) |
| Ingress Protection (IP) | IP44 (Installation- and position-dependent per EN 60034-5) |
| Moisture / Environmental Class | H1 |
| Operating Temperature (50 Hz) | -25 °C to +65 °C (-13 °F to +149 °F) |
| Operating Temperature (60 Hz) | -25 °C to +50 °C (-13 °F to +122 °F) |
| Storage / Transport Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) internally connected |
| Electrical Protection Class | Class I (with customer connection of protective earth) |
| Touch Current (IEC 60990) | < 0.75 mA (Measuring circuit Fig. 4, TN system) |
| Insulation Class | Class “F” |
| Termination Type | Silicone Cable with 4x Splice |
| Cable Exit Orientation | Variable |
| Lead Wire Gauge & Spec | 4G 0.5 mm² (4-conductor silicone jacketed cable) |
| Wiring Pinout / Connection | U1 = Blue, Z = Brown, U2 = Black, PE = Green/Yellow |
| Impeller Size | Ø 310 mm (12.20 in) |
| Max. Screw Clearance | 10 mm (0.394 in) |
| Weight | 3.8 kg (8.38 lbs) |
| Blade Count & Geometry | 6 Backward-Curved Blades (Single-Intake) |
| Bearing Type | Ball Bearing |
| Impeller / Blade Material | Sheet Aluminum |
| Rotor Surface | Painted Black |
| Direction of Rotation | Clockwise, viewed toward rotor |
| Installation Position | Shaft horizontal or rotor on bottom (rotor on top available on request) |
| Condensation Drainage Holes | On rotor side |
| Compatible Inlet Ring (Optional) | 31050-2-4013 (Not included in scope of delivery) |
| Standards & Compliance | EN 60335-1, EN 60034-5, IEC 60990, ISO 5801, ISO 13347, CE, CCC |
Applications
ebm-papst R4E310-AP11-01 backward-curved motorized impellers are widely deployed in commercial and industrial plenum pressurization systems where compact axial depth and scroll-free radial discharge are required. Typical OEM installations and MRO replacement environments include data center CRAC/CRAH precision air conditioning units, cleanroom Fan Filter Units (FFUs), rooftop heat recovery ventilation (HRV) air handlers, and ducted commercial HVAC supply and exhaust plenums. Its sheet aluminum impeller and high-temperature silicone harness also make it well suited for industrial power electronics cabinets, chiller condenser modules, and process drying equipment.