Description
ebm-papst R4D500-RA03-01 (also known as R4D500RA0301) is a 500 mm (19.69 in) single-intake, backward-curved RadiCal AC centrifugal motorized impeller powered by an integrated 3-phase M4D138-HF external rotor motor. Configured for dual-voltage 50 Hz operation via Delta (230 VAC) or Star (400 VAC) wiring, this unit delivers up to 5,595 CFM (9,510 m³/h) of free-air volume flow at 1,410 RPM and operates at 1,370 RPM with 1,520 W power input under maximum load conditions (500 Pa / 2.01 in H₂O).
Engineered for demanding industrial environments, it combines a 7-blade polypropylene (PP) impeller with a cast-aluminum rotor surface, maintenance-free ball bearings, and an IP54 / H2 environmental protection rating. Integrated thermal overload protection (TOP) wired out via a lateral 9-core halogen-free cable with crimped splices ensures dependable Class I continuous-duty (S1) operation across ambient temperatures from -40 °C to +55 °C (-40 °F to +131 °F).
Key Features
- High-Output RadiCal Aerodynamics: 500 mm backward-curved 7-blade PP impeller delivers 5,595 CFM (9,510 m³/h) free air and handles up to 650 Pa back pressure.
- Dual-Voltage 3-Phase M4D138-HF Motor: Supports 230 VAC Delta (5.04 A) and 400 VAC Star (2.91 A) 50 Hz connections with reversible phase rotation.
- ErP 2015 Static Efficiency Compliance: Achieves 53.4% overall static efficiency (Grade N = 62) under EU Regulation 327/2011 without requiring an external VSD.
- IP54 & H2 Environmental Durability: Cast-aluminum rotor, ball bearings, and dual-side condensation drainage holes safeguard continuous S1 operation from -40 °C to +55 °C.
- Integrated Thermal Overload Protection: Built-in TOP sensor with dedicated gray lead wires prevents motor overheating when connected to external control switchgear.
- Pre-Terminated Halogen-Free Harness: Lateral 9 x 0.75 mm² halogen-free connection cable with crimped splices simplifies Delta/Star power and protective earth wiring.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R4D500-RA03-01 |
| Alternate Part Number | R4D500RA0301 |
| OEM Item Number | 12089-5-9980 |
| Integrated Motor Model | M4D138-HF (Motor Size 138) |
| Product Series | RadiCal |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | Backward-Curved Single-Intake Motorized Impeller (Unhoused) |
| Motor Design / Technology | 3-Phase AC External Rotor Induction Motor |
| Phase & Supply Type | 3~ (Three-Phase AC, Delta Δ / Star Y Configurable) |
| Rated Voltage | 230 VAC (Delta Δ) / 400 VAC (Star Y) |
| Frequency | 50 Hz |
| Speed (Max. Load) | 1370 RPM (at 500 Pa / 2.01 in H₂O, Point 3) |
| Free-Air Speed (RPM) | 1410 RPM (at 0 Pa / 0.00 in H₂O, Point 1) |
| Intermediate Curve Speed (Point 2) | 1390 RPM (at 250 Pa / 1.00 in H₂O) |
| High-Pressure Curve Speed (Point 4) | 1380 RPM (at 650 Pa / 2.61 in H₂O) |
| ErP Optimum Speed (RPM) | 1370 RPM (at 527 Pa / 2.118 in H₂O) |
| Power Rating (Max. Load) | 1520 W (at 500 Pa / 2.01 in H₂O, Point 3) |
| Free-Air Power Input | 1125 W (at 0 Pa / 0.00 in H₂O, Point 1) |
| Intermediate Curve Power Input (Point 2) | 1350 W (at 250 Pa / 1.00 in H₂O) |
| High-Pressure Curve Power Input (Point 4) | 1385 W (at 650 Pa / 2.61 in H₂O) |
| ErP Optimum Efficiency Power | 1510 W (1.51 kW at 527 Pa / 2.118 in H₂O) |
| Rated Current (Max. Load) | 5.04 A (at 230 VAC Δ) / 2.91 A (at 400 VAC Y, Point 3) |
| Free-Air Current Draw | 2.44 A (at 400 VAC Y, 0 Pa, Point 1) |
| Intermediate Curve Current Draw (Point 2) | 2.71 A (at 400 VAC Y, 250 Pa) |
| High-Pressure Curve Current Draw (Point 4) | 2.75 A (at 400 VAC Y, 650 Pa) |
| Inrush / Starting Current | 24 A (at 230 VAC Δ) / 14 A (at 400 VAC Y) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 5595 CFM (9510 m³/h) at 0 Pa (0.00 in H₂O, Point 1) |
| Operating Duty Point Airflow (Point 2) | 4720 CFM (8020 m³/h) at 1.00 in H₂O (250 Pa) |
| Operating Duty Point Airflow (Max. Load, Point 3) | 3555 CFM (6040 m³/h) at 2.01 in H₂O (500 Pa) |
| Operating Duty Point Airflow (High Pressure, Point 4) | 2360 CFM (4010 m³/h) at 2.61 in H₂O (650 Pa) |
| ErP Optimum Efficiency Duty Point | 3248.9 CFM (5520 m³/h) at 2.118 in H₂O (527 Pa) |
| Max. Static Pressure (Tested Curve Point 4) | 2.61 in H₂O (650 Pa) |
| Min. Back Pressure | 0 in H₂O (0 Pa) |
| Sound Power Level (Max. Load, Point 3) | 73 dB(A) LwAin (Intake, ISO 13347 at 500 Pa) |
| Free-Air Sound Power Level (Point 1) | 81 dB(A) LwAin (Intake, ISO 13347 at 0 Pa) |
| Intermediate Curve Sound Power Level (Point 2) | 77 dB(A) LwAin (Intake, ISO 13347 at 250 Pa) |
| High-Pressure Curve Sound Power Level (Point 4) | 73 dB(A) LwAin (Intake, ISO 13347 at 650 Pa) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes = 53.4%, Efficiency Grade N = 62, Measurement Category A, Specific Ratio = 1.01 (Test Setup LU-136742) |
| Airflow Direction | Single-Intake Axial Suction, Radial Discharge |
| Ingress Protection (IP) | IP54 |
| Moisture / Environmental Class | H2 |
| Operating Temperature | -40 °C to +55 °C (-40 °F to +131 °F; continuous operation below -25 °C requires low-temp bearings) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) with basic insulation (external customer connection required) |
| Electrical Protection Class | Class I (with customer connection of protective earth) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring circuit Fig. 4, TN system) |
| Insulation Class | Class F |
| Termination Type | 9-wire halogen-free cable with 9x crimped splices |
| Cable Exit Orientation | Lateral |
| Lead Wire Gauge & Spec | 9 x 0.75 mm² (Halogen-free) |
| Wiring Pinout / Connection | L1 (U1) = Black, L2 (V1) = Blue, L3 (W1) = Brown, W2 = Yellow, U2 = Green, V2 = White, TOP = 2x Gray, PE = Green/Yellow (Reversible rotation via swapping 2 phases) |
| Impeller Size | Ø 500 mm (19.69 in) |
| Max. Screw Clearance | 18 mm (0.71 in) |
| Weight | 21.5 kg (47.40 lbs) |
| Blade Count & Geometry | 7 Backward-Curved RadiCal Blades |
| Bearing Type | Ball Bearing |
| Impeller / Blade Material | PP Plastic (Polypropylene) |
| Rotor Surface | Cast in Aluminum |
| Direction of Rotation | Clockwise, viewed toward rotor (Reversible by swapping two supply phases) |
| Installation Position | Any |
| Condensation Drainage Holes | On rotor and stator sides |
| Compatible Inlet Ring (Optional) | ebm-papst 50901-2-2943 (Not included in scope of delivery) |
| Standards & Compliance | EN 60034-1 (2010), EN 17166, ISO 5801 Cat. A, ISO 13347, CE, VDE, EAC |
Applications
ebm-papst R4D500-RA03-01 backward-curved RadiCal centrifugal motorized impellers are engineered for pressurized plenum installations in commercial air handling units (AHUs), data center CRAC/CRAH precision cooling systems, and large building heat recovery ventilation (HRV) assemblies. Their unhoused radial discharge geometry and high static pressure capability make them equally well-suited for industrial process chillers, cleanroom air filtration plenums, and heavy-duty power electronics or wind turbine converter cooling cabinets. Equipment manufacturers and MRO technicians rely on this unit for direct drop-in replacement and custom ducted ventilation retrofits where environmental moisture resistance and low acoustic emissions are critical.