Description
ebm-papst R4D450-RH01-01 (also known as R4D450RH0101) is a 450 mm (17.72 in) RadiCal backward-curved, single-intake AC centrifugal fan with integrated M4D110-GF motor. Its three-phase electrical configuration supports 230 VAC delta, 277 VAC delta, 400 VAC star, and 480 VAC star operation across 50 and 60 Hz variants, with nominal speeds from 1350 to 1600 rpm and power from 710 to 1140 W. The fan uses a cast-aluminum rotor surface, six-blade PP impeller, ball bearings, clockwise rotation, and a silicone nine-conductor cable with crimped splices. IP54 protection, Class F insulation, S1 duty, rotor-side drainage, and a thermal overload protector with basic insulation support industrial service.
Key Features
- RadiCal Aerodynamics: Backward-curved, single-intake centrifugal geometry delivers high-volume airflow against substantial system resistance.
- Three-Phase Flexibility: Delta and star wiring supports multiple 230, 277, 400, and 480 VAC operating configurations.
- Motor Integration: M4D110-GF motor provides nominal operating speeds from 1350 to 1600 rpm across rated frequencies.
- Construction: Cast-aluminum rotor surface and six-blade PP impeller combine low mass with corrosion-resistant airflow components.
- Protection: IP54 enclosure protection, Class F insulation, Class I grounding, and integrated TOP thermal overload protection.
- Installation: Shaft-horizontal or rotor-bottom mounting is specified, with rotor-top installation available on request.
- Connection: Silicone 9G 0.75 mm² cable uses nine crimped splices and documented delta/star color-coded phase connections.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R4D450-RH01-01 |
| Alternate Part Number | R4D450RH0101 |
| Integrated Motor Model | M4D110-GF |
| Product Series | RadiCal |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | AC centrifugal fan, backward-curved, single-intake |
| Motor Design / Technology | Three-phase AC motor |
| Phase & Supply Type | 3~ AC supply |
| Rated Voltage | 230 VAC delta; 277 VAC delta; 400 VAC star; 480 VAC star |
| Frequency | 50 Hz and 60 Hz |
| Wiring Configuration | Delta at 230 VAC and 277 VAC; star at 400 VAC and 480 VAC |
| Speed (RPM) | 1350 rpm at 230 VAC/50 Hz delta; 1500 rpm at 230 VAC/60 Hz delta; 1600 rpm at 277 VAC/60 Hz delta; 1350 rpm at 400 VAC/50 Hz star; 1500 rpm at 400 VAC/60 Hz star; 1600 rpm at 480 VAC/60 Hz star |
| Power Rating | 710 W at 230 VAC/50 Hz delta; 1060 W at 230 VAC/60 Hz delta; 1140 W at 277 VAC/60 Hz delta; 710 W at 400 VAC/50 Hz star; 1060 W at 400 VAC/60 Hz star; 1140 W at 480 VAC/60 Hz star |
| Rated Current | 2.51 A at 230 VAC/50 Hz delta; 3.18 A at 230 VAC/60 Hz delta; 3.05 A at 277 VAC/60 Hz delta; 1.45 A at 400 VAC/50 Hz star; 1.84 A at 400 VAC/60 Hz star; 1.76 A at 480 VAC/60 Hz star |
| Starting Current | 10.6 A at 230 VAC/50 Hz delta; 9.7 A at 230 VAC/60 Hz delta; 12.1 A at 277 VAC/60 Hz delta; 6.1 A at 400 VAC/50 Hz star; 5.6 A at 400 VAC/60 Hz star; 7.0 A at 480 VAC/60 Hz star |
| Minimum Back Pressure | 0 Pa (0 in H₂O) |
| Nominal Airflow | 3385 m³/h (1992 cfm) |
| Nominal Pressure Increase | 376 Pa (1.51 in H₂O) |
| Nominal Efficiency | 52.2% and 49.7% |
| Measurement Category | A |
| Efficiency Category | Static |
| Efficiency Grade N | 64.5 and 62 |
| Required Power | 0.67 kW |
| Specific Ratio | 1.00 |
| Ecodesign Measurement | LU-143240 |
| Impeller Size | 450 mm nominal (17.72 in) |
| Blade Count & Geometry | 6 backward-curved blades |
| Motor Size | 110 mm |
| Impeller / Blade Material | PP plastic |
| Rotor Surface | Cast aluminum |
| Bearing Type | Ball bearing |
| Direction of Rotation | Clockwise, viewed toward rotor |
| Installation Position | Shaft horizontal or rotor on bottom; rotor on top on request |
| Condensation Drainage Holes | On rotor side |
| Operating Mode / Duty Cycle | S1 |
| Weight | 9.4 kg (20.72 lb) |
| Product Drawing Dimensional Data | The datasheet states that dimensions must be requested from ebm-papst |
| Maximum Screw Clearance | 12 mm (0.47 in) |
| Accessory Inlet Ring | 45901-2-2943; not included in scope of delivery |
| Termination Type | Silicone cable with crimped splices |
| Lead Wire Gauge & Spec | 9G, 0.75 mm² conductors |
| Wiring Pinout / Connection | L1 black; L2 blue; L3 brown; U1 black; V1 blue; W1 brown; U2 green; V2 white; W2 yellow; TOP gray |
| Connection Diagram | Delta and star connection diagrams provided; reverse any two phases to change rotation direction |
| Thermal Protection | Thermal overload protector (TOP) with basic insulation |
| Electrical Protection Class | Class I with customer connection of protective earth |
| Touch Current | <= 3.5 mA according to IEC 60990 measuring circuit Fig. 4, TN system |
| Insulation Class | Class F |
| Ingress Protection (IP) | IP54 |
| Moisture / Environmental Class | H2 |
| Operating Ambient Temperature | -40 °C to +60 °C (-40 °F to +140 °F) at specified 50 Hz points; -40 °C to +50 °C (-40 °F to +122 °F) at specified 60 Hz points |
| Motor Transport / Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| 50 Hz Measured Point 1 | 400 VAC star, 1405 rpm, 496 W, 1.17 A, 6015 m³/h (3540 cfm), 0 Pa (0.00 in H₂O), LpAin 68 dB(A), LwAin 77 dB(A), LwAout 84 dB(A) |
| 50 Hz Measured Point 2 | 400 VAC star, 1370 rpm, 646 W, 1.33 A, 4975 m³/h (2930 cfm), 200 Pa (0.80 in H₂O), LpAin 66 dB(A), LwAin 75 dB(A), LwAout 81 dB(A) |
| 50 Hz Measured Point 3 | 400 VAC star, 1350 rpm, 710 W, 1.45 A, 3685 m³/h (2170 cfm), 350 Pa (1.41 in H₂O), LpAin 62 dB(A), LwAin 70 dB(A), LwAout 77 dB(A) |
| 50 Hz Measured Point 4 | 400 VAC star, 1370 rpm, 637 W, 1.31 A, 2235 m³/h (1315 cfm), 440 Pa (1.77 in H₂O), LpAin 66 dB(A), LwAin 75 dB(A), LwAout 81 dB(A) |
| 60 Hz Measured Point 1 | 480 VAC star, 1665 rpm, 821 W, 1.43 A, 7245 m³/h (4265 cfm), 0 Pa (0.00 in H₂O) |
| 60 Hz Measured Point 2 | 480 VAC star, 1630 rpm, 1010 W, 1.64 A, 6325 m³/h (3725 cfm), 217 Pa (0.87 in H₂O) |
| 60 Hz Measured Point 3 | 480 VAC star, 1600 rpm, 1140 W, 1.76 A, 4940 m³/h (2905 cfm), 445 Pa (1.79 in H₂O) |
| 60 Hz Measured Point 4 | 480 VAC star, 1610 rpm, 1080 W, 1.71 A, 3150 m³/h (1855 cfm), 609 Pa (2.44 in H₂O) |
| 60 Hz Measured Point 5 | 400 VAC star, 1610 rpm, 771 W, 1.42 A, 6995 m³/h (4120 cfm), 0 Pa (0.00 in H₂O) |
| 60 Hz Measured Point 6 | 400 VAC star, 1555 rpm, 931 W, 1.66 A, 6065 m³/h (3570 cfm), 200 Pa (0.80 in H₂O) |
| 60 Hz Measured Point 7 | 400 VAC star, 1500 rpm, 1060 W, 1.84 A, 4685 m³/h (2755 cfm), 400 Pa (1.61 in H₂O) |
| 60 Hz Measured Point 8 | 400 VAC star, 1525 rpm, 990 W, 1.74 A, 2990 m³/h (1760 cfm), 550 Pa (2.21 in H₂O) |
| Air Performance Test Standard | ISO 5801 installation category A |
| Test Air Density | 1.15 kg/m³ ±2% |
| Sound Measurement Standard | Sound power according to ISO 13347; sound pressure measured at 1 m from fan axis |
| Standards & Compliance | EN 60034-1 (2004), UKCA, CE, CSA C22.2 No. 100, CCC, EAC, VDE, UL 1004-1 |
Applications
ebm-papst R4D450-RH01-01 is an industrial centrifugal fan for data-center CRAC and CRAH units, cleanroom fan-filter plenums, and heat-recovery ventilation equipment. Its backward-curved single-intake architecture suits telecom and power-electronics cabinet cooling, air-handling skids, and equipment requiring controlled airflow against system resistance. OEM builders and MRO teams can also apply it in commercial HVAC modules, process-air machinery, drying systems, and enclosure ventilation assemblies where robust three-phase operation and documented thermal protection are required.