Description
ebm-papst R3G220-RC05-03 (also known as R3G220RC0503, OEM Item No. 51016-5-9980) is an unhoused backward-curved single-inlet RadiCal EC motorized centrifugal impeller engineered around the integrated M3G055-BI electronically commutated motor with a Ø 220 mm (8.66 in) diameter and 71.0 mm (2.80 in) axial profile. Operating across a 200 to 240 VAC (50/60 Hz) single-phase supply, it delivers a free-air flow of 595 CFM (1015 m³/h) at 2815 RPM and a nominal maximum-load duty point of 325 CFM (550 m³/h) at 1.00 in H₂O (250 Pa) static pressure while drawing 85 W and 0.70 A at 2580 RPM. The assembly pairs a 7-blade fiberglass-reinforced PA polyamide impeller with a die-cast aluminum electronics housing, thick-layer passivated rotor, and precision ball bearings rated for continuous S1 operation from -25 °C to +60 °C (-13 °F to +140 °F).
Built-in IP54 ingress protection, an electrically isolated SELV control interface (0–10 VDC / PWM speed control, 10 VDC supply output, and open-collector tachometer signal), soft start, and locked-rotor/thermal overload protection come pre-wired via dual PVC power (3G AWG 20) and control (4X AWG 22) cables.
Key Features
- High-Efficiency RadiCal Aerodynamics: Seven-blade backward-curved PA plastic impeller delivers 595 CFM (1015 m³/h) free air and peaks beyond 1.30 in H₂O (325 Pa).
- Integrated M3G055-BI EC Drive: Single-phase 200–240 VAC (50/60 Hz) brushless motor limits power input to 85 W (0.70 A) across full-speed load points.
- Isolated SELV Control Interface: Supports 0–10 VDC or PWM stepless speed modulation, 10 VDC (1.1 mA) auxiliary output, and 1 PPR open-collector tachometer.
- Comprehensive Active Drive Protection: Incorporates soft start, motor current and output limiting, line undervoltage/overvoltage detection, locked-rotor protection, and thermal overload protection.
- Rugged IP54 Industrial Construction: Features a die-cast aluminum electronics housing, thick-layer passivated open rotor, and maintenance-free ball bearings for any mounting orientation.
- Dual-Harness Pre-Terminated Wiring: Equipped with variable-exit PVC 3G AWG 20 mains leads and 4X AWG 22 control leads with crimped brass tips.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R3G220-RC05-03 |
| Alternate Part Number | R3G220RC0503 |
| OEM Item Number | 51016-5-9980 |
| Integrated Motor Model | M3G055-BI |
| Product Series | R3G220 RadiCal |
| Product Category | EC Centrifugal Fans |
| Fan / Component Type | Backward-Curved Single-Inlet Motorized Impeller (Unhoused) |
| Motor Design / Technology | Electronically Commutated (EC) External Rotor Motor |
| Phase & Supply Type | 1~ (Single-Phase AC Input with Integrated EC Electronics) |
| Rated Voltage | 230 VAC |
| Operating Voltage Range | 200 to 240 VAC |
| Frequency | 50 / 60 Hz |
| Speed (Max. Load) | 2580 RPM (at Point 3 Nominal Max. Load) |
| Free-Air Speed (RPM) | 2815 RPM (at Point 1, 0 Pa) |
| Operating Curve Speeds (Full & Reduced) | 2660 RPM (Pt 2) / 2620 RPM (Pt 4) / 2200 RPM (Pts 5–8) / 1850–1860 RPM (Pts 9–12) / 1500–1550 RPM (Pts 13–16) |
| Power Rating (Max. Load) | 85 W (at Point 3 Nominal Max. Load) |
| Free-Air Power Input | 85 W (at Point 1, 0 Pa) |
| Reduced-Speed Power Input | 40 to 55 W (at 2200 RPM) / 26 to 34 W (at 1850 RPM) / 17 to 19 W (at 1520 RPM) |
| Rated Current (Max. Load) | 0.70 A (at Point 3 Nominal Max. Load) |
| Free-Air Current Draw | 0.70 A (at Point 1, 0 Pa) |
| Reduced-Speed Current Draw | 0.37 to 0.51 A (at 2200 RPM) / 0.27 to 0.34 A (at 1850 RPM) / 0.19 to 0.21 A (at 1520 RPM) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 595 CFM (1015 m³/h) at 0 in H₂O (0 Pa), 2815 RPM (Point 1) |
| Operating Duty Point Airflow (Point 2) | 470 CFM (800 m³/h) at 0.60 in H₂O (150 Pa), 2660 RPM |
| Operating Duty Point Airflow (Point 3 – Max. Load) | 325 CFM (550 m³/h) at 1.00 in H₂O (250 Pa), 2580 RPM |
| Operating Duty Point Airflow (Point 4 – High Pressure) | 210 CFM (355 m³/h) at 1.30 in H₂O (325 Pa), 2620 RPM |
| Reduced-Speed Curve Duty Points (2200 RPM) | 465 CFM (795 m³/h) at 0 Pa (Pt 5) / 390 CFM (665 m³/h) at 0.41 in H₂O (103 Pa, Pt 6) / 280 CFM (480 m³/h) at 0.76 in H₂O (189 Pa, Pt 7) / 175 CFM (300 m³/h) at 0.92 in H₂O (229 Pa, Pt 8) |
| Reduced-Speed Curve Duty Points (1850 RPM) | 390 CFM (660 m³/h) at 0 Pa (Pt 9) / 325 CFM (555 m³/h) at 0.29 in H₂O (71 Pa, Pt 10) / 235 CFM (400 m³/h) at 0.53 in H₂O (132 Pa, Pt 11) / 150 CFM (250 m³/h) at 0.65 in H₂O (163 Pa, Pt 12) |
| Reduced-Speed Curve Duty Points (1520 RPM) | 320 CFM (540 m³/h) at 0 Pa (Pt 13) / 265 CFM (450 m³/h) at 0.19 in H₂O (47 Pa, Pt 14) / 190 CFM (320 m³/h) at 0.35 in H₂O (86 Pa, Pt 15) / 120 CFM (205 m³/h) at 0.43 in H₂O (108 Pa, Pt 16) |
| Max. Static Pressure (Measured Table) | 1.30 in H₂O (325 Pa) at 210 CFM (355 m³/h) |
| Max. Static Pressure (Chart Curve) | Approx. 1.69 in H₂O (420 Pa) shut-off curve boundary |
| Aerodynamic Measurement Standard | ISO 5801 Installation Category A (Air Density ρ = 1.15 kg/m³ ± 2%, Measurements LU-152958-1 / LU-167052-1 / LU-152961-1) |
| Airflow Direction | Axial Intake, Radial (Centrifugal) Discharge |
| Ingress Protection (IP) | IP54 (Dust Protected, Splash Water Resistant) |
| Operating Temperature | -25 °C to +60 °C (-13 °F to +140 °F) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Locked-Rotor Protection, Over-Temperature Protected Electronics & Motor (TOP), Motor Current Limit, Output Limit, Soft Start, Line Undervoltage Detection, Overvoltage Detection |
| Electrical Protection Class | Class I (with customer-connected protective earth) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring network Fig. 4, TN system) |
| Insulation Class | Class B |
| Control / Signal Features | 0–10 VDC / PWM Control Input, Open-Collector Tachometer Output (1 Pulse/Rev), +10 VDC (max. 1.1 mA) Short-Circuit-Proof Auxiliary Voltage Output, SELV Isolated Control Interface |
| Termination Type | Dual Wire Harness (3-Wire Power Cable + 4-Wire Control Cable) with Crimped Brass Lead Tips |
| Cable Exit Orientation | Variable |
| Lead Wire Gauge & Spec | Power Line: PVC 3G AWG 20 (3x crimped brass lead tips) | Control Line: PVC 4X AWG 22 (4x crimped brass lead tips) |
| Power Wiring Pinout (Cable 1) | CON10 (Black) = L (230 VAC, 50/60 Hz Supply) | CON11 (Blue) = N (Neutral Conductor) | CON12 (Green/Yellow) = PE (Protective Earth) |
| Control & Signal Pinout (Cable 2) | 1 (Blue) = GND | 2 (Yellow) = 0–10 V / PWM Control Input (Electrically Isolated) | 3 (Red) = +10 VDC Output (max. 1.1 mA, Short-Circuit-Proof) | 4 (White) = Tacho Output (Open Collector, 1 Pulse/Rev) |
| Impeller Size | Ø 220 mm (8.66 in) |
| Outer Dimensions (Ø × D) | Ø 220 × 71.0 mm (Ø 8.66 × 2.80 in) |
| Total Axial Depth | 73.0 mm (2.87 in) |
| Max. Screw Clearance | 5 mm (0.20 in) max. screw thread depth |
| Weight | 1.13 kg (2.49 lbs) |
| Blade Count & Geometry | 7 Backward-Curved RadiCal Blades, Single Inlet |
| Bearing Type | Ball Bearing |
| Electronics Housing Material | Die-Cast Aluminum |
| Impeller / Blade Material | PA Plastic (Polyamide) |
| Rotor Surface | Thick Layer Passivated |
| Direction of Rotation | Clockwise, seen on rotor |
| Installation Position | Any |
| Condensation Drainage Holes | None, open rotor |
| Compatible Inlet Ring (Optional) | 09609-2-4013 (Inlet Nozzle, ordered separately) |
| EMC Standards | EN 61000-6-2 (Industrial Immunity), EN 61000-3-2/3 (Harmonics), EN 55022 Class B (Emission) |
| Standards & Compliance | EN 60335-1, CE, UL 2111, CSA C22.2 No. 77, CCC, EAC |
| RoHS / Environmental Compliance | RoHS3 Compliant |
Applications
ebm-papst R3G220-RC05-03 backward-curved EC motorized impellers are engineered for pressurized plenum and ductless air-movement architectures where compact axial depth, low acoustic signature, and demand-controlled airflow modulation are essential. Typical deployments include cleanroom fan filter units (FFUs), data center CRAC/CRAH precision cooling modules, commercial heat recovery ventilation (HRV) and air handling units (AHUs), and medical diagnostic or laboratory environmental chambers. In industrial automation and power electronics, this unhoused RadiCal centrifugal fan provides reliable closed-loop thermal management inside high-density inverter cabinets, telecom rectifiers, and refrigeration condensers.