R2E250-RB06-01 ebm-papst 230VAC 250mm AC Centrifugal Fan

$415.64

ebm-papst R2E250-RB06-01 (R2E250RB0601) 230VAC Ø250mm RadiCal centrifugal fan, 2750/3100RPM, 880/1005CFM, 250/390W, with PA impeller, M2E074-EI motor & IP44.

SKU: R2E250-RB06-01 Category: Brand:

Description

ebm-papst R2E250-RB06-01 (also known as R2E250RB0601) is an unhoused single-intake backward-curved RadiCal AC centrifugal motorized impeller powered by an integrated M2E074-EI external-rotor motor with a 250 mm (9.84 in) diameter and 123 mm (4.84 in) axial depth. Operating on single-phase 230 VAC (50/60 Hz) power with a 5 µF / 450 VDB run capacitor, it delivers 880 CFM (1495 m³/h) at 50 Hz and 1005 CFM (1710 m³/h) at 60 Hz in free air, with nominal maximum-load ratings of 2750 RPM / 250 W / 1.10 A at 50 Hz and 3100 RPM / 390 W / 1.71 A at 60 Hz.

Engineered for continuous S1 industrial duty, the assembly features an aerodynamically optimized 7-blade polyamide (PA) plastic impeller, a black-painted rotor with rotor-side condensation drainage holes, maintenance-free ball bearings, IP44 and H1 environmental protection, internally connected thermal overload protection (TOP), and a 4G 0.5 mm² silicone connection cable with 4 crimped splices.

Key Features

  • Dual-Frequency RadiCal Aerodynamics: Delivers 880 CFM (1495 m³/h) at 50 Hz and 1005 CFM (1710 m³/h) at 60 Hz free air.
  • High Static Pressure Capability: Sustains static pressures up to 2.21 in H₂O (550 Pa) at 50 Hz and 2.81 in H₂O (700 Pa) at 60 Hz.
  • 7-Blade RadiCal PA Impeller: Fiberglass-reinforced polyamide backward-curved geometry minimizes flow losses and lowers intake acoustic emissions.
  • Integrated M2E074-EI External-Rotor Motor: Size 74 ball-bearing motor with Class F insulation, S1 continuous duty, and 5 µF / 450 VDB capacitor pairing.
  • Internal Thermal Overload Protection: Equipped with an internally wired thermal overload protector (TOP) to safeguard windings against overheating.
  • IP44 & H1 Environmental Durability: Black-painted rotor with rotor-side condensation drainage holes operates from -25 °C to +70 °C (50 Hz).
  • Silicone Cable Termination: Variable-exit 4G 0.5 mm² high-temperature silicone lead wire terminated with four factory-crimped splices.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) R2E250-RB06-01
Alternate Part Number R2E250RB0601
OEM Item Number 11456-5-9980
Integrated Motor Model M2E074-EI (Motor Size 74)
Product Series RadiCal R2E250 Series
Product Category AC Centrifugal Fans
Fan / Component Type Backward-Curved Single-Intake Motorized Centrifugal Impeller (Unhoused)
Motor Design / Technology AC External-Rotor Capacitor-Run Induction Motor
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 / 60 Hz
Speed (Max. Load) 2750 RPM (50 Hz) / 3100 RPM (60 Hz)
Free-Air Speed (RPM) 2820 RPM (50 Hz) / 3225 RPM (60 Hz)
Power Rating (Max. Load) 250 W (50 Hz) / 390 W (60 Hz)
Free-Air Power Input 212 W (50 Hz) / 336 W (60 Hz)
Rated Current (Max. Load) 1.10 A (50 Hz) / 1.71 A (60 Hz)
Free-Air Current Draw 0.93 A (50 Hz) / 1.48 A (60 Hz)
Inrush / Starting Current 3.15 A (50 Hz) / 3.00 A (60 Hz)
Run Capacitor 5 µF, 450 VDB (Standard S0 per CE)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 880 CFM / 1495 m³/h (50 Hz) | 1005 CFM / 1710 m³/h (60 Hz) at 0 Pa
Operating Duty Point Airflow (50 Hz) 755 CFM (1285 m³/h) at 0.80 in H₂O (200 Pa) | 575 CFM (980 m³/h) at 1.61 in H₂O (400 Pa, Max. Load) | 350 CFM (595 m³/h) at 2.21 in H₂O (550 Pa)
Operating Duty Point Airflow (60 Hz) 835 CFM (1420 m³/h) at 1.20 in H₂O (300 Pa) | 645 CFM (1095 m³/h) at 2.01 in H₂O (500 Pa, Max. Load) | 370 CFM (630 m³/h) at 2.81 in H₂O (700 Pa)
Max. Measured Curve Static Pressure 2.21 in H₂O (550 Pa) at 50 Hz / 2.81 in H₂O (700 Pa) at 60 Hz
Min. Back Pressure 0 in H₂O (0 Pa)
Sound Pressure Level (Max. Load) 62 dB(A) (50 Hz) / 65 dB(A) (60 Hz) at 1 m Intake
Free-Air Sound Pressure Level 69 dB(A) (50 Hz) / 73 dB(A) (60 Hz) at 1 m Intake
Sound Power Level (Max. Load) 71 dB(A) (50 Hz) / 73 dB(A) (60 Hz) Intake (ISO 13347)
Free-Air Sound Power Level 78 dB(A) (50 Hz) / 81 dB(A) (60 Hz) Intake (ISO 13347)
Aerodynamic Measurement Standard ISO 5801 Installation Category A (Air Density ρ = 1.15 kg/m³ ± 2%, Test Setups LU-130850-1 & LU-130856-1)
Airflow Direction Single-Intake Axial Suction, Radial Centrifugal Discharge
Ingress Protection (IP) IP44 (Installation- and position-dependent as per EN 60034-5)
Moisture / Environmental Class H1
Operating Temperature -25 °C to +70 °C (-13 °F to +158 °F) at 50 Hz | -25 °C to +55 °C (-13 °F to +131 °F) at 60 Hz
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) Internally Connected
Electrical Protection Class Class I (With customer connection of protective earth)
Touch Current (IEC 60990) < 0.75 mA (Measuring circuit Fig. 4, TN system)
Insulation Class Class F
Termination Type Silicone Cable with 4x Crimped Splices
Cable Exit Orientation Variable
Lead Wire Gauge & Spec 4G 0.5 mm² Silicone Insulated Cable
Wiring Pinout / Connection U1 = Blue, Z = Brown, U2 = Black, PE = Green/Yellow
Impeller Size Ø 250 mm (9.84 in)
Outer Dimensions (Ø × D) Ø 250 × 123 mm (Ø 9.84 × 4.84 in)
Max. Screw Clearance 10 mm (0.39 in)
Weight 3.8 kg (8.38 lbs)
Blade Count & Geometry 7 Backward-Curved RadiCal Blades
Bearing Type Ball Bearing
Impeller / Blade Material PA (Polyamide) Plastic
Rotor Surface Painted Black
Direction of Rotation Clockwise, Viewed Toward Rotor
Installation Position Shaft Horizontal or Rotor on Bottom (Rotor on Top on Request)
Condensation Drainage Holes On Rotor Side
Compatible Inlet Ring (Optional) 96359-2-4013 (Not included in scope of delivery)
Standards & Compliance EN 60335-1, CCC, EAC (Commissioning not permitted in the European Economic Area)

Applications

ebm-papst R2E250-RB06-01 backward-curved RadiCal centrifugal motorized impellers are engineered for high-pressure plenum and ducted air movement in commercial HVAC air handling units (AHUs), heat recovery ventilation (HRV) systems, and precision data center CRAC/CRAH cooling modules. Their compact unhoused radial-discharge profile integrates directly into cleanroom fan filter units (FFUs), industrial chillers, heat pumps, and pressurized power electronics or variable frequency drive (VFD) enclosures. This model serves as an exact factory-Drop-In OEM replacement for equipment requiring item 11456-5-9980 in demanding MRO and facility ventilation retrofits.