R2E225-RA92-09 ebm-papst 230VAC 225mm AC Centrifugal Fan

$197.87

ebm-papst R2E225-RA92-09 (R2E225RA9209) 230VAC Ø225x99mm RadiCal centrifugal fan, 2500/2600RPM, 765CFM (1300m³/h), 155/210W, with PA6 impeller, TOP & IP44.

SKU: R2E225-RA92-09 Category: Brand:

Description

ebm-papst R2E225-RA92-09 (also known as R2E225RA9209, OEM Item No. 10989-5-9980) is a RadiCal® series single-inlet, unhoused backward-curved AC motorized centrifugal impeller powered by an external-rotor M2E068-DF motor and measuring Ø225 × 99 mm (8.86 × 3.90 in). Operating on single-phase 230 VAC (50/60 Hz) power, it delivers a nominal maximum-load speed of 2500 RPM (50 Hz) / 2600 RPM (60 Hz) at 155 W / 210 W (0.68 A / 0.92 A) and achieves a maximum free-air flow of 703.35 CFM (1195 m³/h) at 50 Hz and 765.15 CFM (1300 m³/h) at 60 Hz.

Built with an aerodynamically optimized 7-blade fiberglass-reinforced PA6 plastic impeller and a black-coated external rotor on precision ball bearings, this unit provides IP44 ingress protection, Class F insulation, and an internally wired thermal overload protector (TOP). Electrical termination is completed via a 450 mm (17.72 in) 4-wire 0.5 mm² silicone connection harness with crimped brass lead tips for permanent split-capacitor (3.5 µF / 450 VDB) operation.

Key Features

  • Dual-Frequency Aerodynamic Output: Delivers up to 703.35 CFM (1195 m³/h) at 50 Hz and 765.15 CFM (1300 m³/h) at 60 Hz.
  • RadiCal® Composite Impeller: Aerodynamic 7-blade backward-curved impeller molded from high-strength fiberglass-reinforced PA6 polyamide for low-noise static pressure.
  • Integrated M2E068-DF AC Motor: External-rotor single-phase 230 VAC motor rated at 155 W / 210 W with precision ball bearings for S1 continuous duty.
  • ErP 2015 Static Efficiency: Achieves 42.5% overall static efficiency (Grade N = 62) with an optimum point of 705 m³/h at 320 Pa.
  • Thermal & Environmental Protection: Features internally wired thermal overload protector (TOP), IP44 enclosure rating, F1-2 humidity class, and rotor-side drain holes.
  • Silicone Harness Termination: Equipped with a 450 mm (17.72 in) 4G 0.5 mm² silicone cable with crimped brass ferrules.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) R2E225-RA92-09
Alternate Part Number R2E225RA9209
OEM Item Number 10989-5-9980 (Revision 77497)
Integrated Motor Model M2E068-DF
Product Series RadiCal® R2E225
Product Category AC Centrifugal Fans
Fan / Component Type Backward-Curved Motorized Impeller (Single Inlet, Unhoused)
Motor Design / Technology AC External-Rotor Permanent Split Capacitor (PSC) Motor
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 / 60 Hz
Speed (Max. Load) 2500 RPM (50 Hz, Nominal) / 2600 RPM (60 Hz, Nominal); 2700 RPM (60 Hz, Curve Pt. 2)
Free-Air Speed (RPM) 2660 RPM (50 Hz) / 2900 RPM (60 Hz)
Optimum Efficiency Speed (RPM) 2560 RPM (50 Hz, Curve Pt. 3 & ErP) / 2700 RPM (60 Hz, Curve Pt. 3)
High-Pressure Speed (Curve Pt. 4) 2615 RPM (50 Hz at 425 Pa) / 2815 RPM (60 Hz at 500 Pa)
Power Rating (Max. Load) 155 W (50 Hz) / 210 W (60 Hz)
Free-Air Power Input 130 W (50 Hz) / 190 W (60 Hz)
Optimum Efficiency Power Input 150 W (50 Hz, Curve Pt. 3) / 207 W (60 Hz, Curve Pt. 3) / 140 W (0.14 kW, ErP Directive)
High-Pressure Power Input (Curve Pt. 4) 139 W (50 Hz at 425 Pa) / 196 W (60 Hz at 500 Pa)
Rated Current (Max. Load) 0.68 A (50 Hz) / 0.92 A (60 Hz)
Free-Air Current Draw 0.57 A (50 Hz) / 0.83 A (60 Hz)
Optimum Efficiency Current Draw 0.65 A (50 Hz, Curve Pt. 3) / 0.90 A (60 Hz, Curve Pt. 3)
High-Pressure Current Draw (Curve Pt. 4) 0.61 A (50 Hz at 425 Pa) / 0.85 A (60 Hz at 500 Pa)
Inrush / Starting Current 1.25 A (50 Hz) / 1.20 A (60 Hz)
Run Capacitor 3.5 µF, 450 VDB
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 703.35 CFM (1195 m³/h, 50 Hz) / 765.15 CFM (1300 m³/h, 60 Hz) at 0 Pa
Operating Duty Point Airflow (Max. Load, Curve Pt. 2) 567.98 CFM (965 m³/h) at 0.804 in H₂O (200 Pa, 50 Hz) / 594.47 CFM (1010 m³/h) at 0.804 in H₂O (200 Pa, 60 Hz)
Operating Duty Point Airflow (Optimum Efficiency, Curve Pt. 3) 432.61 CFM (735 m³/h) at 1.306 in H₂O (325 Pa, 50 Hz) / 459.09 CFM (780 m³/h) at 1.406 in H₂O (350 Pa, 60 Hz)
Operating Duty Point Airflow (High Pressure, Curve Pt. 4) 279.58 CFM (475 m³/h) at 1.707 in H₂O (425 Pa, 50 Hz) / 270.75 CFM (460 m³/h) at 2.009 in H₂O (500 Pa, 60 Hz)
ErP Optimum Efficiency Duty Point 414.95 CFM (705 m³/h) at 1.286 in H₂O (320 Pa)
Max. Tested Curve Static Pressure (Pt. 4) 1.707 in H₂O (425 Pa, 50 Hz) / 2.009 in H₂O (500 Pa, 60 Hz)
Max. Static Pressure (Chart Curve Shut-Off) 2.17 in H₂O (540 Pa, 50 Hz) / 2.85 in H₂O (710 Pa, 60 Hz)
Min. Back Pressure 0 Pa (0 in H₂O)
Sound Pressure Level (Max. Load, Curve Pt. 2) 63 dB(A) (50 Hz) / 64 dB(A) (60 Hz) (Inlet side at 1 m)
Free-Air Sound Pressure Level (Curve Pt. 1) 66 dB(A) (50 Hz) / 69 dB(A) (60 Hz) (Inlet side at 1 m)
Optimum Efficiency Sound Pressure Level (Curve Pt. 3) 58 dB(A) (50 Hz) / 60 dB(A) (60 Hz) (Inlet side at 1 m)
High-Pressure Sound Pressure Level (Curve Pt. 4) 63 dB(A) (50 Hz) / 66 dB(A) (60 Hz) (Inlet side at 1 m)
Sound Power Level (Max. Load, Curve Pt. 2) 70 dB(A) (50 Hz) / 72 dB(A) (60 Hz) (Inlet side per ISO 13347)
Free-Air Sound Power Level (Curve Pt. 1) 73 dB(A) (50 Hz) / 76 dB(A) (60 Hz) (Inlet side per ISO 13347)
Optimum Efficiency Sound Power Level (Curve Pt. 3) 66 dB(A) (50 Hz) / 68 dB(A) (60 Hz) (Inlet side per ISO 13347)
High-Pressure Sound Power Level (Curve Pt. 4) 70 dB(A) (50 Hz) / 73 dB(A) (60 Hz) (Inlet side per ISO 13347)
ErP Efficiency & Grade (EU 327/2011) Overall Static Efficiency ηes = 42.5% (2015 Req: 42.5%), Efficiency Grade N = 62, Installation Category A, Specific Ratio 1.00
Airflow Direction Axial Intake, Radial Centrifugal Discharge
Ingress Protection (IP) IP44 (Depending on installation and position as per EN 60034-5)
Moisture / Environmental Class F1-2
Operating Temperature (50 Hz) -25 °C to +70 °C (-13 °F to +158 °F)
Operating Temperature (60 Hz) -25 °C to +65 °C (-13 °F to +149 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) Wired Internally
Electrical Protection Class Class I (with customer protective earth connection)
Touch Current (IEC 60990) < 0.75 mA (Measuring network Fig. 4, TN system)
Insulation Class Class F
Termination Type 4 Wire Leads with Crimped Brass Lead Tips (Splice Terminals)
Cable Exit Orientation Variable
Lead Wire Gauge & Spec Silicone Cable 4G 0.5 mm² (20 AWG Approx.)
Cable / Lead Length 450 ± 20 mm (17.72 ± 0.79 in)
Wire Stripped / Ferrule Lead Length 85 ± 10 mm (3.35 ± 0.39 in)
Wiring Pinout / Connection U1 = Blue (Line), Z = Brown (Capacitor), U2 = Black (Neutral/Common), PE = Green/Yellow (Protective Earth)
Impeller Size Ø225 mm (8.86 in)
Outer Dimensions (Ø × D) Ø225 × 99 ± 1 mm (8.86 × 3.90 ± 0.04 in)
Impeller Blade Axial Width 88.4 mm (3.48 in)
Inlet Ring Depth 44.5 mm (1.75 in)
Inlet Nozzle / Intake Ring Diameter Ø153.5 mm (6.04 in) Inner / Ø169 mm (6.65 in) Outer
Shaft / Hub Diameter Ø92 mm (3.62 in) External Rotor Hub
Mounting Hole Pitch Ø58 ± 0.2 mm (2.28 ± 0.01 in) Bolt Circle (4 × 90°)
Mounting Hole Diameter / Thread Size 4 × M4 Threaded Holes
Max. Screw Clearance 5 mm (0.20 in) Max. Screw Depth
Weight 1.6 kg (3.53 lbs)
Blade Count & Geometry 7 Backward-Curved Aerodynamic Blades
Bearing Type Ball Bearing
Impeller / Blade Material Fiberglass-Reinforced PA6 Plastic
Rotor Surface Coated in Black
Direction of Rotation Clockwise, Seen on Rotor
Installation Position Shaft Horizontal or Rotor on Bottom (Rotor on Top on Request)
Condensation Drainage Holes Rotor-Side
Compatible Inlet Ring (Optional) 96358-2-4013 (Not Included in Standard Delivery)
Standards & Compliance EN 60335-1, ISO 5801 (Category A), ISO 13347, CE, CCC, EAC
RoHS / Environmental Compliance RoHS3 Compliant

Applications

ebm-papst R2E225-RA92-09 backward-curved motorized centrifugal impellers are engineered for pressurized plenum and ducted ventilation systems where compact radial discharge and static pressure efficiency are required without a scroll housing. Typical industrial and commercial deployments include data center computer room air handlers (CRAH), cleanroom fan filter units (FFUs), commercial heat recovery ventilation (HRV) units, and rooftop air handling modules. This impeller is also widely specified for MRO replacement and OEM thermal management inside high-density power electronics enclosures, variable frequency drive (VFD) cabinets, medical imaging chillers, and industrial process drying machinery.