Description
ebm-papst R2D225-RA26-11 (also known as R2D225RA2611) is a RadiCal series 3-phase, backward-curved, single-intake AC centrifugal motorized impeller measuring Ø225 × 99 mm (Ø8.86 × 3.90 in) and driven by an integrated M2D068-DF external-rotor motor. Operating on 400 VAC (50/60 Hz) or 480 VAC (60 Hz) Y-wired supply, it delivers up to 685 CFM (1,160 m³/h) at 50 Hz and 795 CFM (1,350 m³/h) at 60 Hz with power ratings from 150 W to 235 W. The assembly combines a 7-blade PA plastic impeller, ball bearings, internal thermal overload protection (TOP), IP44 environmental sealing, and a dedicated 5 V Hall IC speed-sensing harness alongside lateral PFA power leads.
Key Features
- High-Efficiency RadiCal Aerodynamics: Backward-curved 7-blade PA plastic impeller exceeds ErP 2015 efficiency requirements at 43.6% static efficiency.
- Wide 3-Phase Voltage Compatibility: Supports 400 VAC (50/60 Hz) and 480 VAC (60 Hz) Y-connected operation up to 795 CFM.
- Integrated Hall IC Feedback: Equipped with a 3-pole Molex sensor harness providing 5 VDC Hall-effect rotational speed monitoring.
- Rugged External-Rotor Drive: M2D068-DF motor features maintenance-free ball bearings, Class F insulation, and S1 continuous-duty rating.
- Comprehensive Thermal & Ingress Protection: Internal thermal overload protector (TOP), IP44 enclosure rating, and rotor-side condensation drainage holes.
- Reversible Rotation & Multi-Agency Approvals: Phase-reversal rotation control certified to CE, UL 1004-3, UL 2111, CSA C22.2 No. 77, and CCC.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R2D225-RA26-11 |
| Alternate Part Number | R2D225RA2611 |
| OEM Item Number | 13367-5-9980 |
| Integrated Motor Model | M2D068-DF (Motor Size 68) |
| Product Series | RadiCal |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | Backward-Curved, Single-Intake Centrifugal Motorized Impeller (Unhoused) |
| Motor Design / Technology | 3-Phase AC External-Rotor Asynchronous Motor |
| Phase & Supply Type | 3-Phase AC (3~), Star / Wye (Y) Wiring |
| Rated Voltage | 400 VAC (50 Hz) / 400 VAC (60 Hz) / 480 VAC (60 Hz) |
| Frequency | 50 / 60 Hz |
| Speed (Max. Load) | 2530 RPM (400 VAC, 50 Hz) / 2700 RPM (400 VAC, 60 Hz) / 2900 RPM (480 VAC, 60 Hz) |
| Free-Air Speed (RPM) | 2645 RPM (400 VAC, 50 Hz) / 2880 RPM (400 VAC, 60 Hz) / 3065 RPM (480 VAC, 60 Hz) |
| ErP Optimum Speed (RPM) | 2555 RPM (400 VAC, 50 Hz) |
| Power Rating (Max. Load) | 150 W (400 VAC, 50 Hz) / 200 W (400 VAC, 60 Hz) / 235 W (480 VAC, 60 Hz) |
| Free-Air Power Input | 122 W (400 VAC, 50 Hz) / 171 W (400 VAC, 60 Hz) / 192 W (480 VAC, 60 Hz) |
| ErP Optimum Efficiency Power | 140 W (0.14 kW at 400 VAC, 50 Hz) |
| Rated Current (Max. Load) | 0.27 A (400 VAC, 50 Hz) / 0.33 A (400 VAC, 60 Hz) / 0.33 A (480 VAC, 60 Hz) |
| Free-Air Current Draw | 0.24 A (400 VAC, 50 Hz) / 0.28 A (400 VAC, 60 Hz) / 0.28 A (480 VAC, 60 Hz) |
| Inrush / Starting Current | 0.74 A (400 VAC, 50 Hz) / 0.72 A (400 VAC, 60 Hz) / 0.83 A (480 VAC, 60 Hz) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 685 CFM (1,160 m³/h) at 400 VAC 50 Hz / 745 CFM (1,270 m³/h) at 400 VAC 60 Hz / 795 CFM (1,350 m³/h) at 480 VAC 60 Hz |
| Operating Duty Point Airflow (50 Hz) | 575 CFM (975 m³/h) at 0.60 in H₂O (150 Pa); 440 CFM (745 m³/h) at 1.20 in H₂O (300 Pa); 260 CFM (445 m³/h) at 1.61 in H₂O (400 Pa) |
| Operating Duty Point Airflow (400 VAC, 60 Hz) | 610 CFM (1,040 m³/h) at 0.69 in H₂O (171 Pa); 460 CFM (785 m³/h) at 1.38 in H₂O (343 Pa); 265 CFM (450 m³/h) at 1.91 in H₂O (476 Pa) |
| Operating Duty Point Airflow (480 VAC, 60 Hz) | 660 CFM (1,120 m³/h) at 0.80 in H₂O (200 Pa); 500 CFM (845 m³/h) at 1.61 in H₂O (400 Pa); 285 CFM (480 m³/h) at 2.21 in H₂O (550 Pa) |
| ErP Optimum Efficiency Duty Point | 414.95 CFM (705 m³/h) at 1.278 in H₂O (318 Pa) |
| Max. Static Pressure (Chart Curve) | 1.89 in H₂O (470 Pa) at 50 Hz / 2.53 in H₂O (630 Pa) at 480 VAC 60 Hz |
| Min. Back Pressure | 0 in H₂O (0 Pa) |
| Sound Pressure Level (Max. Load, Intake) | 57 dB(A) at 400 VAC 50 Hz / 61 dB(A) at 480 VAC 60 Hz (measured at 1 m distance) |
| Free-Air Sound Pressure Level (Intake) | 66 dB(A) at 400 VAC 50 Hz / 70 dB(A) at 480 VAC 60 Hz (measured at 1 m distance) |
| Sound Power Level (Max. Load, Intake) | 65 dB(A) at 400 VAC 50 Hz / 69 dB(A) at 480 VAC 60 Hz (ISO 13347) |
| Free-Air Sound Power Level (Intake) | 74 dB(A) at 400 VAC 50 Hz / 78 dB(A) at 480 VAC 60 Hz (ISO 13347) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes: 43.6% (Req. 42.5%), Efficiency Grade N: 63.1 (Req. 62), Measurement Category A (Static), Specific Ratio 1.00, VSD: No |
| Airflow Direction | Axial intake, radial discharge |
| Ingress Protection (IP) | IP44 (installation- and position-dependent per EN 60034-5) |
| Moisture / Environmental Class | F2-1; H1+ |
| Operating Temperature (400 VAC, 50 Hz) | -25 °C to +80 °C (-13 °F to +176 °F) |
| Operating Temperature (400 / 480 VAC, 60 Hz) | -25 °C to +55 °C (-13 °F to +131 °F) |
| Storage / Transport Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Internal Thermal Overload Protector (TOP) |
| Electrical Protection Class | Class I (with customer protective earth connection) |
| Touch Current (IEC 60990) | < 0.75 mA (measuring circuit Fig. 4, TN system) |
| Insulation Class | Class F |
| Control / Signal Features | Integrated 5 VDC Hall IC speed sensor output (1 pulse/rev); reversible rotation via phase reversal |
| Termination Type | 4-wire crimped splices (power) + 3-pole Molex 70107-0037 connector housing with Molex 16-02-0078 pins (Hall IC) |
| Cable Exit Orientation | Lateral |
| Lead Wire Gauge & Spec | Power: PFA AWG20 (3-phase) + AWG18 (PE); Sensor: Raychem Spec. 44 AWG24 (3-conductor) |
| Power Wiring Pinout (Cable 1) | L1: Black, L2: Blue, L3: Brown, PE: Green/Yellow |
| Sensor Wiring Pinout (Cable 2 – Hall IC) | Pin 4.1 (+5 V): Red, Pin 4.2 (Out): White, Pin 4.3 (0 V): Black |
| Impeller Size | Ø225 mm (Ø8.86 in) |
| Outer Dimensions (Ø × D) | Ø225 × 99 mm (Ø8.86 × 3.90 in) |
| Total Axial Depth | 99 ± 1 mm (3.90 ± 0.04 in) |
| Impeller / Shroud Axial Height | 88.4 ± 1.5 mm (3.48 ± 0.06 in) |
| Mounting Hole Pitch | Ø58 mm (Ø2.28 in) bolt circle diameter (4-hole pattern) |
| Mounting Hole Thread Size | 4 × M4 tapped holes |
| Max. Screw Clearance | 5 mm (0.20 in) max screw insertion depth |
| Weight | 2.2 kg (4.85 lbs) |
| Blade Count & Geometry | 7 backward-curved blades |
| Bearing Type | Ball bearings |
| Impeller / Blade Material | PA (Polyamide) plastic |
| Rotor Surface | Painted black |
| Direction of Rotation | Clockwise, viewed toward rotor (reversible by swapping any two supply phases) |
| Installation Position | Shaft horizontal or rotor on bottom (rotor on top available on request) |
| Condensation Drainage Holes | On rotor side |
| Compatible Inlet Ring (Optional) | ebm-papst 96358-2-4013 (sold separately) |
| Standards & Compliance | CE, EN 60034-1, EN 60204-1, UL 1004-3, UL 2111, CSA C22.2 No. 77, CCC, ErP 2015 (EU 327/2011) |
Applications
ebm-papst R2D225-RA26-11 is engineered for high-static-pressure air movement in precision industrial and commercial thermal management systems. Typical OEM and MRO installations include data center CRAC and CRAH cooling modules, cleanroom fan filter units (FFUs), and building heat recovery ventilation (HRV) plenums. It is also widely integrated into telecom rectifier racks, variable frequency drive (VFD) cabinets, and industrial process drying or filtration enclosures requiring compact, unhoused backward-curved airflow with speed feedback.