Description
ebm-papst K2E250-AA01-09 (also known as K2E250AA0109) is a 250 mm (9.84 in) single-phase AC backward-curved centrifugal fan with a PA plastic housing (without flange), driven by an integrated M2E068-EC external-rotor motor. Operating on 230 VAC at 50/60 Hz, it delivers 2450 RPM (50 Hz) / 2500 RPM (60 Hz), 195 W / 265 W input power, 0.86 A / 1.16 A current draw, and 694.5 CFM (1180 m³/h) airflow at 50 Hz with a 5 µF / 400 VDB motor capacitor.
Built with an 11-blade galvanized sheet steel impeller, black-coated rotor, and ball bearings, it features an internally wired thermal overload protector (TOP), Class B insulation, and a 3-conductor PFA AWG20 lead terminated with a Molex 03-06-2032 connector.
Key Features
- Dual-Frequency 230 VAC Operation: Runs at 2450 RPM (195 W, 0.86 A) on 50 Hz and 2500 RPM (265 W, 1.16 A) on 60 Hz.
- High-Static Backward-Curved Impeller: 11-blade galvanized sheet steel wheel inside a PA plastic housing delivers 694.5 CFM (1180 m³/h) at 50 Hz.
- Integrated M2E068-EC Motor & Capacitor: External-rotor single-phase motor paired with a 5 µF, 400 VDB P2 (CE) run capacitor for S1 continuous duty.
- Internal Thermal Overload Protection: Features internally wired TOP protection, Class B insulation, and ball bearings rated from -25 °C to 55 °C.
- Pre-Terminated Molex Harness: Variable-exit PFA 3x AWG20 cable equipped with a 3-pin Molex 03-06-2032 housing for rapid OEM installation.
- Global Safety & Regulatory Compliance: Certified to UL 2111, CSA C22.2 Nr. 77, CCC, and EN 60335-1 with touch current under 0.75 mA.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | K2E250-AA01-09 |
| Alternate Part Number | K2E250AA0109 |
| OEM Item Number | 12376-5-9980 (Rev. 79567) |
| Integrated Motor Model | M2E068-EC |
| Product Series | K2E250 |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | AC Centrifugal Fan, Backward Curved, With Housing (Without Flange) |
| Motor Design / Technology | Single-Phase External Rotor AC Capacitor Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Speed (RPM) | 2450 RPM (50 Hz) / 2500 RPM (60 Hz) |
| Power Rating | 195 W (50 Hz) / 265 W (60 Hz) |
| Rated Current | 0.86 A (50 Hz) / 1.16 A (60 Hz) |
| Run Capacitor | 5 µF, 400 VDB (P2 / CE Standard) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Data Definition Type | cu (Customer Unit) |
| Airflow (Max. Free Air, 50 Hz) | 694.5 CFM (1180 m³/h) |
| Max. Static Pressure (Chart Curve) | 2.57 in H₂O (640 Pa) [Chart Scale Max: 2.81 in H₂O / 700 Pa] |
| Air Performance Measurement Standard | ISO 5801, Installation Category A (Measurement LU-60910, ρ = 1.2 kg/m³) |
| Acoustic Measurement Standard | LwA per ISO 13347 / LpA at 1 m distance to fan axis (suction side) |
| Ingress Protection (IP) | IP00 |
| Moisture / Environmental Class | F1-2 |
| Operating Temperature | -25 °C to 55 °C (-13 °F to 131 °F) |
| Storage / Transport Temperature | -40 °C to 80 °C (-40 °F to 176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP), wired internally |
| Electrical Protection Class | Class I (when protective earth is connected by customer) |
| Touch Current (IEC 60990) | < 0.75 mA (Measuring network Fig. 4, TN system) |
| Insulation Class | Class B |
| Termination Type | Lead wires with 3-pin Molex connector (Housing 03-06-2032, Pins 02-06-2101) |
| Cable Exit Orientation | Variable |
| Lead Wire Gauge & Spec | 3 × AWG20, PFA insulated |
| Wiring Pinout / Connection | Pin 1.1 / Z: Brown | Pin 1.2 / U2: Black | Pin 1.3 / U1: Blue |
| Impeller Size | 250 mm (9.84 in) |
| Weight | 5.4 kg (11.91 lbs) |
| Blade Count & Geometry | 11 backward-curved blades |
| Bearing Type | Ball bearing |
| Housing / Scroll / Frame Material | PA plastic (without flange) |
| Impeller / Blade Material | Galvanized sheet steel |
| Rotor Surface | Coated in black |
| Direction of Rotation | Clockwise, seen on rotor |
| Installation Position | Any |
| Condensation Drainage Holes | None |
| Standards & Compliance | EN 60335-1, UL 2111, CSA C22.2 Nr. 77, CCC |
Applications
ebm-papst K2E250-AA01-09 is a housed backward-curved AC centrifugal fan built for compact air-handling assemblies and high-resistance ductwork. It is widely deployed in commercial ventilation units, heat recovery ventilation (HRV) plenums, precision electronics enclosures, and cleanroom air filtration modules. OEMs and MRO technicians also rely on this unit for industrial drying equipment, telecom shelter cooling cabinets, and medical or laboratory exhaust systems requiring steady airflow against elevated static pressure.