Description
ebm-papst D2E146-HR93-01 (also known as D2E146HR9301) is a 4-speed, dual-inlet forward-curved AC centrifugal blower fan built around the integrated M2E068-CF single-phase motor and housed in a durable polypropylene (PP) scroll assembly measuring 218 × 253 × 199 mm (8.58 × 9.96 × 7.83 in) with a 146 mm (5.75 in) impeller.
Engineered for 230 VAC 50/60 Hz operation, it delivers up to 373.7 CFM (635 m³/h) at 1,100 RPM and 150 W (0.66 A) under 50 Hz free-air conditions, and 200.1 CFM (340 m³/h) at 220 Pa (0.884 in H₂O) back pressure, 1,750 RPM nominal, and 165 W (0.73 A) at 60 Hz max load. The blower incorporates anti-vibration motor mounting on both sides, Calotte bearings, an integrated 4 µF 400 VDB capacitor, internal thermal overload protection (TOP), and a 6-pin AMP Universal Mate-N-Lok coded plug system rated to IP20.
Key Features
- Dual-Inlet Forward-Curved Scroll Design: 146 mm polypropylene impeller and scroll housing generate up to 373.7 CFM (635 m³/h) and 1.45 in H₂O (360 Pa).
- Four-Speed Tapped Motor Control: Integrated M2E068-CF motor supports four discrete speed stages selectable via break-before-make external switching.
- Integrated Capacitor & Terminal Architecture: Includes a pre-wired 4 µF, 400 VDB P2 (CE) run capacitor inside the terminal box with variable cable exit.
- Coded AMP Mate-N-Lok Harness: Terminated with a 6-pin AMP Universal Mate-N-Lok connector shell (926 682-3) for rapid, error-proof plug-and-play installation.
- Dual-Sided Anti-Vibration Suspension: Motor is vibration-isolated on both sides with Calotte bearings and partial aluminum rotor casting for smooth S1 continuous duty.
- Internal Thermal & Electrical Safety: Features an internally wired thermal overload protector (TOP), Class F insulation, less than 0.75 mA touch current, and VDE/CCC/CE approvals.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | D2E146-HR93-01 |
| Alternate Part Number | D2E146HR9301 |
| OEM Item Number | 11077-5-9980 (Rev. 77823) |
| Integrated Motor Model | M2E068-CF |
| Product Series | D2E146 |
| Product Category | AC Blower Fans |
| Fan / Component Type | Dual-Inlet Forward-Curved Centrifugal Blower (With Scroll Housing) |
| Motor Design / Technology | Single-Phase AC Permanent Split Capacitor (PSC) External-Rotor Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Nominal Free-Air Speed (50 Hz, Stage 4) | 1,050 RPM (Nominal Data Table) / 1,100 RPM (ISO 5801 Chart Curve) |
| Nominal Max-Load Speed (60 Hz, Stage 4) | 1,750 RPM (at 220 Pa / 0.884 in H₂O Min. Back Pressure) |
| Chart Speed Range Across Speed Stages (50 Hz) | Stage 4: 1,100–2,330 RPM | Stage 3: 805–2,105 RPM | Stage 2: 640–1,785 RPM | Stage 1: 505–1,405 RPM |
| Chart Speed Range Across Speed Stages (60 Hz) | Stage 4: 1,600–2,390 RPM | Stage 3: 1,280–2,225 RPM | Stage 2: 1,005–1,825 RPM | Stage 1: 770–1,370 RPM |
| Nominal Free-Air Power Input (50 Hz, Stage 4) | 150 W |
| Nominal Max-Load Power Input (60 Hz, Stage 4) | 165 W (at 220 Pa / 0.884 in H₂O Min. Back Pressure) |
| Chart Power Input Range by Stage (50 Hz) | Stage 4: 124–150 W | Stage 3: 81–100 W | Stage 2: 71–83 W | Stage 1: 64–70 W |
| Chart Power Input Range by Stage (60 Hz) | Stage 4: 155–160 W | Stage 3: 98–107 W | Stage 2: 79–84 W | Stage 1: 67–69 W |
| Nominal Free-Air Current Draw (50 Hz, Stage 4) | 0.66 A |
| Nominal Max-Load Current Draw (60 Hz, Stage 4) | 0.73 A (at 220 Pa / 0.884 in H₂O Min. Back Pressure) |
| Chart Current Draw Range by Stage (50 Hz) | Stage 4: 0.55–0.66 A | Stage 3: 0.45–0.49 A | Stage 2: 0.40–0.43 A | Stage 1: 0.36–0.38 A |
| Chart Current Draw Range by Stage (60 Hz) | Stage 4: 0.68–0.71 A | Stage 3: 0.55–0.56 A | Stage 2: 0.48 A | Stage 1: 0.42 A |
| Run Capacitor | 4 µF, 400 VDB, Standard P2 (CE) |
| Capacitor Wiring / Operation Mode | Integrated Capacitor Connected via Terminal Box |
| Operating Mode / Duty Cycle | S1 (Continuous Operation) |
| Airflow (Max. Free Air, 50 Hz Stage 4) | 373.7 CFM (635 m³/h) at 0 in H₂O (0 Pa) |
| Free-Air Airflow by Speed Stage (50 Hz) | Stage 4: 373.7 CFM (635 m³/h) | Stage 3: 267.8 CFM (455 m³/h) | Stage 2: 206.0 CFM (350 m³/h) | Stage 1: 156.0 CFM (265 m³/h) |
| Operating Duty Point Airflow (50 Hz Stage 4) | 294.3 CFM (500 m³/h) at 0.562 in H₂O (140 Pa); 211.9 CFM (360 m³/h) at 1.044 in H₂O (260 Pa); 132.4 CFM (225 m³/h) at 1.366 in H₂O (340 Pa) |
| Operating Duty Point Airflow (60 Hz Stage 4) | 247.2 CFM (420 m³/h) at 0.602 in H₂O (150 Pa); 200.1 CFM (340 m³/h) at 0.884 in H₂O (220 Pa); 158.9 CFM (270 m³/h) at 1.124 in H₂O (280 Pa); 100.1 CFM (170 m³/h) at 1.447 in H₂O (360 Pa) |
| Max. Static Pressure (Chart Curve) | 1.366 in H₂O (340 Pa) at 50 Hz / 1.447 in H₂O (360 Pa) at 60 Hz (Stage 4 Upper Curve Limit; Chart Axis Max: 1.688 in H₂O / 420 Pa) |
| Min. Back Pressure | 0 in H₂O (0 Pa) at 50 Hz / 0.884 in H₂O (220 Pa) at 60 Hz |
| Air Performance Measurement Standard | ISO 5801, Installation Category A (Air Density ρ = 1.2 kg/m³) |
| Airflow Direction | Dual Axial Intake to Radial Tangential Scroll Discharge |
| Ingress Protection (IP) | IP20 |
| Moisture / Environmental Class | F0 |
| Operating Temperature | -20 °C to +50 °C (-4 °F to +122 °F) |
| Storage / Transport Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) Wired Internally |
| Electrical Protection Class | Class I (When Protective Earth Is Connected by Customer) |
| Touch Current (IEC 60990) | Less than 0.75 mA (Measuring Network Fig. 4, TN System) |
| Insulation Class | Class F |
| Control / Signal Features | 4 Discrete AC Speed Stages (External Switch Must Break Circuit When Changing Speeds) |
| Termination Type | Lead Wires with Coded Plug & Terminal Box (AMP Universal Mate-N-Lok Shell 926 682-3 with 6x Pins 926 886-1) |
| Cable Exit Orientation | Variable |
| Wiring Pinout / Connection | Pin 1.1: L = Stage 1 (Min.) | Pin 1.2: L = Stage 2 | Pin 1.3: L = Stage 3 | Pin 1.4: L = Stage 4 (Max.) | Pin 1.5: N (Neutral) | Pin 1.6: PE (Protective Earth) |
| Impeller Size | Ø 146 mm (5.75 in) |
| Outer Dimensions (L × H × D) | 218 × 253 × 199 mm (8.58 × 9.96 × 7.83 in) |
| Scroll Housing Width (Axial) | 199 mm (7.83 in) |
| Scroll Profile Sub-Dimensions (Drawing) | 220 mm (8.66 in) / 178 mm (7.01 in) / 173 mm (6.81 in) / 155 mm (6.10 in) / 112 mm (4.41 in) / 110 mm (4.33 in) |
| Mounting Fastener Specification | 4 × Sheet Metal Nuts for Thread EN ISO 1478-ST4.8 (Min. Screw Length 14.5 mm / 0.57 in Plus Mounting Material Thickness) |
| Weight | 2.5 kg (5.51 lbs) |
| Bearing Type | Calotte Bearing (Self-Aligning Sleeve Bearing) |
| Motor Suspension | Anti-Vibration Mounted on Both Sides |
| Housing / Scroll / Frame Material | Polypropylene (PP) Plastic |
| Impeller / Blade Material | Polypropylene (PP) Plastic |
| Rotor Surface | Partially Cast in Aluminum |
| Direction of Rotation | Counter-Clockwise (CCW), Seen on Rotor |
| Installation Position | Shaft Horizontal |
| Condensation Drainage Holes | None |
| Standards & Compliance | CE, EN 60335-2-31, VDE, CCC, GOST |
Applications
ebm-papst D2E146-HR93-01 is engineered for ducted air delivery and multi-stage airflow modulation in commercial HVAC air handling units (AHUs), fan coil units, and variable air volume (VAV) terminal boxes. Its dual-inlet forward-curved scroll geometry and vibration-isolated motor suspension make it well suited for commercial kitchen exhaust hoods, residential and light-commercial heat recovery ventilation (HRV) systems, and doorway air curtains. Industrial OEMs also integrate this blower into drying and curing chambers, laboratory fume extraction cabinets, and enclosed process cooling plenums requiring selectable multi-speed static pressure control.