Description
ebm-papst D2E133-CI33-56 (also known as D2E133CI3356) is a heavy-duty dual-intake, forward-curved AC centrifugal scroll blower powered by an external-rotor M2E068-CF motor with a 133 mm (5.24 in) impeller inside an unflanged 203 × 213 × 168 mm (7.99 × 8.39 × 6.61 in) scroll housing.
Engineered for single-phase 230 VAC (50/60 Hz) continuous S1 operation with a 4 µF / 400 VDB run capacitor, it delivers 1700 RPM, 175 W (0.77 A), and 420 CFM (715 m³/h) at 50 Pa (0.20 in H₂O) minimum back pressure at 50 Hz, scaling to 2100 RPM, 190 W (0.84 A), and 300 CFM (515 m³/h) at 200 Pa (0.80 in H₂O) at 60 Hz. Built with a hot-dip galvanized sheet-steel impeller and scroll housing, a partly cast aluminum rotor surface, and precision ball bearings, this blower withstands demanding ducted static pressures up to 300 Pa (1.20 in H₂O) at 50 Hz and 400 Pa (1.61 in H₂O) at 60 Hz. It integrates an internally connected thermal overload protector (TOP), IP44 environmental sealing, Class B insulation, and an axial PVC 4G 0.5 mm² cable terminated with four crimped splices.
Key Features
- Dual-Intake Scroll Aerodynamics: Delivers 420 CFM (715 m³/h) at 50 Hz and high-pressure 60 Hz duty up to 400 Pa (1.61 in H₂O).
- Galvanized Steel Construction: Hot-dip galvanized sheet-steel scroll housing and forward-curved impeller resist corrosion in industrial air streams.
- Integrated M2E068-CF Motor: External-rotor AC capacitor motor paired with precision ball bearings supports continuous S1 duty in any orientation.
- Built-In Thermal Protection: Internally connected thermal overload protector (TOP) and Class B insulation safeguard windings against overheating and overload.
- IP44 & Class I Safety: IP44 splash-resistant enclosure with <0.75 mA touch current and CE, CCC, and EAC global certifications.
- Pre-Terminated Axial Harness: Factory-wired PVC 4G 0.5 mm² axial power cable features 4x crimped splices for rapid OEM cabinet integration.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | D2E133-CI33-56 |
| Alternate Part Number | D2E133CI3356 |
| OEM Item Number | 11076-5-9980 (Change 90251) |
| Integrated Motor Model | M2E068-CF |
| Product Series | D2E133 |
| Product Category | AC Blower Fans |
| Fan / Component Type | Dual-Intake Forward-Curved Centrifugal Blower with Scroll Housing (Without Flange) |
| Motor Design / Technology | AC External-Rotor Capacitor-Run Asynchronous Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Speed (Max. Load) | 1700 RPM (50 Hz, Pt 1 at 50 Pa) / 2100 RPM (60 Hz, Pt 1 at 200 Pa) |
| Speed (Curve Point 2) | 1900 RPM (50 Hz at 135 Pa) / 2330 RPM (60 Hz at 265 Pa) |
| Speed (Curve Point 3) | 2150 RPM (50 Hz at 220 Pa) / 2535 RPM (60 Hz at 335 Pa) |
| Speed (Curve Point 4 / High Pressure) | 2415 RPM (50 Hz at 300 Pa) / 2805 RPM (60 Hz at 400 Pa) |
| Power Rating (Max. Load) | 175 W (50 Hz, Pt 1 at 50 Pa) / 190 W (60 Hz, Pt 1 at 200 Pa) |
| Power Input (Curve Point 2) | 159 W (50 Hz at 135 Pa) / 176 W (60 Hz at 265 Pa) |
| Power Input (Curve Point 3) | 146 W (50 Hz at 220 Pa) / 171 W (60 Hz at 335 Pa) |
| Power Input (Curve Point 4 / High Pressure) | 129 W (50 Hz at 300 Pa) / 161 W (60 Hz at 400 Pa) |
| Rated Current (Max. Load) | 0.77 A (50 Hz, Pt 1 at 50 Pa) / 0.84 A (60 Hz, Pt 1 at 200 Pa) |
| Current Draw (Curve Point 2) | 0.69 A (50 Hz at 135 Pa) / 0.77 A (60 Hz at 265 Pa) |
| Current Draw (Curve Point 3) | 0.64 A (50 Hz at 220 Pa) / 0.75 A (60 Hz at 335 Pa) |
| Current Draw (Curve Point 4 / High Pressure) | 0.56 A (50 Hz at 300 Pa) / 0.71 A (60 Hz at 400 Pa) |
| Inrush / Starting Current | 0.84 A (50 Hz) / 0.88 A (60 Hz) |
| Run Capacitor | 4.0 µF, 400 VDB |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Nominal Airflow (at Min. Back Pressure / Pt 1) | 420 CFM (715 m³/h) at 0.20 in H₂O (50 Pa, 50 Hz) / 300 CFM (515 m³/h) at 0.80 in H₂O (200 Pa, 60 Hz) |
| Operating Duty Point Airflow (50 Hz Curve LU-105286-1) | Pt 1: 420 CFM (715 m³/h) at 0.20 in H₂O (50 Pa); Pt 2: 385 CFM (650 m³/h) at 0.54 in H₂O (135 Pa); Pt 3: 325 CFM (550 m³/h) at 0.88 in H₂O (220 Pa); Pt 4: 230 CFM (390 m³/h) at 1.20 in H₂O (300 Pa) |
| Operating Duty Point Airflow (60 Hz Curve LU-105290-1) | Pt 1: 300 CFM (515 m³/h) at 0.80 in H₂O (200 Pa); Pt 2: 250 CFM (430 m³/h) at 1.06 in H₂O (265 Pa); Pt 3: 205 CFM (350 m³/h) at 1.34 in H₂O (335 Pa); Pt 4: 115 CFM (190 m³/h) at 1.61 in H₂O (400 Pa) |
| Max. Tested Curve Static Pressure (Pt 4) | 1.20 in H₂O (300 Pa) at 50 Hz / 1.61 in H₂O (400 Pa) at 60 Hz |
| Min. Required Back Pressure | 0.20 in H₂O (50 Pa) at 50 Hz / 0.80 in H₂O (200 Pa) at 60 Hz |
| Aerodynamic & Acoustic Test Standard | ISO 5801 Installation Category A (Airflow) / ISO 13347 (Acoustics) |
| Ingress Protection (IP) | IP44 (Installation- and position-dependent) |
| Moisture / Environmental Class | H0 (Dry environment) |
| Operating Temperature (50 Hz) | -25 to +35 °C (-13 to +95 °F) |
| Operating Temperature (60 Hz) | -25 to +25 °C (-13 to +77 °F) |
| Storage / Transport Temperature | -40 to +80 °C (-40 to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) internally connected |
| Electrical Protection Class | Class I (with customer connection of protective earth) |
| Touch Current (IEC 60990) | < 0.75 mA (Measuring circuit Fig. 4, TN system) |
| Insulation Class | Class B |
| Termination Type | 4 Wire Leads with 4x Crimped Splices |
| Cable Exit Orientation | Axial |
| Lead Wire Gauge & Spec | PVC 4G 0.5 mm² (4-Conductor Cable) |
| Wiring Pinout / Connection | U1 = Blue, Z = Brown, U2 = Black, PE = Green/Yellow |
| Impeller Size | Ø 133 mm (5.24 in) |
| Dimensions (L × H × D) | 203 × 213 × 168 mm (7.99 × 8.39 × 6.61 in) |
| Weight | 3.3 kg (7.28 lbs) |
| Blade Geometry | Forward-Curved, Dual-Intake Centrifugal Impeller |
| Bearing Type | Ball Bearing |
| Housing / Scroll Material | Sheet Steel, Hot-Dip Galvanized (Without Flange) |
| Impeller / Blade Material | Sheet Steel, Hot-Dip Galvanized |
| Rotor Surface | Partly Cast in Aluminum |
| Direction of Rotation | Counterclockwise, Viewed Toward Rotor |
| Installation Position | Any |
| Condensation Drainage Holes | None |
| Standards & Compliance | EN 60335-1, CE, CCC, EAC |
| RoHS / Environmental Compliance | RoHS3 Compliant |
Applications
ebm-papst D2E133-CI33-56 dual-intake centrifugal scroll blower is engineered for pressurized air movement in ducted commercial HVAC air handling units (AHUs), variable air volume (VAV) terminal boxes, fan coil units, and doorway air curtains. Its compact galvanized steel volute housing and forward-curved Sirocco wheel deliver concentrated airflow against high system resistance in industrial curing and drying ovens, reflow soldering tunnels, and packaging or printing machinery. Furthermore, its continuous-duty ball bearing system and splash-resistant enclosure make it a reliable OEM and MRO replacement blower for laboratory fume hoods, environmental test chambers, and power electronics cabinet ventilation.