Description
ebm-papst A6E630-AN01-01 (also known as A6E630AN0101) is a 630 mm (24.80 in) S-series HyBlade® AC axial fan powered by a single-phase external-rotor M6E110-GF motor. Operating on 230 VAC at 50 Hz, it delivers up to 6,486.1 CFM (11,020 m³/h) of free-air volume flow at 925 RPM (467 W / 2.04 A) and maintains a nominal maximum-load rating of 860 RPM, 600 W, and 2.62 A with a 14 µF / 400 VDB run capacitor integrated via the terminal box. The impeller utilizes five sickled blades constructed from press-fitted sheet steel blanks sprayed with polypropylene (PP) plastic for high aerodynamic efficiency (ErP Static Grade N = 40) and reduced acoustic emissions (60 to 64 dB(A) inlet sound pressure across its operating curve).
Built for continuous S1 duty from -40 °C to +55 °C (-40 °F to +131 °F), this 10 kg (22.05 lbs) fan features ball bearings, IP54 and F4-1 environmental protection, rotor-side condensate discharge holes, and brought-out thermal overload protection (TOP).
Key Features
- High-Volume 50 Hz Aerodynamics: Delivers 6,486.1 CFM (11,020 m³/h) at free air and 3,946.4 CFM (6,705 m³/h) at 100 Pa (0.401 in H₂O) max back pressure.
- HyBlade® Composite Impeller: Five sickled blades with press-fitted sheet steel cores sprayed with PP plastic reduce weight and lower acoustic emissions to 60–64 dB(A).
- ErP Directive Compliant: Achieves 32.2% overall static efficiency (ηes) and Efficiency Grade N = 40 at 6,725 m³/h (3,958.2 CFM) and 98 Pa.
- Integrated Terminal Box & Capacitor: Axial-exit PP plastic terminal box houses the pre-connected 14 µF / 400 VDB motor capacitor and external TOP leads.
- Harsh-Environment IP54 Durability: Rated for -40 °C to +55 °C (-40 °F to +131 °F) operation with F4-1 humidity resistance, black-coated rotor, and rotor-side drainage holes.
- Industrial Safety & Approvals: Class F insulation, Protection Class I grounding, ball bearing system, and VDE, CCC, GOST, and CE compliance.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | A6E630-AN01-01 |
| Alternate Part Number | A6E630AN0101 |
| OEM Item Number | 10124-5-9980 (Revision 78380) |
| Integrated Motor Model | M6E110-GF |
| Product Series | HyBlade® S Series (Sickled Blades) |
| Product Category | AC Axial Fans |
| Fan / Component Type | AC Axial Fan (Unhoused Impeller with Terminal Box) |
| Motor Design / Technology | 6-Pole Single-Phase AC External Rotor Capacitor Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 Hz |
| Speed (Max. Load) | 860 RPM (at 100 Pa / 0.401 in H₂O, Curve Point 4) |
| Free-Air Speed (RPM) | 925 RPM (at 0 Pa, Curve Point 1) |
| Intermediate Curve Speed (RPM) | 905 RPM (at 40 Pa, Point 2); 885 RPM (at 70 Pa, Point 3) |
| ErP Optimum Speed (RPM) | 865 RPM (at 98 Pa / 0.393 in H₂O) |
| Power Rating (Max. Load) | 600 W (at 100 Pa / 0.401 in H₂O, Curve Point 4) |
| Free-Air Power Input | 467 W (at 0 Pa, Curve Point 1) |
| Intermediate Curve Power Input | 521 W (at 40 Pa, Point 2); 559 W (at 70 Pa, Point 3) |
| ErP Optimum Efficiency Power | 590 W (0.59 kW at 98 Pa) |
| Rated Current (Max. Load) | 2.62 A (at 100 Pa / 0.401 in H₂O, Curve Point 4) |
| Free-Air Current Draw | 2.04 A (at 0 Pa, Curve Point 1) |
| Intermediate Curve Current Draw | 2.27 A (at 40 Pa, Point 2); 2.44 A (at 70 Pa, Point 3) |
| Run Capacitor | 14 µF, 400 VDB |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 6,486.1 CFM (11,020 m³/h at 0 Pa, Curve Point 1) |
| Operating Duty Point Airflow (Point 2) | 5,632.7 CFM (9,570 m³/h) at 0.161 in H₂O (40 Pa) |
| Operating Duty Point Airflow (Point 3) | 4,849.9 CFM (8,240 m³/h) at 0.281 in H₂O (70 Pa) |
| Operating Duty Point Airflow (Point 4 Max. Load) | 3,946.4 CFM (6,705 m³/h) at 0.401 in H₂O (100 Pa) |
| ErP Optimum Efficiency Duty Point | 3,958.2 CFM (6,725 m³/h) at 0.393 in H₂O (98 Pa) |
| Max. Static Pressure | 0.401 in H₂O (100 Pa) |
| Sound Pressure Level (Max. Load) | 61 dB(A) (Inlet side at 1 m distance, 100 Pa, Point 4) |
| Free-Air Sound Pressure Level | 64 dB(A) (Inlet side at 1 m distance, 0 Pa, Point 1) |
| Intermediate Curve Sound Pressure Level | 61 dB(A) (at 40 Pa, Point 2); 60 dB(A) (at 70 Pa, Point 3) |
| Sound Power Level (Inlet, Max. Load) | 68 dB(A) (per ISO 13347 at 100 Pa, Point 4) |
| Free-Air Sound Power Level (Inlet) | 70 dB(A) (per ISO 13347 at 0 Pa, Point 1) |
| Intermediate Curve Sound Power Level (Inlet) | 67 dB(A) (at 40 Pa, Point 2); 66 dB(A) (at 70 Pa, Point 3) |
| Sound Power Level (Outlet, Max. Load) | 67 dB(A) (at 100 Pa, Point 4) |
| Free-Air Sound Power Level (Outlet) | 70 dB(A) (at 0 Pa, Point 1) |
| Intermediate Curve Sound Power Level (Outlet) | 67 dB(A) (at 40 Pa, Point 2); 65 dB(A) (at 70 Pa, Point 3) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes = 32.2%, Efficiency Grade N = 40 (Measurement Category A, Static, Specific Ratio 1.00, No VSD) |
| AirPerformance Measurement Standard | ISO 5801 Installation Category A (Measurement LU-105789) |
| Airflow Direction | “V” (Intake over motor / struts) |
| Ingress Protection (IP) | IP54 |
| Moisture / Environmental Class | F4-1 |
| Operating Temperature | -40 °C to +55 °C (-40 °F to +131 °F) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) brought out (external connection required) |
| Electrical Protection Class | Class I (if protective earth is connected by customer) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring network Fig. 4, TN system) |
| Insulation Class | Class F |
| Termination Type | Via Terminal Box (with integrated capacitor connected via terminal box) |
| Cable Exit Orientation | Axial |
| Impeller Size | Ø 630 mm (24.80 in) |
| Weight | 10 kg (22.05 lbs) |
| Blade Count & Geometry | 5 Sickled Blades (HyBlade® S Series) |
| Bearing Type | Ball Bearing |
| Electronics Housing Material | Polypropylene (PP) Plastic (Terminal Box) |
| Impeller / Blade Material | Press-fitted sheet steel blank, sprayed with PP (polypropylene) plastic |
| Rotor Surface | Coated in black |
| Direction of Rotation | Counter-clockwise (seen on rotor) |
| Installation Position | Shaft horizontal or rotor on bottom; rotor on top on request |
| Condensation Drainage Holes | Rotor-side |
| Standards & Compliance | EN 61800-5-1, CE, VDE, CCC, GOST |
Applications
The ebm-papst A6E630-AN01-01 HyBlade® AC axial fan is engineered for high-volume heat rejection across commercial refrigeration condensers, air-cooled liquid chillers, dry coolers, and industrial heat exchangers. Its hybrid steel-and-polypropylene sickle blade geometry and moisture-resistant construction make it well suited for outdoor rooftop HVAC plenums, cold-storage evaporator coils, and agricultural or industrial building ventilation systems. It serves as a direct OEM replacement and MRO spare for thermal management assemblies requiring low-noise axial airflow and reliable all-weather performance.