Description
ebm-papst A6D630-AN01-01 (also known as A6D630AN0101) is a heavy-duty 3-phase AC axial fan from the HyBlade S-series, integrating an M6D110-GF external rotor motor with a 5-blade Ø630 mm (24.80 in) hybrid impeller and a 209.5 mm (8.25 in) axial installation depth. Supporting dual-speed Delta (Δ) and Star (Y) wiring across 400 VAC (50/60 Hz) and 480 VAC (60 Hz) power supplies, this unit delivers up to 6,635 CFM (11,270 m³/h) at 890 RPM / 600 W on 400 VAC 50 Hz Delta and reaches a maximum free-air output of 7,710 CFM (13,105 m³/h) at 1,070 RPM / 810 W on 480 VAC 60 Hz Delta. Engineered for harsh industrial environments, it features press-fitted sheet steel blades overmolded with polypropylene (PP) plastic, a black-painted rotor with rotor-side condensation drainage holes, maintenance-free ball bearings, and an axial PP terminal box. The motor is safeguarded by an integrated Thermal Overload Protector (TOP) with basic insulation, Class F insulation, IP54 ingress protection, and H2 environmental moisture resistance.
Key Features
- Dual-Speed Delta/Star 3-Phase Operation: Configurable in Delta (Δ) or Star (Y) connections across 400 VAC (50/60 Hz) and 480 VAC (60 Hz) networks for two-step airflow and acoustic control.
- HyBlade Hybrid Impeller Architecture: Combines a high-strength press-fitted sheet steel core sprayed with aerodynamic polypropylene (PP) plastic across 5 sickle-shaped blades to reduce tonal noise.
- High-Volume Aerodynamic Performance: Delivers up to 7,710 CFM (13,105 m³/h) free-air flow at 480 VAC 60 Hz (Δ) and overcomes up to 105 Pa (0.42 in H₂O) static back pressure at 400 VAC 50 Hz (Δ).
- IP54 & H2 Environmental Durability: Built with Class F motor insulation, H2 moisture protection, rotor-side condensation drainage holes, and an operating range down to -40 °C (-40 °F).
- Integrated Thermal Overload Protection: Equipped with internal TOP thermal switch leads (2x gray) wired to the axial PP terminal box for external motor circuit breaker interlocking.
- ErP 2015 Compliant Efficiency: Achieves a 32.3% overall static efficiency (Efficiency Grade N = 40) in accordance with European Commission Regulation (EU) 327/2011.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | A6D630-AN01-01 |
| Alternate Part Number | A6D630AN0101 |
| Integrated Motor Model | M6D110-GF (Motor Size 110) |
| Product Series | A6D630 HyBlade (S Series, Sickle-Shaped Blades) |
| Product Category | AC Axial Fans |
| Fan / Component Type | 3-Phase AC Tubeaxial Fan (Unhoused Motor-Impeller Assembly) |
| Phase & Supply Type | 3-Phase AC, Delta (Δ) / Star (Y) Dual-Speed Configurable |
| Rated Voltage | 400 VAC (50/60 Hz) / 480 VAC (60 Hz) |
| Frequency | 50 / 60 Hz |
| Speed (RPM) at 400 VAC (50 Hz) | 890 RPM (Δ Max Load) / 690 RPM (Y Max Load) ; 930 RPM (Δ Free Air) / 790 RPM (Y Free Air) |
| Speed (RPM) at 480 VAC (60 Hz) | 1070 RPM (Δ Max Load) / 820 RPM (Y Max Load) ; 1095 RPM (Δ Free Air) / 895 RPM (Y Free Air) |
| Power Consumption at 400 VAC (50 Hz) | 600 W (Δ Max Load) / 400 W (Y Max Load) ; 439 W (Δ Free Air) / 319 W (Y Free Air) |
| Power Consumption at 480 VAC (60 Hz) | 810 W (Δ Max Load) / 550 W (Y Max Load) ; 684 W (Δ Free Air) / 491 W (Y Free Air) |
| Current Draw at 400 VAC (50 Hz) | 1.20 A (Δ Max Load) / 0.68 A (Y Max Load) ; 1.07 A (Δ Free Air) / 0.56 A (Y Free Air) |
| Current Draw at 480 VAC (60 Hz) | 1.35 A (Δ Max Load) / 0.80 A (Y Max Load) ; 1.18 A (Δ Free Air) / 0.71 A (Y Free Air) |
| Inrush / Starting Current | 4.0 A (400V 50Hz Δ) / 1.33 A (400V 50Hz Y) ; 3.5 A (400V 60Hz Δ) / 1.17 A (400V 60Hz Y) |
| Max. Airflow at 400 VAC (50 Hz, Free Air) | 6635 CFM (11270 m³/h) in Δ / 5665 CFM (9620 m³/h) in Y |
| Max. Airflow at 480 VAC (60 Hz, Free Air) | 7710 CFM (13105 m³/h) in Δ / 6335 CFM (10765 m³/h) in Y |
| ErP Optimum Efficiency Duty Point | 4423 CFM (7515 m³/h) at 92 Pa (0.369 in H₂O), 890 RPM, 600 W (ηes = 32.3%, Grade N = 40) |
| Max. Back Pressure at 400 VAC (50 Hz) | 0.42 in H₂O (105 Pa) in Δ / 0.22 in H₂O (56 Pa) in Y |
| Max. Back Pressure at 480 VAC (60 Hz) | 0.22 in H₂O (55 Pa) in Δ / 0.14 in H₂O (35 Pa) in Y |
| Sound Pressure Level (LpAin at 1 m) | 59 to 64 dB(A) (400V 50Hz Δ) / 53 to 59 dB(A) (400V 50Hz Y) ; 64 to 68 dB(A) (480V 60Hz Δ) / 58 to 63 dB(A) (480V 60Hz Y) |
| Sound Power Level (LwAin / LwAout) | 65 to 70 dB(A) Intake / 64 to 69 dB(A) Outlet (400V 50Hz Δ) ; 70 to 74 dB(A) Intake & Outlet (480V 60Hz Δ) |
| Airflow Direction | “V” (Intake over motor/struts, discharge over impeller) |
| Direction of Rotation | Counterclockwise, viewed toward rotor |
| Impeller Diameter | Ø 630 mm (24.80 in) |
| Installation Depth / Thickness | 209.5 mm (8.25 in) |
| Blade Count & Geometry | 5 Sickle-Shaped HyBlade Impeller Blades |
| Impeller / Blade Material | Press-fitted sheet steel blank, sprayed with PP (Polypropylene) plastic |
| Rotor Surface | Painted black |
| Terminal Box Material | PP (Polypropylene) plastic |
| Rotor Mounting Thread & Clearance | 4x M6 threaded holes (Max. screw clearance 12 mm; tightening torque 1.5 ± 0.2 Nm) |
| Bearing Type | Maintenance-Free Ball Bearings |
| Installation Position | Shaft horizontal or rotor on bottom (rotor on top available on request) |
| Condensation Drainage Holes | On rotor side |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Weight | 9.9 kg (21.83 lbs) |
| Termination Type | Axial Terminal Box with M20 x 1.5 Cable Gland (Cable Ø 6 to 12 mm; torque 2.0 ± 0.3 Nm) |
| Wiring Pinout / Connection | L1 = V1 (Blue), L2 = U1 (Black), L3 = W1 (Brown), W2 (Yellow), U2 (Green), V2 (White), TOP (2x Gray), PE (Green/Yellow) |
| Motor Protection | Thermal Overload Protector (TOP) with basic insulation (external evaluation required) |
| Electrical Protection Class | Class I (with customer connection of protective earth PE) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring circuit Fig. 4, TN system) |
| Insulation Class | Class “F” |
| Ingress Protection (IP) | IP54 (Dust Protected, Splash Water Resistant) |
| Moisture / Environmental Class | H2 |
| Operating Ambient Temperature | -40 to +65 °C (-40 to +149 °F) at 400V 50Hz ; -40 to +60 °C (-40 to +140 °F) at 400V 60Hz ; -40 to +55 °C (-40 to +131 °F) at 480V 60Hz |
| Storage & Transport Temperature | -40 to +80 °C (-40 to +176 °F) |
| Standards & Approvals | EN 61800-5-1, Commission Regulation (EU) 327/2011 (ErP), CE, VDE, CCC, EAC, RoHS3 Compliant |
Applications
ebm-papst A6D630-AN01-01 is engineered for high-volume heat rejection in commercial HVACR condensers, air-cooled liquid chillers, dry coolers, and industrial refrigeration evaporators. Its weather-resistant HyBlade hybrid impeller and low-temperature ball bearing system make it directly suited for outdoor heat exchangers, cold-storage blast freezers, and large walk-in environmental test chambers. Additionally, OEMs and MRO facility engineers deploy this unit in industrial process cooling towers, generator set radiator packages, and heavy-duty transformer cooling banks requiring two-speed Delta/Star airflow modulation.