Description
ebm-papst R2E180-BD52-06 (also known as R2E180BD5206) is an unhoused single-phase AC backward-curved centrifugal motorized impeller powered by an integrated M2E052-CA external-rotor motor with a 180 mm (7.087 in) diameter. Operating on 230 VAC at 50/60 Hz, it achieves a nominal free-air speed of 2300 RPM at 52 W / 0.24 A (50 Hz) and 65 W / 0.30 A (60 Hz), delivering up to 205 CFM (350 m³/h) of free-air airflow and handling static pressures up to 0.80 in H₂O (200 Pa) at 50 Hz or 0.92 in H₂O (230 Pa) at 60 Hz across its measured operating curve.
Built for continuous S1 industrial duty from -25 °C to +70 °C (50 Hz) or +65 °C (60 Hz), this 6-blade impeller combines stainless and galvanized sheet steel construction with precision ball bearings, an unpainted rotor, and an internally connected thermal overload protector (TOP). Electrical termination is simplified via a lateral AWG 20 ETFE cable factory-crimped with three 6.3 × 0.8 mm flat push-on receptacles.
Key Features
- Dual-Frequency Aerodynamic Output: Delivers 205 CFM (350 m³/h) free-air flow and sustains up to 0.92 in H₂O (230 Pa) curve pressure.
- Stainless Steel 6-Blade Impeller: Combines corrosion-resistant stainless and galvanized sheet steel geometry with clockwise rotation for high-pressure plenum installations.
- Integrated M2E052-CA External-Rotor Motor: Features precision ball bearings, Class F insulation, and S1 continuous-duty rating for reliable thermal management.
- Internal TOP Thermal Protection: Equipped with an internally connected thermal overload protector and low touch current (< 0.75 mA per IEC 60990).
- ETFE High-Temp Quick-Connect Harness: Lateral AWG 20 ETFE cable terminated with three 6.3 × 0.8 mm crimped flat push-on receptacles.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R2E180-BD52-06 |
| Alternate Part Number | R2E180BD5206 |
| OEM Item Number | 10842-5-9980 |
| Integrated Motor Model | M2E052-CA (Motor Size 52) |
| Product Series | R2E Series |
| Product Category | AC Centrifugal Fans |
| Fan / Component Type | Unhoused AC Centrifugal Motorized Impeller |
| Motor Design / Technology | Single-Phase AC External-Rotor Capacitor-Run Motor |
| Phase & Supply Type | 1~ (Single-Phase AC) |
| Rated Voltage | 230 VAC |
| Frequency | 50 / 60 Hz |
| Free-Air Speed (RPM) | 2300 RPM (50 Hz, Pt 1) / 2300 RPM (60 Hz, Pt 1) |
| Speed at Curve Duty Point 2 | 2300 RPM (50 Hz at 70 Pa) / 2295 RPM (60 Hz at 70 Pa) |
| Speed at Curve Duty Point 3 | 2320 RPM (50 Hz at 140 Pa) / 2330 RPM (60 Hz at 140 Pa) |
| Speed (Max. Curve Pressure Point 4) | 2445 RPM (50 Hz at 200 Pa) / 2610 RPM (60 Hz at 230 Pa) |
| Free-Air Power Input | 52 W (50 Hz, Pt 1) / 65 W (60 Hz, Pt 1) |
| Power Input at Curve Duty Point 2 | 52 W (50 Hz at 70 Pa) / 65 W (60 Hz at 70 Pa) |
| Power Input at Curve Duty Point 3 | 51 W (50 Hz at 140 Pa) / 64 W (60 Hz at 140 Pa) |
| Power Input (Max. Curve Pressure Point 4) | 48 W (50 Hz at 200 Pa) / 60 W (60 Hz at 230 Pa) |
| Free-Air Current Draw | 0.24 A (50 Hz, Pt 1) / 0.30 A (60 Hz, Pt 1) |
| Current Draw at Curve Duty Point 2 | 0.23 A (50 Hz at 70 Pa) / 0.28 A (60 Hz at 70 Pa) |
| Current Draw at Curve Duty Point 3 | 0.22 A (50 Hz at 140 Pa) / 0.28 A (60 Hz at 140 Pa) |
| Current Draw (Max. Curve Pressure Point 4) | 0.21 A (50 Hz at 200 Pa) / 0.26 A (60 Hz at 230 Pa) |
| Run Capacitor | 1.5 µF, 400 VDB |
| Capacitor Standard / Safety Class | S0 (CE) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 205 CFM (350 m³/h) at 0 Pa (50 / 60 Hz, Curve Point 1) |
| Operating Duty Point 2 Airflow | 170 CFM (290 m³/h) at 0.28 in H₂O (70 Pa) (50 / 60 Hz) |
| Operating Duty Point 3 Airflow | 135 CFM (225 m³/h) at 0.56 in H₂O (140 Pa) (50 Hz) / 135 CFM (230 m³/h) at 0.56 in H₂O (140 Pa) (60 Hz) |
| Operating Duty Point 4 Airflow (Max. Curve Load) | 105 CFM (175 m³/h) at 0.80 in H₂O (200 Pa) (50 Hz) / 100 CFM (170 m³/h) at 0.92 in H₂O (230 Pa) (60 Hz) |
| Max. Measured Static Pressure (Curve Point 4) | 0.80 in H₂O (200 Pa) (50 Hz) / 0.92 in H₂O (230 Pa) (60 Hz) |
| Max. Static Pressure (Shutoff Chart Curve) | 1.00 in H₂O (250 Pa) (50 Hz) / 1.05 in H₂O (260 Pa) (60 Hz) |
| Min. Back Pressure | 0 in H₂O (0 Pa) |
| Aerodynamic Measurement Setup | ISO 5801 Installation Category A (LU-37375-1 at 50 Hz / LU-37376-1 at 60 Hz) |
| Ingress Protection (IP) | IP00 |
| Moisture / Environmental Class | H0 (Dry Environment) |
| Operating Temperature | -25 °C to +70 °C (-13 °F to +158 °F) at 50 Hz / -25 °C to +65 °C (-13 °F to +149 °F) at 60 Hz |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Thermal Overload Protector (TOP) Internally Connected |
| Electrical Protection Class | Class I (With Customer Protective Earth Connection at Marked PE Point) |
| Touch Current (IEC 60990) | < 0.75 mA (Measuring Circuit Fig. 4, TN System) |
| Insulation Class | Class F |
| Termination Type | 3 × Crimped Flat Push-On Receptacles (6.3 × 0.8 mm) |
| Cable Exit Orientation | Lateral Cable Exit |
| Lead Wire Gauge & Spec | ETFE Insulated Cable, AWG 20 |
| Wiring Pinout / Connection | U1 = Blue, Z = Brown, U2 = Black |
| Impeller Size | Ø 180 mm (7.087 in) |
| Motor Frame Size | Size 52 |
| Weight | 1.0 kg (2.205 lbs) |
| Blade Count & Geometry | 6 Backward-Curved Centrifugal Blades |
| Bearing Type | Ball Bearing |
| Impeller / Blade Material | Stainless Sheet Steel & Galvanized Sheet Steel |
| Rotor Surface | Unpainted |
| Direction of Rotation | Clockwise (Viewed Toward Rotor) |
| Installation Position | Any |
| Condensation Drainage Holes | None |
| Standards & Compliance | EN 60335-1, CE, CCC, EAC |
Applications
ebm-papst R2E180-BD52-06 unhoused backward-curved centrifugal motorized impellers are engineered for pressurized plenum and ducted air-handling assemblies requiring compact axial depth and corrosion-resistant stainless steel blades. Common OEM and MRO installations include precision cabinet cooling units, cleanroom Fan Filter Units (FFUs), commercial heat recovery ventilation (HRV) modules, laboratory extraction hoods, and industrial drying or curing equipment. Its versatile all-position mounting and quick-connect flat receptacle harness make it a direct drop-in replacement for thermal management subsystems inside power electronics enclosures, medical sterilizers, and automated manufacturing machinery.