Description
ebm-papst R1G280-AE17-44 (also known as R1G280AE1744,) is a single-inlet, unhoused backward-curved EC centrifugal motorized impeller powered by an integrated M1G074-CF external-rotor motor, measuring Ø280 mm × 125 mm (11.02 in × 4.92 in). Operating across a wide 36 to 60 VDC telecom bus range (rated at 54 VDC nominal / 48 VDC battery system), it delivers 1106.53 CFM (1880 m³/h) of free-air airflow at 1860 RPM while drawing 120 W (2.60 A), and reaches up to 1121.25 CFM (1905 m³/h) and 1.205 in H₂O (300 Pa) of static pressure at 60 VDC. Engineered for harsh outdoor and industrial environments, this 11-blade black-coated sheet-steel impeller features Telcordia GR-487-CORE salt-fog resistance, IP44 ingress protection, F4-1 humidity rating, and maintenance-free ball bearings. Closed-loop thermal management is supported via a 4-wire AWG 20 lateral lead cable providing 0–10 VDC / PWM speed control, a 2-pulse/rev tachometer output, and fail-safe full-speed operation upon control-line cable break.
Key Features
- Wide-Range Telecom Bus Operation: Runs across 36 to 60 VDC (48/54 VDC nominal), delivering 1106.53 CFM (1880 m³/h) at 1860 RPM.
- High Back-Pressure Impeller Geometry: Single-inlet 11-blade backward-curved sheet-steel wheel sustains up to 1.161 in H₂O (289 Pa) at 54 VDC.
- Telcordia GR-487 Salt-Fog Durability: Black-coated steel rotor and impeller meet Telcordia GR-487-CORE salt-fog standards with IP44 and F4-1 humidity protection.
- 0–10 VDC & PWM Speed Control: Yellow control lead accepts 1–10 V analog or 1–10 kHz PWM signals with fail-safe 100% speed cable-break detection.
- Closed-Loop Tachometer Feedback: White signal wire outputs 2 pulses per revolution (max. 10 mA sink) for continuous PLC or controller speed monitoring.
- Comprehensive Electronic Protection: Integrated motor current limiting, locked-rotor protection, and reverse-polarity safeguard ensure reliable S1 continuous duty from -25°C to +60°C.
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | R1G280-AE17-44 |
| Alternate Part Number | R1G280AE1744 |
| OEM Item Number | 50822-5-9980 |
| Integrated Motor Model | M1G074-CF |
| Product Series | R1G280 Series |
| Product Category | EC Centrifugal Fans |
| Fan / Component Type | Single-Inlet Backward-Curved Motorized Impeller (Unhoused) |
| Motor Design / Technology | Electronically Commutated (EC) External-Rotor DC Motor |
| Rated Voltage | 54 VDC (48 VDC Nominal Telecom System, Max. 3.5% Residual Ripple) |
| Operating Voltage Range | 36 to 60 VDC |
| Speed (RPM) | 1860 RPM (Nominal Free Air at 54 VDC) / 1890 RPM (at 60 VDC) / 1765 RPM (at 48 VDC) |
| Power Rating | 120 W (Free Air at 54 VDC) / 101 W (Free Air at 48 VDC) |
| Max. Input Power | 131 W (at 54 VDC Load) / 150 W (at 60 VDC Load) |
| Rated Current | 2.60 A (Free Air at 54 VDC) / 2.41 A (Free Air at 48 VDC) |
| Max. Current Draw | 2.99 A (at 54 VDC Load) / 3.21 A (at 60 VDC Load) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 1106.53 CFM (1880 m³/h) at 54 VDC / 1121.25 CFM (1905 m³/h) at 60 VDC / 1038.85 CFM (1765 m³/h) at 48 VDC |
| Operating Duty Point Airflow (54 VDC) | 882.87 CFM (1500 m³/h) at 0.378 in H₂O (94 Pa, 1725 RPM, 126 W) / 629.78 CFM (1070 m³/h) at 0.739 in H₂O (184 Pa, 1650 RPM, 131 W) / 347.26 CFM (590 m³/h) at 1.161 in H₂O (289 Pa, 1770 RPM, 124 W) |
| Operating Duty Point Airflow (60 VDC) | 909.36 CFM (1545 m³/h) at 0.402 in H₂O (100 Pa, 1770 RPM, 141 W) / 656.27 CFM (1115 m³/h) at 0.804 in H₂O (200 Pa, 1710 RPM, 150 W) / 353.15 CFM (600 m³/h) at 1.205 in H₂O (300 Pa, 1810 RPM, 136 W) |
| Operating Duty Point Airflow (48 VDC) | 832.84 CFM (1415 m³/h) at 0.338 in H₂O (84 Pa, 1640 RPM, 106 W) / 597.41 CFM (1015 m³/h) at 0.671 in H₂O (167 Pa, 1570 RPM, 110 W) / 326.66 CFM (555 m³/h) at 1.029 in H₂O (256 Pa, 1680 RPM, 104 W) |
| Operating Duty Point Airflow (36 VDC) | 891.70 CFM (1515 m³/h) at 0 Pa (1520 RPM, 64 W) / 723.95 CFM (1230 m³/h) at 0.257 in H₂O (64 Pa) / 523.84 CFM (890 m³/h) at 0.510 in H₂O (127 Pa) / 282.52 CFM (480 m³/h) at 0.776 in H₂O (193 Pa) |
| Max. Static Pressure | 1.161 in H₂O (289 Pa) at 54 VDC / 1.205 in H₂O (300 Pa) at 60 VDC / 1.029 in H₂O (256 Pa) at 48 VDC |
| Airflow Direction | Axial Intake, Radial Discharge (Single Inlet) |
| Ingress Protection (IP) | IP44 |
| Moisture / Environmental Class | Humidity Class F4-1; Salt-Fog Resistant per Telcordia GR-487-CORE (Release No. 2) |
| Operating Temperature | -25°C to +60°C (-13°F to +140°F) |
| Storage Temperature | -40°C to +80°C (-40°F to +176°F) |
| Motor & Drive Protection | Motor Current Limit, Reverse Polarity Protection, Locked-Rotor Protection, Control-Line Cable Break Detection (100% Speed Fail-Safe) |
| Insulation Class | Class B |
| Control / Signal Features | 0–10 VDC Analog / PWM Speed Control Input (1–10 kHz, Safe Start at 4 V or 40% PWM); Speed Monitoring Tachometer Output (2 Pulses/Rev, Isink max = 10 mA) |
| Termination Type | 4-Wire Connection Cable with Crimped Brass Lead Tips (Lateral Exit) |
| Lead Wire Gauge & Spec | AWG 20 |
| Cable / Lead Length | 450 ±20 mm (17.72 ±0.79 in), Stripped 35 mm (1.38 in) |
| Wiring Pinout / Connection | Conn. 1 (Red): Un +48/54 VDC Supply | Conn. 2 (Yellow): PWM/Lin Control Input (0–10 V) | Conn. 3 (White): Tach Output | Conn. 4 (Blue): GND (Reference Mass) |
| Impeller Size | Ø280 mm (11.02 in) |
| Dimensions (Ø × D) | Ø280 mm × 125 ±1 mm (11.02 in × 4.92 ±0.04 in); Impeller Depth: 111.7 mm (4.40 in) |
| Weight | 3.04 kg (6.70 lbs) |
| Blade Count & Geometry | 11 Backward-Curved Blades |
| Bearing Type | Ball Bearing |
| Impeller / Blade Material | Sheet Steel, Coated in Black |
| Rotor / Surface Finish | Coated in Black |
| Direction of Rotation | Clockwise (Viewed Toward Rotor) |
| Installation Position | Any |
| Condensation Drainage Holes | None |
| Mounting Hole Pitch | Ø58 ±0.15 mm (2.28 in) Bolt Circle (4 × M4 Threaded Holes) |
| Max. Screw Clearance | 6 mm (0.24 in) |
| Compatible Inlet Ring (Optional) | Inlet Nozzle Part No. 96360-2-4013 (Sold Separately) |
| EMC Standards | Immunity: EN 61000-6-2 (Industrial Environment); Emission: EN 55022 (Class B) |
| Standards & Compliance | UL 1004-1, CSA C22.2 No. 77, CCC, Telcordia GR-487-CORE |
Applications
ebm-papst R1G280-AE17-44 backward-curved EC centrifugal motorized impellers are engineered for high-static-pressure air movement in outdoor telecommunications base stations, roadside 5G/LTE radio enclosures, and battery backup cabinets. Their salt-fog-resistant construction and direct DC-bus compatibility make them ideal for air-to-air heat exchangers, free-cooling filter plenums, and coastal or industrial power electronics cabinets exposed to corrosive moisture. In mission-critical OEM installations and MRO retrofits, the integrated analog/PWM speed control and tachometer feedback allow environmental controllers to modulate airflow dynamically while maintaining fail-safe full-speed cooling if a control wire is severed.