Description
ebm-papst K3G250-RE07-07 (also known as K3G250RE0707) is a single-intake, backward-curved RadiCal EC centrifugal fan module with an integrated housing and an M3G055-DF brushless EC motor sized around a 250 mm (9.84 in) impeller. Operating on single-phase 230 VAC (200 to 240 VAC, 50/60 Hz) power, it delivers up to 840 CFM (1430 m³/h) of free-air volume flow and 500 CFM (850 m³/h) at 1.45 in H₂O (360 Pa) under nominal maximum load at 2510 RPM (170 W, 1.40 A).
Engineered for demanding industrial environments from -25 °C to +60 °C (-13 °F to +140 °F), this 2.7 kg (5.95 lbs) module combines a 7-blade PA plastic impeller and matching PA housing with a die-cast aluminum electronics enclosure and precision ball bearings. It achieves IP54 and H1 moisture protection while offering a galvanic SELV control interface with 0-10 VDC / PWM speed modulation, a 1 pulse/revolution tachometer output, soft start, and comprehensive electronic thermal and voltage protection via dual PVC wire harnesses with crimped splices.
Key Features
- High-Efficiency RadiCal Aerodynamics: Delivers 840 CFM (1430 m³/h) free-air flow and 2.01 in H₂O (500 Pa) peak static pressure.
- ErP Directive Over-Compliance: Achieves 57.8% overall static efficiency and N = 76.7 efficiency grade via integrated EC drive technology.
- Galvanically Isolated SELV Control: Supports stepless 0-10 VDC or PWM speed adjustment, +10 VDC auxiliary supply, and open-collector tachometer output.
- Comprehensive Active Motor Protection: Incorporates soft start, power and current limitation, thermal overload protection, and line overvoltage and undervoltage detection.
- Rugged IP54 & H1 Construction: Combines a thick-film passivated rotor, die-cast aluminum electronics housing, and 7-blade PA plastic impeller Assembly.
- Dual Pre-Terminated Wire Harnesses: Equipped with variable-exit AWG20 mains leads (3x crimped splices) and AWG22 control leads (4x crimped splices).
Technical Specifications
| Manufacturer | ebm-papst |
|---|---|
| Manufacturer Part Number (MPN) | K3G250-RE07-07 |
| Alternate Part Number | K3G250RE0707 |
| OEM Item Number | 52679-5-9980 |
| Integrated Motor Model | M3G055-DF |
| Product Series | RadiCal |
| Product Category | EC Centrifugal Fans |
| Fan / Component Type | Backward-Curved Single-Intake EC Centrifugal Module with Housing |
| Motor Design / Technology | Electronically Commutated (EC) Brushless External Rotor Motor with Integrated Variable Speed Drive |
| Phase & Supply Type | 1~ (Single-Phase AC Input) |
| Rated Voltage | 230 VAC |
| Operating Voltage Range | 200 to 240 VAC |
| Frequency | 50 / 60 Hz |
| Speed (Max. Load) | 2510 RPM (Nominal Point 3 at 360 Pa) |
| Free-Air Speed (RPM) | 2650 RPM (Point 1 at 0 Pa) |
| Intermediate Curve Speed (Point 2) | 2625 RPM (at 200 Pa) |
| Max. Pressure Speed (Point 4) | 2650 RPM (at 500 Pa) |
| ErP Optimum Speed (RPM) | 2535 RPM (at 380 Pa) |
| Part-Load Reference Curve Speeds | 2400 RPM (Points 5–8), 2000 RPM (Points 9–12), 1600 RPM (Points 13–16) |
| Power Rating (Max. Load) | 170 W (Nominal Points 2 & 3) |
| Free-Air Power Input | 143 W (Point 1 at 0 Pa) |
| Max. Pressure Power Input (Point 4) | 168 W (at 500 Pa) |
| ErP Optimum Efficiency Power | 160 W (0.16 kW at 380 Pa) |
| Part-Load Power Input (at 2400 RPM) | 105 W (0 Pa), 130 W (167 Pa), 143 W (322 Pa), 124 W (409 Pa) |
| Part-Load Power Input (at 2000 RPM) | 61 W (0 Pa), 75 W (116 Pa), 83 W (224 Pa), 72 W (284 Pa) |
| Part-Load Power Input (at 1600 RPM) | 31 W (0 Pa), 39 W (74 Pa), 43 W (143 Pa), 37 W (182 Pa) |
| Rated Current (Max. Load) | 1.40 A (Nominal Points 2 & 3) |
| Free-Air Current Draw | 1.18 A (Point 1 at 0 Pa) |
| Max. Pressure Current Draw (Point 4) | 1.39 A (at 500 Pa) |
| Part-Load Current Draw (at 2400 RPM) | 0.87 A (0 Pa), 1.08 A (167 Pa), 1.19 A (322 Pa), 1.03 A (409 Pa) |
| Part-Load Current Draw (at 2000 RPM) | 0.51 A (0 Pa), 0.62 A (116 Pa), 0.69 A (224 Pa), 0.60 A (284 Pa) |
| Part-Load Current Draw (at 1600 RPM) | 0.26 A (0 Pa), 0.32 A (74 Pa), 0.35 A (143 Pa), 0.31 A (182 Pa) |
| Operating Mode / Duty Cycle | S1 (Continuous Duty) |
| Airflow (Max. Free Air) | 840 CFM (1430 m³/h) at 0 in H₂O (0 Pa) [Point 1] |
| Operating Duty Point Airflow (Point 2) | 705 CFM (1200 m³/h) at 0.80 in H₂O (200 Pa) |
| Operating Duty Point Airflow (Max. Load Point 3) | 500 CFM (850 m³/h) at 1.45 in H₂O (360 Pa) |
| Operating Duty Point Airflow (Peak Pressure Point 4) | 295 CFM (500 m³/h) at 2.01 in H₂O (500 Pa) |
| ErP Optimum Efficiency Duty Point | 470.87 CFM (800 m³/h) at 1.53 in H₂O (380 Pa) |
| Part-Load Curve Duty Points (2400 RPM) | 760 CFM (1290 m³/h at 0 Pa); 645 CFM (1095 m³/h at 0.67 in H₂O / 167 Pa); 470 CFM (800 m³/h at 1.29 in H₂O / 322 Pa); 265 CFM (455 m³/h at 1.64 in H₂O / 409 Pa) |
| Part-Load Curve Duty Points (2000 RPM) | 635 CFM (1075 m³/h at 0 Pa); 540 CFM (915 m³/h at 0.47 in H₂O / 116 Pa); 395 CFM (670 m³/h at 0.90 in H₂O / 224 Pa); 220 CFM (380 m³/h at 1.14 in H₂O / 284 Pa) |
| Part-Load Curve Duty Points (1600 RPM) | 505 CFM (860 m³/h at 0 Pa); 430 CFM (730 m³/h at 0.30 in H₂O / 74 Pa); 315 CFM (535 m³/h at 0.57 in H₂O / 143 Pa); 180 CFM (305 m³/h at 0.73 in H₂O / 182 Pa) |
| Max. Static Pressure (Chart Curve) | 2.01 in H₂O (500 Pa) at 295 CFM (500 m³/h) |
| Sound Pressure Level (Max. Load) | 59 dB(A) at 1 m (Nominal Point 3, Intake Side) |
| Free-Air Sound Pressure Level | 70 dB(A) at 1 m (Point 1 at 0 Pa, Intake Side) |
| Intermediate Sound Pressure Level (Point 2) | 64 dB(A) at 1 m (at 200 Pa, Intake Side) |
| Max. Pressure Sound Pressure Level (Point 4) | 65 dB(A) at 1 m (at 500 Pa, Intake Side) |
| Sound Power Level (Max. Load) | 67 dB(A) (Nominal Point 3 per ISO 13347, Intake Side) |
| Free-Air Sound Power Level | 77 dB(A) (Point 1 at 0 Pa per ISO 13347, Intake Side) |
| Intermediate Sound Power Level (Point 2) | 71 dB(A) (at 200 Pa per ISO 13347, Intake Side) |
| Max. Pressure Sound Power Level (Point 4) | 72 dB(A) (at 500 Pa per ISO 13347, Intake Side) |
| ErP Efficiency & Grade (EU 327/2011) | Overall Static Efficiency ηes = 57.8% (2015 Target: 43.1%); Efficiency Grade N = 76.7 (Target: 62); Measurement Category A; Efficiency Category Static; Specific Ratio = 1.00; VSD Integrated (Setup LU-153273) |
| Aerodynamic Test Standard | ISO 5801 Installation Category A (Test Setup LU-154717-1 at ρ = 1.15 kg/m³ ± 2%) |
| Ingress Protection (IP) | IP54 |
| Moisture / Environmental Class | H1 |
| Operating Temperature | -25 °C to +60 °C (-13 °F to +140 °F) |
| Storage Temperature | -40 °C to +80 °C (-40 °F to +176 °F) |
| Motor & Drive Protection | Electronic Motor Protection, Thermal Overload Protection (Electronics & Motor), Power Limiter, Motor Current Limitation, Soft Start, Overvoltage Detection, Line Undervoltage Detection |
| Electrical Protection Class | Class I (With Customer Connection of Protective Earth) |
| Touch Current (IEC 60990) | <= 3.5 mA (Measuring Circuit Fig. 4, TN System) |
| Insulation Class | Class B |
| Control / Signal Features | 0-10 VDC / PWM Control Input (Ri = 100 kΩ), Tachometer Output (Open Collector, 1 Pulse/Rev, Isink max = 10 mA), Fixed +10 VDC +/-3% Auxiliary Output (Imax = 10 mA, Short-Circuit-Proof), SELV Potential Safely Disconnected from Mains |
| Termination Type | Dual PVC Multi-Core Cables with 3x and 4x Crimped Splices |
| Cable Exit Orientation | Variable Cable Exit |
| Lead Wire Gauge & Spec | Power Cable: PVC AWG20 (3x Crimped Splices); Control Cable: PVC AWG22 (4x Crimped Splices) |
| Power Wiring Pinout (Cable 2 – AWG20) | CON10 = L (Black, Mains Phase); CON11 = N (Blue, Neutral Conductor); CON12 = PE (Green/Yellow, Protective Earth Ground) |
| Control Wiring Pinout (Cable 1 – AWG22) | Wire 1 = GND (Blue, SELV Reference Ground); Wire 2 = 0-10V/PWM (Yellow, Control Input Ri = 100 kΩ); Wire 3 = +10 V (Red, Fixed 10 VDC +/-3% Supply, Max. 10 mA); Wire 4 = Tach (White, Open-Collector Tachometer Output, 1 Pulse/Rev) |
| Impeller Size | Ø 250 mm (9.84 in) |
| Weight | 2.7 kg (5.95 lbs) |
| Blade Count & Geometry | 7 Backward-Curved Single-Intake Blades |
| Bearing Type | Ball Bearing |
| Electronics Housing Material | Die-Cast Aluminum |
| Housing / Scroll / Frame Material | PA Plastic (Integrated Module Housing) |
| Impeller / Blade Material | PA Plastic |
| Rotor Surface | Thick-Film Passivated |
| Direction of Rotation | Clockwise, Viewed Toward Rotor |
| Installation Position | Any |
| Condensation Drainage Holes | None (Open Rotor) |
| EMC Standards | Immunity: EN 61000-6-2 (Industrial Environment); Emission: EN 61000-6-4 (Industrial Environment) |
| Standards & Compliance | EN 60335-1, CE, UL 1004-7 + 60730, C22.2 No. 77 + CAN/CSA-E60730-1, EAC, CCC |
Applications
ebm-papst K3G250-RE07-07 backward-curved RadiCal EC centrifugal fan modules are engineered for drop-in integration inside modular air handling units (AHUs), commercial heat recovery ventilation (HRV) systems, and cleanroom fan filter units (FFUs). Their compact single-intake guide housing and resistance to elevated static back pressure make them ideal for data center precision cooling plenums, ducted building ventilation boxes, and enclosed power electronics cabinets. OEM system builders and facility MRO teams rely on this variable-speed centrifugal module for demand-controlled airflow regulation and closed-loop building management system (BMS) monitoring across industrial process cooling and HVAC installations.