D2E133-AM47-01 ebm-papst 230VAC 133mm AC Dual-Inlet Blower

$456.74

ebm-papst D2E133-AM47-01 (D2E133AM4701) 230VAC Ø133mm dual-inlet blower, 1500/1800RPM, 417.9CFM (710m³/h), 190/200W, with galvanized steel scroll & IP44.

SKU: D2E133-AM47-01 Category: Brand:

Description

ebm-papst D2E133-AM47-01 (also known as D2E133AM4701) is an industrial dual-inlet, forward-curved AC centrifugal scroll blower (without discharge flange) driven by an integrated M2E068-DF external-rotor motor with a 133 mm (5.24 in) impeller inside a compact 170.5 × 180 × 215 mm (6.71 × 7.09 × 8.46 in) scroll housing. Engineered for single-phase 230 VAC operation across 50 Hz and 60 Hz power grids, it delivers 417.89 CFM (710 m³/h) at free air (50 Hz, 1500 RPM, 190 W, 0.84 A) and 332.55 CFM (565 m³/h) against a minimum required back pressure of 100 Pa / 0.401 in H₂O at 60 Hz (1800 RPM, 200 W CE / 210 W UL, 0.88 A / 0.92 A), while reaching up to 275 Pa (1.105 in H₂O) at 50 Hz and 375 Pa (1.507 in H₂O) at 60 Hz along its high-pressure curve.

Built for continuous S1 duty in demanding commercial and industrial ventilation environments, the blower features a hot-galvanized sheet steel volute housing and forward-curved dual-intake impeller paired with precision ball bearings and a one-side bracket-mounted motor suspension. It incorporates an internally wired thermal overload protector (TOP), Class B insulation, IP44 ingress protection, and an axial-exit PVC power cable terminated with four crimped brass lead tips for reliable OEM integration.

Key Features

  • Dual-Inlet Forward-Curved Aerodynamics: Delivers 417.89 CFM (710 m³/h) at 50 Hz free air and 332.55 CFM (565 m³/h) at 60 Hz (100 Pa).
  • High-Pressure Scroll Performance: Generates static pressure up to 1.105 in H₂O (275 Pa) at 50 Hz and 1.507 in H₂O (375 Pa) at 60 Hz.
  • Hot-Galvanized Steel Construction: Corrosion-resistant hot-galvanized sheet steel scroll housing (without flange) and dual-inlet forward-curved impeller.
  • Integrated M2E068-DF External-Rotor Drive: Bracket-mounted 230 VAC motor with ball bearings and 3 µF / 450 VDB UL-rated run capacitor system.
  • Internal Thermal Overload Protection: Built-in internally wired TOP sensor, Class B winding insulation, Class I grounding, and IP44 environmental sealing.
  • Pre-Terminated Axial Harness: Equipped with an axial-exit PVC cable featuring 4x crimped brass lead tips (U1/Z/U2/PE) for rapid wiring.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) D2E133-AM47-01
Alternate Part Number D2E133AM4701
OEM Item Number 10430-5-9980 (Revision KM66668)
Integrated Motor Model M2E068-DF
Product Series D2E133
Product Category AC Blower Fans
Fan / Component Type AC Dual-Inlet Forward-Curved Centrifugal Scroll Blower (With Housing, Without Flange)
Motor Design / Technology Single-Phase AC External-Rotor Capacitor-Run Induction Motor
Phase & Supply Type 1~ (Single-Phase AC)
Rated Voltage 230 VAC
Frequency 50 / 60 Hz
Free-Air Speed (RPM) 1500 RPM (50 Hz at 0 Pa Free Air)
Speed (Max. Load) 1800 RPM (60 Hz CE & UL 2111 at 100 Pa Min. Back Pressure)
High-Pressure Curve Speed (RPM) 1890 to 2570 RPM (50 Hz at 102–275 Pa) / 2310 to 2945 RPM (60 Hz at 200–375 Pa)
Free-Air Power Input 190 W (50 Hz CE at 0 Pa Free Air)
Power Rating (Max. Load) 200 W (60 Hz CE at 100 Pa) / 210 W (60 Hz UL 2111 at 100 Pa)
High-Pressure Curve Power Input 164 W to 118 W (50 Hz at 102–275 Pa) / 181 W to 159 W (60 Hz at 200–375 Pa)
Free-Air Current Draw 0.84 A (50 Hz CE at 0 Pa Free Air)
Rated Current (Max. Load) 0.88 A (60 Hz CE at 100 Pa) / 0.92 A (60 Hz UL 2111 at 100 Pa)
High-Pressure Curve Current Draw 0.72 A to 0.52 A (50 Hz at 102–275 Pa) / 0.78 A to 0.70 A (60 Hz at 200–375 Pa)
Run Capacitor 3 µF, 450 VDB (UL Standard)
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air) 417.89 CFM (710 m³/h) at 0 Pa (50 Hz, Curve LU-105263 Pt. 1)
Operating Duty Point Airflow (50 Hz Curve LU-105263) 376.69 CFM (640 m³/h) at 0.410 in H₂O (102 Pa, Pt. 2); 270.75 CFM (460 m³/h) at 0.804 in H₂O (200 Pa, Pt. 3); 173.63 CFM (295 m³/h) at 1.105 in H₂O (275 Pa, Pt. 4)
Operating Duty Point Airflow (60 Hz Curve LU-105265) 332.55 CFM (565 m³/h) at 0.401 in H₂O (100 Pa, Pt. 1 Max. Load); 250.15 CFM (425 m³/h) at 0.804 in H₂O (200 Pa, Pt. 2); 176.57 CFM (300 m³/h) at 1.206 in H₂O (300 Pa, Pt. 3); 105.94 CFM (180 m³/h) at 1.507 in H₂O (375 Pa, Pt. 4)
Min. Back Pressure 0 Pa (50 Hz) / 100 Pa (0.401 in H₂O at 60 Hz)
Max. Static Pressure (Tested Curve Point) 1.105 in H₂O (275 Pa at 50 Hz, Pt. 4) / 1.507 in H₂O (375 Pa at 60 Hz, Pt. 4)
Sound Pressure Level 55.0 dB(A)
Ingress Protection (IP) IP44 (Depending on Installation and Position)
Moisture / Environmental Class F0
Operating Temperature -40 °C to +35 °C (-40 °F to +95 °F at 50 Hz) / -40 °C to +25 °C (-40 °F to +77 °F at 60 Hz)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal Overload Protector (TOP) Wired Internally
Electrical Protection Class Class I (With Protective Earth Ground)
Touch Current (IEC 60990) < 0.75 mA
Insulation Class Class B
Termination Type PVC Connection Cable with 4x Crimped Brass Lead Tips (4 Wire Leads)
Cable Exit Orientation Axial
Wiring Pinout / Connection U1 = Blue, Z = Brown, U2 = Black, PE = Green/Yellow
Impeller Size Ø 133 mm (5.24 in)
Dimensions (L × H × W) 170.5 × 180.0 × 215.0 mm (6.71 × 7.09 × 8.46 in) Scroll Housing
Weight 3.48 kg (7.67 lbs)
Blade Geometry Forward-Curved Dual-Inlet Centrifugal Impeller
Bearing Type Ball Bearing
Motor Suspension Motor Mounted via Brackets on One Side
Housing / Scroll Material Hot-Galvanised Sheet Steel (Without Flange)
Impeller / Blade Material Hot-Galvanised Sheet Steel
Rotor Surface Partially Cast in Aluminium
Direction of Rotation Clockwise (Seen on Rotor)
Installation Position Any
Condensation Drainage Holes None
Standards & Compliance CE, EN 60335-1, UL 2111, CCC
RoHS / Environmental Compliance RoHS3 Compliant

Applications

ebm-papst D2E133-AM47-01 dual-inlet forward-curved centrifugal scroll blowers are engineered for high-pressure ducted airflow in commercial HVAC air handling units (AHUs), variable air volume (VAV) terminal boxes, fan coil units, and doorway air curtains. Their compact galvanized steel volute housing and dual-intake geometry make them ideal for industrial drying and curing ovens, reflow soldering tunnels, printing and packaging machinery, and laboratory fume extraction plenums. Designed to overcome significant ductwork and filter resistance, this blower provides dependable OEM integration and drop-in MRO replacement in continuous-duty process heating, cooling, and cabinet pressurization systems.