A6D800-AD01-01 ebm-papst 400VAC 800mm AC Axial Fan

$425.00

ebm-papst A6D800-AD01-01 (A6D800AD0101) 400VAC 800mm HyBlade AC axial fan, 880/670RPM, 24110m³/h, 1940W, with TOP thermal protection & IP54.

SKU: A6D800-AD01-01 Category: Brand:

Description

ebm-papst A6D800-AD01-01 (also known as A6D800AD0101) is an 800 mm (31.5 in) AC axial fan from the HyBlade® sickled-blade S series, built around the integrated M6D138-LA three-phase motor and designed for terminal-box wiring in Delta or Star connection at 400 VAC, 50 Hz. In Delta it delivers 880 RPM, 1940 W, 3.9 A and up to 24,110 m³/h (14,197 CFM) free-air flow with 160 Pa maximum back pressure, while Star connection derates it to 670 RPM, 1210 W, 2.23 A and 92 Pa for lower-duty installations. Construction pairs a cast aluminium rotor surface with aluminium-sheet blades sprayed in PP plastic, ball bearings, IP 54 ingress protection, Class F insulation and a brought-out thermal overload protector (TOP). It is protection Class I with axial cable exit, S1 continuous duty, and complies with EN 60034, EN 61800-5-1, CE and VDE.

Key Features

  • HyBlade® Sickled Impeller: Five aluminium-sheet blades PP-sprayed on cast aluminium rotor for high-efficiency large-diameter airflow.
  • Dual Delta / Star Connection: Field-selectable 880 RPM high-output or 670 RPM derated operating point at 400 VAC 50 Hz.
  • High-Volume Air Performance: Up to 24,110 m³/h (14,197 CFM) free air with 160 Pa maximum back pressure per ISO 5801.
  • TOP Thermal Motor Protection: Brought-out thermal overload protector contacts wired via two grey leads for customer monitoring.
  • Rugged Industrial Construction: IP 54, Class F insulation, F3-1 humidity class, ball bearings and S1 continuous duty rating.
  • All-Position Installation: Any mounting position with condensate discharge holes on both rotor and stator sides.
  • Terminal Box Wiring: Axial cable exit supporting 7–14 mm cable diameter with defined tightening torques and VDE approval.

Technical Specifications

Manufacturer ebm-papst
Manufacturer Part Number (MPN) A6D800-AD01-01
Alternate Part Number A6D800AD0101
OEM Item Number 10510-5-9980 (Revision 76656, Release 2026-04-05)
Integrated Motor Model M6D138-LA
Product Series A6D800 HyBlade® S Series (sickled blades)
Product Category AC Axial Fans
Fan / Component Type AC axial fan, HyBlade® sickled-blade impeller
Motor Design / Technology Three-phase asynchronous motor, external rotor
Phase & Supply Type 3~ (three-phase AC)
Rated Voltage 400 VAC
Frequency 50 Hz
Connection Type Delta (Δ) or Star (Y), selectable via terminal box
Speed (RPM, Delta, Max. Load) 880 min⁻¹
Speed (RPM, Star, Max. Load) 670 min⁻¹
Free-Air Speed (RPM, Delta) 925 min⁻¹
Free-Air Speed (RPM, Star) 780 min⁻¹
ErP Optimum Speed (RPM) 905 min⁻¹
Power Rating (Delta, Max. Load) 1940 W
Power Rating (Star, Max. Load) 1210 W
Free-Air Power Input (Delta) 1380 W
Free-Air Power Input (Star) 1000 W
ErP Optimum Efficiency Power 1.72 kW
Rated Current (Delta, Max. Load) 3.90 A
Rated Current (Star, Max. Load) 2.23 A
Free-Air Current Draw (Delta) 3.30 A
Free-Air Current Draw (Star) 1.85 A
Inrush / Starting Current (Delta) 13 A
Inrush / Starting Current (Star) 4.3 A
Operating Mode / Duty Cycle S1 (Continuous Duty)
Airflow (Max. Free Air, Delta) 24,110 m³/h (14,197 CFM) at 0 Pa
Airflow (Max. Free Air, Star) 20,430 m³/h (12,015 CFM) at 0 Pa
Operating Duty Point Airflow (Delta, Intermediate) 20,850 m³/h (12,272 CFM) at 60 Pa (0.241 in H₂O)
Operating Duty Point Airflow (Delta, Max. Load) 13,450 m³/h (7,918 CFM) at 160 Pa (0.642 in H₂O)
Operating Duty Point Airflow (Star, Intermediate) 16,980 m³/h (9,997 CFM) at 40 Pa (0.161 in H₂O)
Operating Duty Point Airflow (Star, Max. Load) 10,250 m³/h (6,032 CFM) at 92 Pa (0.369 in H₂O)
ErP Optimum Efficiency Duty Point 17,215 m³/h (10,127 CFM) at 124 Pa (0.498 in H₂O)
Max. Static Pressure (Chart Curve) 240 Pa (0.965 in H₂O)
Max. Back Pressure (Delta) 160 Pa (0.642 in H₂O)
Max. Back Pressure (Star) 92 Pa (0.369 in H₂O)
Sound Pressure Level (Intake, Delta, Max. Load) 70 dB(A)
Sound Pressure Level (Intake, Delta, Free Air) 65 dB(A)
Sound Pressure Level (Intake, Star, Max. Load) 62 dB(A)
Sound Pressure Level (Intake, Star, Free Air) 61 dB(A)
Sound Power Level (Intake, Delta, Max. Load) 77 dB(A)
Sound Power Level (Intake, Delta, Free Air) 72 dB(A)
Sound Power Level (Outlet, Delta, Max. Load) 76 dB(A)
Sound Power Level (Outlet, Delta, Free Air) 72 dB(A)
Sound Power Level (Intake, Star, Max. Load) 70 dB(A)
Sound Power Level (Intake, Star, Free Air) 68 dB(A)
Sound Power Level (Outlet, Star, Max. Load) 69 dB(A)
Sound Power Level (Outlet, Star, Free Air) 67 dB(A)
ErP Efficiency & Grade (EU 327/2011) Overall static efficiency ηes 35.2% (Request 2013: 31.2%, Request 2015: 35.2%), Efficiency grade N 40 (36 / 40)
ErP Measurement Category Installation category A, specific ratio 1.00, no variable speed drive
Airflow Direction “V” (direction of air flow per drawing)
Ingress Protection (IP) IP 54
Moisture / Environmental Class F3-1
Operating Temperature -40 °C to +60 °C (-40 °F to +140 °F)
Storage Temperature -40 °C to +80 °C (-40 °F to +176 °F)
Motor & Drive Protection Thermal overload protector (TOP) brought out to terminal box
Electrical Protection Class Class I (if protective earth is connected by customer)
Touch Current (IEC 60990) <= 3.5 mA (measuring network Fig. 4, TN system)
Insulation Class Class F
Termination Type Terminal box (PP plastic)
Cable Exit Orientation Axial cable exit
Cable Diameter Range min. 7 mm (0.276 in), max. 14 mm (0.551 in)
Cable Gland Tightening Torque 2 ± 0.3 Nm
Wiring Pinout / Connection Delta: L1 = U1 black, L2 = V1 blue, L3 = W1 brown; Star: W2 yellow, U2 green, V2 white; TOP 2 x grey; PE green/yellow
Impeller Size Ø800 mm (Ø31.5 in)
Weight 24 kg (52.9 lbs)
Blade Count & Geometry 5 sickled HyBlade® blades, blade angle 0°
Bearing Type Ball bearing
Housing / Terminal Box Material Terminal box: PP plastic
Impeller / Blade Material Aluminium sheet insert, sprayed with PP plastic
Rotor Surface Cast in aluminium
Direction of Rotation Clockwise, seen on rotor
Installation Position Any mounting position
Condensation Drainage Holes On rotor and stator sides
Max. Screw Depth (Mounting) 18 mm (0.709 in)
Mounting Screw Tightening Torque 1.5 ± 0.2 Nm
Standards & Compliance CE, EN 60034, EN 61800-5-1, VDE approval, ErP directive

Applications

ebm-papst A6D800-AD01-01 is a large-diameter industrial AC axial fan deployed where very high air volumes must be moved against moderate system resistance. Typical equipment includes air handling units, condenser and dry cooler arrays, industrial process cooling towers, agricultural and livestock ventilation tunnels, wind tunnel and test rigs, and large power electronics cabinets in OEM machinery builds. MRO teams also specify it as a drop-in replacement fan for retrofitting evaporator and refrigeration condenser banks, mining and tunnel ventilation modules, and heavy-duty drying or paint booth exhaust systems.